Input pressure
supervision
Input pressure supervision signal
has gone below the alarm limit.
Check the process.
Check the parameters
Check the input pressure sensor
and connections.
1409
Input pressure supervision signal
has gone below the fault limit.
111
1315
Temperature fault
1
At least one of the selected
temperature input signals has
reached the alarm limit.
Find the cause of temperature
raise.
Check the temperature sensor
and connections.
Check that the temperature
input is hardwired if no sensor is
connected.
See option board manual for
further information.
1316
At least one of the selected
temperature input signals has
reached the fault limit.
112
1317
Temperature fault
2
At least one of the selected
temperature input signals has
reached the fault limit.
1318
At least one of the selected
temperature input signals has
reached the fault limit.
Fault
code
Fault
ID
Fault name
Possible cause
Remedy