8.5.6 Pump 1 - 6 (2.1.4.1 - 2.1.4.6)
Fig. 29
Pump 1 - 6
Description
This display is shown for the individual pumps and makes it
possible to set an operating mode.
Setting range
It is possible to select "Auto" or "Manual" as well as the operating
mode of the pump for manual operation - "Max.", "Normal", "Min."
or "Stop". For mains-operated pumps only "Normal" or "Stop" can
be selected.
Setting via control panel
• Operation > Further settings > Individual pump control.
1. Select pump.
2. Select resetting: Auto / Manual.
3. Manual: Select operating mode.
Normal: Set the setpoint.
Factory setting
Auto.
8.5.7 Operation, pilot pump (2.1.4.7)
Fig. 30
Operation, pilot pump
Description
This display is only shown in systems that have been configured
with a pilot pump.
It is possible to set the operating mode and setpoint for the pilot
pump.
Setting range
Auto
It is possible to select if the pilot pump is to be used as a backup
pump. If the pilot pump is selected as a backup pump, it will start
if the main pumps are running at 100 % speed and still cannot
reach or maintain the setpoint.
The setpoint of the pilot pump can either be set to the same value
as that of the main pumps by selecting "Use system setpoint" or
to another value.
Manual
Max., Normal, Min., Stop.
Setting via control panel
• Operation > Further settings > Individual pump control > Pilot
pump.
Select resetting: Auto / Manual.
Auto
1. Select if the pump is also to be used as backup pump (only
possible if the system does not already incorporate a backup
pump).
2. Select "Use system setpoint" or enter a setpoint.
Manual
1. Select operating mode.
2. Normal: Set the setpoint.
Factory setting
Auto.
Use system setpoint.