Expert Power Control 8291
© 2020 GUDE Systems GmbH
Specifications
and inserted into the Configuation - Console input field. Public keys are accepted in
SSH2 or OpenSSH format.
4.7.2
Push Messages
On the console channels (Telnet, SSH or serial console) push messages can be activ-
ated, which output sensor values in time intervals (every n seconds) or from an ad-
justable change of the sensor value threshold on this channel. The generated message
always starts with a "#" and ends with a CR/LF. This also applies to sensor limit value
messages if "Console" is selected as message channel in Sensors - Configuration.
If you open a Telnet or SSH connection, you can use "console telnet pushmsgs set 1"
or "console ssh pushmsgs set 1" to temporarily activate the push messages. From now
on push messages will be sent asynchronously on this channel. The asynchronicity of
the messages can cause problems on a connection if you send commands yourself.
Then there are the possibilities:
·
Filter all incoming characters between "#" and CR/LF
·
or open a second channel (Telnet, SSH, serial) and activate Push Messages
4.7.3
Console Cmd 8291
Command
Description
Note
logout
go to login prompt w hen enabled
2
quit
quits telnet session - nothing in serial console
2
back
back one cmd level
2
help
show all cmds from this level
2
help all
show all cmds
2
bank
enters cmd group "bank"
bank {bank_num} pow ersrc set {pow ersrc_num} sets pow er src of bank
bank {bank_num} pow ersrc show
show s pow er src of bank
bank pow ersrc all "{field_list}" show
show s pow er src energy sensors of field list for
all banks
bank pow ersrc {pow ersrc_num} "{field_list}"
show
show s pow er src energy sensors of field list for
given bank
bank all "{field_list}" show
show s bank energy sensors of field list for all
banks
bank {bank_num} "{field_list}" value show
show s bank energy sensors of field list for given
bank
bank {bank_num} {energy_sens} events set
{OFF=0|ON=1}
enables sensor events on/off
bank {bank_num} {energy_sens} events show
show s if sensor events are enabled
bank {bank_num} {energy_sens} events type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2,E
VT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER=5,E
VT_DISPLAY=6,EVT_CONSOLE=7}"
enables different event types
bank {bank_num} {energy_sens} events type
show
show s w hat event types are enabled
bank {bank_num} {energy_sens} events beeper sets beeper tone