3. SPECIFICATIONS

DISPLAY

Dot-matrix LCD with back light 
16 characters x 2 line.

GSM Modem

900/1800 MHz, dual band.

Switch inputs

Number

8 inputs

Reaction 

200 mS, min.

time
Status

Default open,
Close will alarm

Analog input

Number

8 channels

4 to 20 mA

Input

125 ohm

impedance
Resolution

12 bits A/D converter

Setting

4 mA. 20 mA setting

by front

Unit setting

buttons

High/Low alarm value 
setting

Relay outputs Number

8 relays

Function

Relay 1 to Relay 7 can 
control by mobile via SMS
Relay 8 is the alarm relay
used to connect to field
alarm system

Max load

1 ACA/250 ACV
1 DCA/24 DCV

Standard

CE conformity

3

Summary of Contents for GSM-888

Page 1: ...GSM CONTROL SYSTEM Model GSM 888 ...

Page 2: ... Analog input 4 20 mA 10 7 2 IO Switch input Relay output 15 7 3 TEL Telephone 17 7 4 RP Ring period 19 7 5 IM Switch input management 20 7 6 SAVE 21 8 SMS COMMAND from MOBILE CONFIRM SMS from SYSTEM ERROR SMS COMMAND ALARM SMS from SYSTEM 22 9 IMPORTANT OPERATION PROCEDURES and CONSIDERATION 31 10 TROUBLE SHOOTING 36 11 UNIT LIST of ANALOG INPUT 38 12 FULL LINE TRANSMITTERS optional 40 ...

Page 3: ...CH1 28 0 C CH2 53 7 RH CH3 7 01 pH CH8 230 5 ACV Setting Analog input alarm High alarm Low alarm to enable or disable via SMS Setting Input switch alarm close alarm to enable or disable via SMS Relay output On Off setting via SMS Dot matrix LCD display show Analog input value Switch input and Relay output status All setting value will be saved into EPROM IC no loss Mobile telephone can call all ch...

Page 4: ... velocity Light Clamp current Load Cell Potential Angle EMF IR UV light Moisture detail please refer the LUTRON Transmitter catalog www lutron com tw 2 APPLICATION Industrial remote monitor controller alarm system Industrial security system Home security system Building supervision Industrial systems Pumping stations Power station Agriculture usage Animal husbandry Water supply systems Traffic sys...

Page 5: ...arm Analog input Number 8 channels 4 to 20 mA Input 125 ohm impedance Resolution 12 bits A D converter Setting 4 mA 20 mA setting by front Unit setting buttons High Low alarm value setting Relay outputs Number 8 relays Function Relay 1 to Relay 7 can control by mobile via SMS Relay 8 is the alarm relay used to connect to field alarm system Max load 1 ACA 250 ACV 1 DCA 24 DCV Standard CE conformity...

Page 6: ...DC 9V Power Less than 400 mA DC consumption Size 193 x 149 x 46 cm 7 6 x 4 9 x 1 8 inch Weight 592 g 1 3 LB Accessories Operation manual 1 PC includes AC 100 240 V DC 9V 1 Amp power adapter 1 PC Antenna 1 PC Accessories Full line 4 to 20 mA industrial optional transmitters refer page 40 4 ...

Page 7: ...3 FRONT PANEL LAYOUT DESCRIPTION Fig 1 Fig 2 5 ...

Page 8: ...Fig 3 Fig 4 6 ...

Page 9: ...9 Numerical buttons 4 10 Decimal button 4 11 button 4 12 button 4 13 button 4 14 SETUP button 4 15 ENTER button 4 16 RESET button 4 17 IP Switch input terminals 4 18 CH Analog input 4 20 mA input terminals 4 19 OP Relay output terminals 4 20 Fix hole for wall installation 4 21 Fix hole for wall installation 4 22 Screws for the SIM card cover 4 23 SIM card holder 4 24 Terminal instruction label 7 ...

Page 10: ...wn mobile to proceed as the instruction manual Note To cancel the PIN code is the necessary procedures otherwise your GSM system will be not working properly 3 To guarantee flawless operation of your GSM Control System ensure that adequate signal strength is permanently to and from your mobile telephone network Check this with your mobile before installation 4 Open the SIM card cover by loosing th...

Page 11: ...dicator and Output indicator The LCD will lit and count down from 90 seconds back to 0 second then present the SETUP SCREEN refer page 10 The Output indicator 4 7 Fig 1 will show the default Relay On Off status if the Relay On the Output indicator will lit The System indicator 4 6 Fig 1 will flash per 1 second On 1 second Off if the CPU Circuit working properly 6 GSM indicator 4 4 Fig 1 a If the G...

