16
The Sensor
Configuration window
Open this window by selecting
Installation | Sensor Configuration
from the Menu
Bar. The following table shows all the configuration parameters which can be pro-
grammed via this window. All these parameters can also be read or programmed via
R100
Configuration
parameter
Value range
Factory
setting
Description
Sensor 1
Signal type
No sensor,
0-20 mA, 4-20 mA,
0-10 V, 2-10 V
No
sensor
Type of electrical signal from sensor.
Unit
m, m³/h, feet, gpm,
%
m
Unit of sensor value.
Max. sensor value
[1; 250]
1
Sensor maximum value.
Min. sensor value
[0; 249]
0
Sensor minimum value (offset from zero).
Limits
Max. stop
Enable, Disable
[Min sensor value;
Max sensor value]
Max.
Sensor maximum (high) limit for start/stop control.
Max. warning
Min.
Sensor maximum (high) limit for warning.
Max. alarm
Max.
Sensor maximum (high) limit for alarm, pump will be
stopped.
Min. stop
Min.
Sensor minimum (low) limit for start/stop control.
Min. warning
Max.
Sensor minimum (low) limit for warning.
Min. alarm
Min.
Sensor minimum (low) limit for alarm, pump will be
stopped.
Stop type
Fill, Empty
Fill
Fill:
pump stops at high limit and starts at low limit
Empty:
pump starts at high limit and stops at low limit
Sensor 2
External setpoint
Enable, Disable
Disable
Sensor signal used as external analogue setpoint.
Signal type
No sensor,
0-20 mA, 4-20 mA,
0-10 V, 2-10 V,
SPP 1
No
sensor
Type of electrical signal from sensor.
Unit
m, m³/h, feet, gpm,
%
m
Unit of sensor value.
Max. sensor value
[1; 250]
1
Sensor maximum value.
Min. sensor value
[0; 249]
0
Sensor minimum value (offset from zero).
Limits
Max. stop
Enable, Disable
[Min sensor value;
Max sensor value]
Max.
Sensor maximum (high) limit for start/stop control.
Max. warning
Min.
Sensor maximum (high) limit for warning.
Max. alarm
Max.
Sensor maximum (high) limit for alarm, pump will be
stopped.
Min. stop
Min.
Sensor minimum (low) limit for start/stop control.
Min. warning
Max.
Sensor minimum (low) limit for warning.
Min. alarm
Min.
Sensor minimum (low) limit for alarm, pump will be
stopped.
Stop type
Fill, Empty
Fill
Fill:
Pump stops at high limit and starts at low limit.
Empty:
Pump starts at high limit and stops at low limit.
Digital input
Function
Off, Stop, Start,
Flow
Off
Function of the external digital input.
Flow
[0; 100 l/pulse],
[0;26,4 Gal/pulse]
0 l/pulse Scaling digital input for flow measurement.
Accumulated flow
Sensor
None, Sensor 1,
Sensor 2, Digital
None
Signal source for calculation of accumulated flow
(pumped volume).
Max. Run Time
Enable, Disable
[0; 1000 m³],
[0;264200 gallons]
Disable
0 m³.
Stop of pump when defined volume is pumped.