Specifications
ipacl
enters cmd group "ipacl"
ipacl ping enabled set {OFF=0|ON=1}
enables ICMP ping on/off
ipacl ping enabled show
show s if ICMP ping enabled
ipacl enabled set {OFF=0|ON=1}
enable IP filter on/off
ipacl enabled show
show s if IP filter enabled
ipacl filter {ipacl_num} set "{dns_name}"
sets IP filter {ipacl_num}
ipacl filter {ipacl_num} show
show s IP filter {ipacl_num}
linesensor
enters cmd group "linesensor"
linesensor all {field_list} show
show s energy sensors according field list of all
line sensors
5
linesensor {line_num} {energy_sensor} value
show
show s energy sensor of given line
5
linesensor {line_num} ovp show
show state of Overvoltage Protection
linesensor {line_num} counter reset
resets energy metering counter
linesensor {line_num} label set "{name}"
sets line meter to label
linesensor {line_num} label show
show s label of line meter
linesensor {line_num} {energy_sensor} events
set {OFF=0|ON=1}
enables events on/off
linesensor {line_num} {energy_sensor} events
show
show s if events are enabled
linesensor {line_num} {energy_sensor} events
type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2,E
VT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER=5}"
enables different event types
linesensor {line_num} {energy_sensor} events
type show
show s w hat event types are enabled
linesensor {line_num} {energy_sensor} events
beeper mode set {CONTINOUS=0|
INTERMITTENT=1}
sets beeper tone
linesensor {line_num} {energy_sensor} events
beeper mode show
show s beeper tone
linesensor {line_num} {energy_sensor} maxval
set {float}
sets maximum value for line meter
linesensor {line_num} {energy_sensor} maxval
show
show s maximum value for line meter
linesensor {line_num} {energy_sensor} minval set
{float}
sets minimum value for line meter
linesensor {line_num} {energy_sensor} minval
show
show s minimum value for line meter
linesensor {line_num} {energy_sensor} hyst set
{float}
sets hysterese value for line meter
linesensor {line_num} {energy_sensor} hyst
show
show s hysterese value for line meter
linesensor {line_num} {energy_sensor} publish
mode set {NONE=0|INTERVAL=1|DIFFERENCE=2}
sets publish mode
linesensor {line_num} {energy_sensor} publish
mode show
show s publish mode
linesensor {line_num} {energy_sensor} publish
trigger set {float}
sets trigger value for publish
linesensor {line_num} {energy_sensor} publish
trigger show
show s trigger value for publish
linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port set {port_num}
sets Port for Pow er Port Sw itching actions
linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port show
show s Port for Pow er Port Sw itching actions
linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state set {OFF=0|ON=1|
DISABLED=2}
sets Port state for Pow er Port Sw itching actions
linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state show
show s Port state for Pow er Port Sw itching ac-
tions