K-BUS
○
R
KNX/EIB
Switch Blind Actuator
30
www.video-star.com.cn
Tel.
:(
8620
)
39338986
Fax
:(
8620
)
39338465
receives a telegram
“
0
”
, the Shutter is moved to the top; the object receives a telegram
“
1
”
, the Shutter is
moved to the bottom. If the option
“
move to save position
”
is selected, the object receives a telegram
“
0
”
, the
Shutter is moved to the top, then back to its original position; the object receives a telegram
“
1
”
, the Shutter is
moved to the bottom, then back to its original position.
The Shutter actuator continually determines the current position of the Shutter as well as the angle position of
the slat using the duration of individual movements. Over longer periods, slight inaccuracies may occur when
determining the position due to temperature variations and aging processes. Therefore the Shutter actuator uses the
upper and lower limit positions to clearly define the current position of the Shutter. Each time that the Shutter is in
the upper or lower limit position, the position is updated in the memory of the Shutter actuator.
If the limit positions have not been reached during normal operation, a reference movement can be triggered
via a bus telegram to move the Shutter right to the top or right to the bottom. Depending on the parameter settings,
the Shutter either remains in the reference position after the reference movement or moves back into the saved
position.
Parameter
“
position of slat after arriving on lower end position
”
The parameter can set the slat positions of slat after the lower end position is reached. Options:
0%/10%/…/90%/100%
For example, if select
“
40%
”
, when the object
“
Shutter UP/DOWN
”
receives a telegram
“
1
”
, the
shutter will move to the lower end position, then the slat positions are adjusted to 40%.
Note: the parameter only relates to the
“
Down
”
reaction (the parameter option with
“
Down
”
), the safety
operation and the percentage value control way are not affected for the parameter.
Parameter “When blind is under end position, up/down object function is”
The parameter defines whether the blind still can be moved via the object “shutter/blind up/down” when the
blind is under end position. Options
:
Disable
Enable
If select “
disable
”
,
It can not be moved
。
If select “
enable
”
,
It can be moved
,
and the running time is the total move time.
Parameter
“
Set response mode for position
”
The parameter defines the response mode for shutter position. Options:
Respond after read only
respond after change
If select“
Respond after read only
”,only when the device receive the current shutter position from other bus
devices or the bus read the current shutter position,object “Shutter position status/slat position status”send the