4. Parameter setting description in ETS
The parameters will be described in the form of the function interfaces.
4.1
Parameter window “General”
Parameter window “General” can be shown in fig.4.1. Here set some general parameters, that applies to the
curtain output, also applies to the switch output.
Fig. 4.1 Parameter Window “General”
Parameter “Operation delay after power voltage recovery [5…250s]”
The parameter defined the delay time that scan and relay operation after bus voltage recovery. No operation
will be executed before the scan and relay operation delay finished, the operation during this process will be
recorded and executed after the delay over. Meanwhile, telegrams sent during the scan delay will be recorded and
executed after the delay.
The delay time here does not include the initiation time of the device, normally it will take 3 seconds to
re-initiate the device after power voltage recovery. I.e the delay will start counter after the initiation time.
Note: During delay, the programming LED is on green , and the device can not be operated. After delay over,
the LED will flash green, and the device can be operated.
Parameter “
Sending cycle
of
‘in operation’ telegram (1...240s, 0 = inactive):
”
The parameter determines the time interval to send the telegram which shows the actuator is working normally
or not via the bus. With the setting “
0
”, the actuator doesn’t send the telegram; if the setting is not “
0
”, a telegram