Chapter 8: Configuring a Temperature Zone
Calibrating the Temperature Probe
Although temperature probes are manufactured with high accuracy, some probes might show slight meas-
urement variations. The probe calibration allows you to compensate for such a variation by up to ± 10 °
F (± 5.5 °C) with an accuracy of one tenth of a degree
1. In edit mode, under the
Calibration
tab, click on the edit field next to the
Offset
button to display the
keypad.
2. Enter the impedance offset in ohms.
3. Enter the temperature offset and the low and high trouble impedances.
NOTE:
Enter value from left to right and always enter a decimal value. For example, a value of 1 °F
requires you to enter 10 to obtain 1.0 °F.
Use the
+/-
button to change between a positive and a negative value.
For example, if a probe shows a measurement difference of + 1.3 °F from the actual temperature, you
must enter – 1.3 °F to calibrate the probe.
56
895-00677
Agri Alert 128 Touch
Summary of Contents for 890-00584
Page 14: ...NOTES 14 895 00677 Agri Alert 128 Touch...
Page 20: ...NOTES 20 895 00677 Agri Alert 128 Touch...
Page 30: ...NOTES 30 895 00677 Agri Alert 128 Touch...
Page 38: ...NOTES 38 895 00677 Agri Alert 128 Touch...
Page 44: ...NOTES 44 895 00677 Agri Alert 128 Touch...
Page 64: ...Chapter 9 Configuring a 0 5 Volt Zone Type 64 895 00677 Agri Alert 128 Touch...
Page 66: ...NOTES 66 895 00677 Agri Alert 128 Touch...
Page 82: ...NOTES 82 895 00677 Agri Alert 128 Touch...
Page 88: ...NOTES 88 895 00677 Agri Alert 128 Touch...
Page 92: ...NOTES 92 895 00677 Agri Alert 128 Touch...
Page 96: ...NOTES 96 895 00677 Agri Alert 128 Touch...
Page 100: ...NOTES 100 895 00677 Agri Alert 128 Touch...
Page 102: ...NOTES 102 895 00677 Agri Alert 128 Touch...
Page 106: ...NOTES 106 895 00677 Agri Alert 128 Touch...
Page 107: ...F Wiring Diagram with Terminals 895 00677 Agri Alert 128 Touch 107...
Page 110: ...NOTES 110 895 00677 Agri Alert 128 Touch...
Page 118: ......