Grundfos RSI Series Installation And Operating Instructions Manual Download Page 15

English (GB)

15

8

600

System fault

Communication between control 
board and power unit has failed.

Reset the fault and restart.
Should the fault re-occur, 
contact the distributor near to 
you.

601

Communication between control 
board and power unit has 
interference, but it is still working.

602

Watchdog has reset the CPU

603

Voltage of auxiliary power in power 
unit is too low.

604

Phase fault: Voltage of an output 
phase does not follow the reference

605

CPLD has faulted but there is no 
detailed information about the fault

606

Control and power unit software are 
incompatible

Update software. Should the 
fault re-occur, contact the 
distributor near to you.

607

Software version cannot be read. 
There is no software in power unit.

Update power unit software. 
Should the fault re-occur, 
contact the distributor near to 
you.

608

CPU overload. Some part of the 
software (for example application) 
has caused an overload situation. 
The source of fault has been 
suspended

Reset the fault and restart.
Should the fault re-occur, 
contact the distributor near to 
you.

609

Memory access has failed. For 
example, retain variables could not 
be restored.

610

Necessary device properties cannot 
be read.

614

Configuration error.

647

Software error

Update software. Should the 
fault re-occur, contact the 
distributor near to you.

648

Invalid function block used in 
application. System software and 
application are not compatible.

649

Resource overload.
Error when loading parameter initial 
values.
Error when restoring parameters.
Error when saving parameters.

9

80

Undervoltage 
(fault)

DC-link voltage is under the voltage 
limits defined.
• most probable cause: too low a 

supply voltage

• AC drive internal fault
• defect input fuse
• external charge switch not closed
Note! This fault is activated only if 
the drive is in Run state.

In case of temporary supply 
voltage break reset the fault and 
restart the AC drive. Check the 
supply voltage. If it is adequate, 
an internal failure has occurred.
Contact the distributor near to 
you.

81

Undervoltage 
(alarm)

10

91

Input phase

Input line phase is missing.

Check supply voltage, fuses and 
cable.

11

100

Output phase 
supervision

Current measurement has detected 
that there is no current in one motor 
phase.

Check motor cable and motor.

Fault 

code

Fault

ID

Fault name

Possible cause

Remedy

Summary of Contents for RSI Series

Page 1: ...RSI 1 5 37 kW Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Page 2: ...ctions Installation and operation must comply with local regulations and accepted codes of good practice Advanced IO http net grundfos com Appl ccmsservices public literature filedata Grundfosliteratu...

Page 3: ...5 5 5 kW TM06 6526 1813 E W W2 L1 L L2 H H2 H1 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame A 8 8 5 9 143 5 191 0 297 0 293 0 315 0 188 0 197 0 214 0 Frame...

Page 4: ...W2 H H2 H1 L1 L L2 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame B 14 9 6 1 180 0 233 0 349 0 345 2 368 0 204 0 214 0 231 0 Frame Size Package Gross weight...

Page 5: ...W2 H H2 H1 L1 L L2 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame C 31 5 8 2 322 0 350 0 385 0 382 5 500 0 230 0 236 0 254 0 Frame Size Package Gross weight...

Page 6: ...age VAC 220 380 Enclosure class IP66 IP66 Power kW Product number Electrical Data Frame size Max P2 kW Rated Output Current A 1 5 99090622 1 5 8 A 2 2 99090633 2 2 11 A 3 0 99090634 3 0 12 5 A 4 0 990...

Page 7: ...he control panel and select min Frequency Caution To ensure a good convective cooling effect install the inverter vertically with at least 10 cm free space at the top and bottom To be installed indoor...

Page 8: ...Can be isolated from ground see chap 12 24Vout 24V aux voltage 13 GND I O ground 14 DI4 Digital input 4 15 DI5 Digital input 5 16 DI6 Digital input 6 17 CM Common for DI1 DI6 18 AO1 Analogue output v...

Page 9: ...every 1500 m increase in altitude Note Adjust control parameters according to the steps indicated in this manual before the first start TM05 4446 2412 Digital display control panel Operating keys The...

Page 10: ...ntrol panel and edit parameter values Down key Navigate control panel and edit parameter values Right key Navigate control panel and edit parameter values Left key Navigate control panel and edit para...

Page 11: ...lay Directions Notes Select Language Select Start up Wizard Verify or adjust the rated motor voltage Verify or adjust the rated frequency Verify or adjust the nominal speed Verify or adjust the rated...

Page 12: ...Select pump type or Other and adjust parameters Select solar modules or other and adjust Vmp maximum power voltage Select the number of solar modules Select if sinus filter is used or not Display Dir...

Page 13: ...req Reference Target frequency 50 Acceleration time Initial ramp time 3 Deceleration time Final ramp time 3 PV modules type Solar panel type sw260 Module MP Voltage Vmp Maximum power point voltage 31...

Page 14: ...n time longer Use brake chopper or brake resistor available as options Activate overvoltage controller Check input voltage 11 Overvoltage software fault 3 20 Earth fault hardware fault Current measure...

Page 15: ...o you 609 Memory access has failed For example retain variables could not be restored 610 Necessary device properties cannot be read 614 Configuration error 647 Software error Update software Should t...

Page 16: ...ure Motor is overloaded Decrease motor load If no motor overload exists check the temperature model parameters 17 160 Motor underload Motor is underloaded Check load 19 180 Power overload short time s...

Page 17: ...l Time Clock RTC battery voltage level is low and the battery should be changed Replace the battery 47 663 Software updated Software of the drive has been updated either the whole software package or...

Page 18: ...limit Carry out the needed maintenance and reset counter 69 1310 Fieldbus mapping error Non existing ID number is used for mapping values to Fieldbus Process Data Out Check parameters in Fieldbus Dat...

Page 19: ...ched the alarm limit Find the cause of temperature raise Check the temperature sensor and connections Check that the temperature input is hardwired if no sensor is connected See option board manual fo...

Page 20: ...circuit Insulation tests must not be performed on a single terminal Use a 500 V mega ohm meter to conduct the test 2 When conducting an insulation test on the motor dismantle the connection between mo...

Page 21: ...on environment 2 Radiator 3 Fan 1 Good ventilation in installation environment 2 Radiator air duct not blocked 3 Fan should be running smoothly if equipped Inverter cabinet 1 Vibration 2 Temperature r...

Page 22: ...ong period of time It is thus necessary to start up the equipment every two years to restore the performance of the capacitor and inspect the inverter function at the same time The voltage must be inc...

Page 23: ...23...

Page 24: ...Tallinn Tel 372 606 1690 Fax 372 606 1691 Finland OY GRUNDFOS Pumput AB Trukkikuja 1 FI 01360 Vantaa Phone 358 0 207 889 500 Telefax 358 0 207 889 550 France Pompes GRUNDFOS Distribution S A Parc d A...

Page 25: ...5020 1426 sk grundfos com Slovenia GRUNDFOS LJUBLJANA d o o Lesko kova 9e 1122 Ljubljana Phone 386 0 1 568 06 10 Telefax 386 0 1 568 06 19 E mail tehnika si grundfos com South Africa GRUNDFOS PTY LTD...

Page 26: ...4145 0516 ECM 1184037 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright...

Reviews: