12

110

Brake chopper 
supervision 
(hardware fault)

No brake resistor installed.
Brake resistor is broken.
Brake chopper failure.

Check brake resistor and 
cabling.
If these are ok, the chopper is 
faulty. Contact the distributor 
near to you.

111

Brake chopper 
saturation alarm

13

120

AC drive 
undertemperature 
(fault)

Too low temperature measured in 
power unit's heat sink or board. Heat 
sink temperature is under -10 °C. 

Check the ambient temperature

14

130

AC drive 
overtemperature 
(fault, heat sink)

Too high temperature measured in 
power unit's heat sink or board. Heat 
sink temperature is over 100 °C. 

Check the correct amount and 
flow of cooling air.
Check the heat sink for dust.
Check the ambient temperature.
Make sure that the switching 
frequency is not too high in 
relation to ambient temperature 
and motor load.

131

AC drive 
overtemperature 
(alarm, heatsink)

132

AC drive 
overtemperature 
(fault, board)

133

AC drive 
overtemperature 
(alarm, board)

15

140

Motor stalled

Motor is stalled.

Check motor and load.

16

150

Motor 
overtemperature

Motor is overloaded.

Decrease motor load.
If no motor overload exists, 
check the temperature model 
parameters.

17

160

Motor underload

Motor is underloaded.

Check load.

19

180

Power overload 
(short-time 
supervision)

Drive power is too high.

Decrease load.

181

Power overload 
(long-time 
supervision)

25

240

Motor control fault

Start angle identification has failed.

Reset the fault and restart.
Should the fault re-occur, 
contact the distributor near to 
you.

241

Generic motor control fault.

26

250

Start-up 
prevented

Start-up of the drive has been 
prevented. Run request is ON when 
a new software (firmware or 
application), parameter setting or 
any other file, which has affects the 
operation of the drive, has been 
loaded to drive.

Reset the fault and stop the AC 
drive.
Load the software and start the 
AC drive.

30

530

STO fault

Emergency stop button has been 
connected or some other STO 
operation has been activated.

When the STO function is 
activated, the drive is in safe 
state.

32

312

Fan cooling

Fan life time is up.

Change fan and reset fan life 
time counter.

33

320

Fire mode 
enabled

Fire mode of the drive is enabled. 
The drive's protections are not in 
use.

Check the parameter settings

Fault 

code

Fault

ID

Fault name

Possible cause

Remedy

Summary of Contents for RSI Series

Page 1: ...RSI 1 5 37 kW Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Page 2: ...ctions Installation and operation must comply with local regulations and accepted codes of good practice Advanced IO http net grundfos com Appl ccmsservices public literature filedata Grundfosliteratu...

Page 3: ...5 5 5 kW TM06 6526 1813 E W W2 L1 L L2 H H2 H1 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame A 8 8 5 9 143 5 191 0 297 0 293 0 315 0 188 0 197 0 214 0 Frame...

Page 4: ...W2 H H2 H1 L1 L L2 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame B 14 9 6 1 180 0 233 0 349 0 345 2 368 0 204 0 214 0 231 0 Frame Size Package Gross weight...

Page 5: ...W2 H H2 H1 L1 L L2 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame C 31 5 8 2 322 0 350 0 385 0 382 5 500 0 230 0 236 0 254 0 Frame Size Package Gross weight...

Page 6: ...age VAC 220 380 Enclosure class IP66 IP66 Power kW Product number Electrical Data Frame size Max P2 kW Rated Output Current A 1 5 99090622 1 5 8 A 2 2 99090633 2 2 11 A 3 0 99090634 3 0 12 5 A 4 0 990...

Page 7: ...he control panel and select min Frequency Caution To ensure a good convective cooling effect install the inverter vertically with at least 10 cm free space at the top and bottom To be installed indoor...

Page 8: ...Can be isolated from ground see chap 12 24Vout 24V aux voltage 13 GND I O ground 14 DI4 Digital input 4 15 DI5 Digital input 5 16 DI6 Digital input 6 17 CM Common for DI1 DI6 18 AO1 Analogue output v...

Page 9: ...every 1500 m increase in altitude Note Adjust control parameters according to the steps indicated in this manual before the first start TM05 4446 2412 Digital display control panel Operating keys The...

Page 10: ...ntrol panel and edit parameter values Down key Navigate control panel and edit parameter values Right key Navigate control panel and edit parameter values Left key Navigate control panel and edit para...

Page 11: ...lay Directions Notes Select Language Select Start up Wizard Verify or adjust the rated motor voltage Verify or adjust the rated frequency Verify or adjust the nominal speed Verify or adjust the rated...

Page 12: ...Select pump type or Other and adjust parameters Select solar modules or other and adjust Vmp maximum power voltage Select the number of solar modules Select if sinus filter is used or not Display Dir...

Page 13: ...req Reference Target frequency 50 Acceleration time Initial ramp time 3 Deceleration time Final ramp time 3 PV modules type Solar panel type sw260 Module MP Voltage Vmp Maximum power point voltage 31...

Page 14: ...n time longer Use brake chopper or brake resistor available as options Activate overvoltage controller Check input voltage 11 Overvoltage software fault 3 20 Earth fault hardware fault Current measure...

Page 15: ...o you 609 Memory access has failed For example retain variables could not be restored 610 Necessary device properties cannot be read 614 Configuration error 647 Software error Update software Should t...

Page 16: ...ure Motor is overloaded Decrease motor load If no motor overload exists check the temperature model parameters 17 160 Motor underload Motor is underloaded Check load 19 180 Power overload short time s...

Page 17: ...l Time Clock RTC battery voltage level is low and the battery should be changed Replace the battery 47 663 Software updated Software of the drive has been updated either the whole software package or...

Page 18: ...limit Carry out the needed maintenance and reset counter 69 1310 Fieldbus mapping error Non existing ID number is used for mapping values to Fieldbus Process Data Out Check parameters in Fieldbus Dat...

Page 19: ...ched the alarm limit Find the cause of temperature raise Check the temperature sensor and connections Check that the temperature input is hardwired if no sensor is connected See option board manual fo...

Page 20: ...circuit Insulation tests must not be performed on a single terminal Use a 500 V mega ohm meter to conduct the test 2 When conducting an insulation test on the motor dismantle the connection between mo...

Page 21: ...on environment 2 Radiator 3 Fan 1 Good ventilation in installation environment 2 Radiator air duct not blocked 3 Fan should be running smoothly if equipped Inverter cabinet 1 Vibration 2 Temperature r...

Page 22: ...ong period of time It is thus necessary to start up the equipment every two years to restore the performance of the capacitor and inspect the inverter function at the same time The voltage must be inc...

Page 23: ...23...

Page 24: ...Tallinn Tel 372 606 1690 Fax 372 606 1691 Finland OY GRUNDFOS Pumput AB Trukkikuja 1 FI 01360 Vantaa Phone 358 0 207 889 500 Telefax 358 0 207 889 550 France Pompes GRUNDFOS Distribution S A Parc d A...

Page 25: ...5020 1426 sk grundfos com Slovenia GRUNDFOS LJUBLJANA d o o Lesko kova 9e 1122 Ljubljana Phone 386 0 1 568 06 10 Telefax 386 0 1 568 06 19 E mail tehnika si grundfos com South Africa GRUNDFOS PTY LTD...

Page 26: ...4145 0516 ECM 1184037 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright...

Reviews: