4.3.2.2
Selection “Flashing”
The parameter window in Fig. 4.7 “X: Time-flashing” will be shown up when selecting “flashing” in the
parameter “Type of time function”. The flashing switch function is mainly used for lamp aging test.
Fig. 4.7 parameter window “X
1,2
: Time-flashing”
The flashing switch can be started via the object “Flashing function”. It is able to set the flashing time in
“Delay for switch on” or “Delay for switch off”, which will restart the flashing when receiving the start flashing
telegram, and define the contact position after flashing.
Parameter
“
Delay for switch on: (0...240Min), (0...59s)
”
The parameter defines the duration time of switch on the output when flashing.
Options:
0...240 min
0...59 s
Note: it will not be executed unless the time is lower than the relay threshold switch frequency. Since there
will be not sufficient energy to do it because of the frequent relay switching, and it may cause the time delay. The
same situation will happen after the bus voltage recovery.
Parameter
“
Delay for switch off: (0...240Min), (0...59s)
”
The parameter defines the duration time of switch off the output when flashing. Options:
0...240 min
0...59 s
Note: it will not be executed unless the time is lower than the relay threshold switch frequency. Since there
will be not sufficient energy to do it because of the frequent relay switching, and it may cause the time delay. The
same situation will happen after the bus voltage recovery.
Parameter
“
Number of ON-impulses (1...255
,
0=no limited)
”