Page 12: ... the LCD will show 1 AD 2 IO 3 TEL SETUP SCREEN 4 RP 5 IM 6 SAVE key in 1 LCD will show CH1 4 mA Value CH1 4 mA setting SCREEN xxxx Use the following buttons Numerical buttons 4 9 Fig 1 Decimal button 4 10 Fig 1 button 4 11 Fig 1 button is used to key in minus value to key in the desired channel 1 4 mA value 4 mA real display value For example 4 mA 0 After finish to key in the desired value should...

Page 13: ...ill show CH1 High Limit CH1 High Limit setting SCREEN xxxx Use the buttons 4 9 4 10 Fig 1 to key in the desired channel 1 High Limit value For example High Limit Value 80 0 After finish to key in the desired value should press the ENTER key Press button once again LCD will show CH1 Low Limit CH1 Low Limit setting SCREEN xxxx Use the buttons 4 9 4 10 4 11 Fig 1 to key in the desired channel 1 Low L...

Page 14: ...ired no should press the ENTER key Press button once again LCD will show CHA xxxxxxxx Channel alarm setting SCREEN Enable Use the buttons 4 9 Fig 1 to select if the Analog alarm High limit value alarm Low Limit value alarm is enable or disable x 1 is enable x 0 is disable For example key in Enable 11000000 will set channel 1 channel 2 High Low alarm is enable channel 3 to channel 8 High Low alarm ...

Page 15: ...o Channel 2 Channel 3 Channel 8 setting SCREEN For example CH2 4mA Value CH2 4 mA setting SCREEN xxxx CHx 4mA Value CHx 4 mA setting SCREEN xxxx In the CHx press the button to select a CHx 20mA Value CHx 20 mA setting SCREEN xxxx b CHx High Limit CHx High Limit setting SCREEN xxxx c CHx Low Limit CHx Low Limit setting SCREEN xxxx 13 ...

Page 16: ...ish all channels channel 1 to channel 8 setting procedures it should press SETUP Button to return the SETUP screen 1 AD 2 IO 3 TEL SETUP SCREEN 4 RP 5 IM 6 SAVE Then key in 6 SAVE LCD will show Save OK SETUP Exit Now the Analog input setting 4mA 20mA High limit value Low Limit value Unit Channel alarm enable disable setting are finished all the data will save into the memory circuit permanently Pr...

Page 17: ...o set the Relay On or Off Relay 1 to Relay 8 The Relay 8 is the alarm relay Relay 8 will be On when alarm Analog High alarm Analog Low alarm Switch input alarm happened If the alarm message stop the Relay 8 will Off Relay 8 can not be controlled by key buttons or mobile SMS command no matter Key in the relay 8 status to 1 or 0 For example Setting Output 11000000 or 11000001 will engage the Relay 1...

Page 18: ...Switch 3 to alarm enable Switch 4 to Switch 8 is alarm disable Under the above a b setting function use the buttons 4 9 Fig 1 to select the desired value 0 or 1 After finish to key in the desired no should key in the ENTER key Before finish the e IO setting it should press SETUP Button to return SETUP SCREEN 1 AD 2 IO 3 TEL SETUP SCREEN 4 RP 5 IM 6 SAVE Then key in 6 SAVE LCD will show Save OK SET...

Page 19: ... Use the button to select the TEL setting screen a b c d as a Telephone Num 1 TEL 1 SETTING SCREEN Enter the first mobile telephone no Telephone no starting with country code For example Germany is 49 Taiwan is 886 Hongkong is 852 For example key in 886919562822 b Telephone Num 2 TEL 2 SETTING SCREEN Enter the second mobile telephone no The procedures are same as the above TEL 1 17 ...

Page 20: ... M 1 S Define the second mobile is the Supervisor or Monitor If only need one mobile telephone to control monitor it just key in one telephone no Telephone Num 1 Under the above a b c d screen use the buttons 4 9 4 11 Fig 1 to key in After finish to key in the desired no or function should key in the ENTER button Before finish the e TEL setting it should key in SETUP Button to return the SETUP SCR...

Page 21: ...e system will send alarm SMS per xx minutes typical set 03 3 minutes For example if key in RP new value 03 the alarm SMS message will send per 3 minutes continuously The alarm SMS message will stop when alarm is off or disable After finish to key in the desired value should press the ENTER button Before finish the RP setting it should press SETUP Button once to return the SETUP SCREEN 1 AD 2 IO 3 ...

Page 22: ...is closed send the SMS alarm message out if the switch is opened again the alarm SMS message will stop Pulse alarm type Input switch is normal open if the switch is closed send the SMS alarm message out if the switch is opened again the alarm SMS message will still send continuously no matter the switch open again Under the Pulse alarm type if intend to stop the alarm SMS it should do as 1 From th...

