8.5.3 Control mode (2.1.2)
Fig. 19
Control mode
Description
There are two control modes, namely closed and open loop.
Closed loop
The typical control mode is closed loop where the built-in PI
controller ensures that the system reaches and maintains the
selected setpoint. The performance is based on the setpoint set
for closed loop. See figures
.
Fig. 20
Booster system controlled by built-in PI controller
(closed loop)
Fig. 21
Regulation curve for closed loop
Setting via control panel
• Operation > Further settings > Control mode > Closed loop.
Set the setpoint. See sections
and
.
Open loop
In open-loop control, the pumps run at a fixed speed.
The pump speed is calculated from the performance set by the
user (0-100 %). The pump performance in percentage is
proportional with the flow rate.
Open-loop control is usually used when the system is controlled
by an external controller which controls the performance via an
external signal. The external controller could for instance be a
building management system connected to the MPC system. In
such cases the MPC is like an actuator. See figures
and
.
Fig. 22
Booster system with external controller (open loop)
Fig. 23
Regulation curve for open loop
Fig. 24
Regulation curve for MPC-E system in open loop
TM
03 223
1 390
5
TM
03
23
90
41
05
P [bar]
Time [sec]
Setpoint
TM
03
22
32
39
05
TM0
3
239
1
3
6
0
7
TM
0
3
9
977
4
807
0
5
Input [%] from
external controller
Flow rate [m
3
/h]
100
50
70.7
5
25
50
75
100
86.6
Flow rate [m
3
/h]
Input [%] from
external controller
Pump 1
Pump 4
Pump 3
Flow rate
Pump 2