Page 23: ...SETUP Button to return SETUP SCREEN 1 AD 2 IO 3 TEL SETUP SCREEN 4 RP 5 IM 6 SAVE Then key in 6 SAVE LCD will show Save OK SETUP Exit 7 6 SAVE After the system are already change the data value function it should press SETUP Button to return SETUP SCREEN 1 AD 2 IO 3 TEL SETUP SCREEN 4 RP 5 IM 6 SAVE Then key in 6 SAVE LCD will show Save OK SETUP Exit The setting procedures are finished completely ...

Page 24: ...SYSTEM ERROR SMS COMMAND ALARM SMS from SYSTEM 8 1 SMS COMMAND from MOBILE SMS CONFIRMATION from SYSTEM There are 6 types of SMS would be send from the mobile are SET DOP xxxxxxxx SET DIP ALARM xxxxxxxx SET CH ALARM xxxxxxxx GET CH GET STATE RESET 22 ...

Page 25: ...y 8 status to 1 or 0 For example SET DOP 11000000 or 11000001 The Relay 1 Relay 2 will be On Relay 3 to Relay 7 will be Off On Off of RELAY 8 is depend on the alarm status For example After mobile send the SMS SET DOP 11111111x to the system the mobile will get the SMS confirmation from the system back as OP 1 8 Relay 1 8 On or Off HHHHHHHL H Relay ON L Relay Off IP 1 8 Input Switch Close or Open ...

Page 26: ... the SMS SET DIP alarm xxxxxxxx to the system The mobile will get the confirmation SMS from the system back as For example If mobile send the SMS SET DIP ALARM 11000000 The mobile will get the SMS confirmation from the system back similar as OP 1 8 Relay 1 8 On or Off HHHHHHHL H Relay ON L Relay Off IP 1 8 Input Switch Close or Open OOOOOOOO O Open C Close CHAM 1 8 Analog alarm enable disable 0000...

Page 27: ... SET DIP alarm xxxxxxxx to the system The mobile will get the confirmation SMS from the system back as For example If mobile send the SMS SET DIP ALARM 11000000 The mobile will get the SMS confirmation from the system back similiar as OP 1 8 Relay 1 8 On or Off HHHHHHHL H Relay ON L Relay Off IP 1 8 Input Switch Close or Open OOOOOOOO O Open C Close CHAM 1 8 Analog alarm enable disable 11000000 0 ...

Page 28: ...status H Reading on High value L Reading on Low value CHS HHLLLLLL N Reading on Normal value C1 980 5 m s CH1 reading value with unit C2 245 2 ACV CH2 reading value with unit C3 980 5 WATT CH3 reading value with unit C4 8 634 pH CH4 reading value with unit C5 200 5 uS CH5 reading value with unit C6 99 52 ACA CH6 reading value with unit C7 502 4 Lux CH7 reading value with unit C8 75 91 dB CH8 readi...

Page 29: ...le disable After mobile send the SMS GET STATE to the system the mobile will get the SMS confirmation from the system back as For example OP 1 8 Relay 1 8 On or Off HHHHHHHL H Relay ON L Relay Off IP 1 8 Input Switch Close or Open OOOOOOOO O Open C Close CHAM 1 8 Analog alarm enable disable 00000000 0 disable 1 enable IPAM 1 8 Input switch alarm 11000000 enable disable 0 disable 1 enable 27 ...

Page 30: ...will not send any SMS confirmation to the mobile it just to execute the reset function to the system only 8 2 ERROR SMS COMMAND If the mobile send the wrong or illegal SMS command to the system the system will send the following SMS back to mobile to hint operator that the SMS command is wrong WRONG INSTRUCTIONS 28 ...

Page 31: ... example CH1 CH8 Channel 1 8 H L N status H Reading on High value L Reading on Low value CHS HHLLLLLL N Reading on Normal value C1 980 5 m s CH1 reading value with unit C2 245 2 ACV CH2 reading value with unit C3 980 5 WATT CH3 reading value with unit C4 8 634 pH CH4 reading value with unit C5 200 5 uS CH5 reading value with unit C6 99 52 ACA CH6 reading value with unit C7 502 4 Lux CH7 reading va...

Page 32: ...6 4 Open are Closed 5 Open 6 Close 7 Open 8 Open If the switch has been bracketed it indicate that this switch alam send already The content text Close or Open shows the existing switch status For example 6 Close it indicate that the Switch 6 has been changed alarm SMS send and the existing Switch status is Close when the time that system send alarm SMS out 30 ...

Page 33: ...to SETUP SCREEN to Regular SCREEN alternatively For example a SETUP SCREEN 1 AD 2 IO 3 TEL SETUP SCREEN 4 RP 5 IM 6 SAVE a Regular SCREEN If the LCD already present any Regular SCREEN it can use the Button or Button to select the following different kind Regular SCREEN a CH1 xxxxxx xxx Regular SCREEN CH1 LO xxxx H xxxx CH1 Analog input High Low Normal value x CHx xxxxxx xxx Regular SCREEN CHx LO x...

Page 34: ...CC Input switch Open Close O Open C Close If the C or O flashed it indicate that the channel x already send the Switch input alarm SMS out k CH 12345678 Regular SCREEN CHA 00000000 Analog alarm enable enable 0 Analog alarm disable 1 Analog alarm enable l CH 12345678 Regular SCREEN IPA 00000000 Input switch alarm enable disable 0 Analog alarm disable 1 Analog alarm enable m CH 12345678 Regular SCRE...

Page 35: ...r will lit The System indicator 4 6 Fig 1 will flash per 1 second On 1 second Off if the CPU Circuit working properly At the beginning the GSM modem is not connecting the mobile network the GSM indicator 4 4 Fig 1 will flash per 0 6 second On and 0 6 second Off After the GSM modem already connect to the mobile network properly the GSM indicator will flash per 0 075 second On and 3 second Off 3 Swi...

Page 36: ...t for the Analog Channel 4 20 mA terminals 4 18 Fig 1 is DC 20 mA do not input the current over the full range 5 Relay Output terminals Warning For the long term operation for each Relay Output Terminal 4 19 Fig 1 please do not connect the max load over 1 ACA 250 ACV 34 ...

Page 37: ...up text 1 SEND SMS Right down text 9 Right up text 1 Wait the confirmation Right down text 5 of sending SMS 7 Alarm delay time a For Analog alarm after measuring value over under High limit value Low limit value 15 seconds continuously system will send alarm SMS out if alarm function is enable b For Switch input alarm close alarm type after switch is closed 3 seconds continuously system will send ...

Page 38: ...ght up down text of LCD show some text refer page 35 but the system do not execute the action as the desired function Corrective action The system may possible not key in the right mobile telephone number Please check and key in telephone no again 3 Power on the system but the GSM indicator is not finished Corrective action May the GSM modem is not triggered Power off wait at least 10 seconds then...

Page 39: ...lready cancel the PIN code of SIM card Use your mobile to check the SIM card If the network signal strength is too weak please use the optional separate antenna to instead the original antenna included 6 When the mobile send the SMS command to the system the mobile do not get any SMS confirmation as desired Corrective action May the LCD SCREEN select to SETTING SCREEN Under normal operation the LC...

Page 40: ...OU 05 pH 31 Hz 06 O2 32 DEG 07 mg L 33 KHz 08 m s 34 metr 09 knot 35 uA 10 km h 36 inS2 11 ft m 37 mA 12 ml h 38 ohm 13 uS 39 Kohm 14 mS 40 Mohm 15 Lux 41 mH 16 Ftcd 42 in s 17 dB 43 nF 18 uWcm 44 uF 19 PPM 45 DCuA 20 mg 46 cm 21 Tesl 47 WATT 22 bar 48 KWAT 23 PSI 49 ACmV 24 cmHg 50 ACV 25 iH20 38 ...

Page 41: ... PF 75 cm s 55 Kg 76 SEC 56 Lb 77 Kgcm 57 gram 78 mmHg 58 oz 79 mH20 59 NewT 80 inHg 60 m m 81 VAR 61 Hour 82 Lbin 62 Min 83 N cm 63 VA 84 CMM 64 KVA 85 CFM 65 KWHr 86 mBAR 66 mF 87 Pa 67 MHz 88 kPa 68 uH 89 uHg 69 mGAU 90 Torr 70 DCV 91 hPa 71 DCA 39 ...

Page 42: ...er TR LXT1A4 Load cell Transmitter TR LDT1A4 pH Transmitter TR PHT1A4 Potential Meter Transmitter TR PTT1A4 Pressure Transmitter TR PST1A4 xxBAR RPM Transmitter TR RPM1A4 Sound level Transmitter TR SLT1A4 Temperature type K Transmitter TR TMK1A4 Temperature Pt 100 ohm Transmitter TR TMP1A4 Vibration Transmitter TR VBT1A4 ACV Transmitter TR ACV1A4 ACA Transmitter TR ACA1A4 DCV Transmitter TR DCV1A4...

Page 43: ...wer 110 ACV or 220 ACV 4 wires Watt Transmitter TR WATxxxxx 1 phase 2 wires 3 phase 3 wires 3 phase 4 wires VAR Transmitter TR VARxxxxx 1 phase 2 wires 3 phase 3 wires 3 phase 4 wires Power Factor Transmitter TR PFTxxxxx 1 phase 2 wires 3 phase 3 wires 3 phase 4 wires The detail specifications please visit the website www lutron com tw 41 0405 GSM888 ...