Operation manual 

GENO-mat duo WE-X 

GENO-mat duo WE-OSMO-X 

 
 

 

 

 

 

 

Edition Oktober 2018 
Order no. 074 184 046-inter 

 

 

Summary of Contents for GENO-mat duo WE-OSMO-X 130

Page 1: ...Operation manual GENO mat duo WE X GENO mat duo WE OSMO X Edition Oktober 2018 Order no 074 184 046 inter...

Page 2: ......

Page 3: ...the brine line 25 3 How to connect the system 25 3 1 Water connection 25 3 2 How to connect the control unit 28 E Start up 29 1 How to fill the brine tank 29 2 How to set up the system 30 2 1 How to s...

Page 4: ...progress Reprints translations into foreign languages electronic storage or digital copying of this operating manual even in parts only with explicit written approval of Gr nbeck Wasseraufbereitung Gm...

Page 5: ...ufacturer Gr nbeck Wasseraufbereitung GmbH Josef Gr nbeck Stra e 1 89420 H chst dt Do Germany Responsible for documentation Markus P pperl System designation GENO mat duo WE X water softener GENO mat...

Page 6: ...ns or general water and waste water treatment our field staff as well as the experts at our headquarters in Hoechstaedt are available to help you Advice and assistance For advice and assistance please...

Page 7: ...ed by Gr nbeck Tasks with this symbol may only be performed by trained and qualified electrical experts according to the VDE guidelines or according to the guidelines of a similar local institution Ta...

Page 8: ...nt of system parts Check the pressure pipes at regular intervals Depressurise the system before starting repair or maintenance work on the system Hazardous to health due to contaminated drinking water...

Page 9: ...waste bin is on the product this product is subject to the European Directive 2012 19 EU This means that this product or the electrical and electronic components must not be disposed with household wa...

Page 10: ...s heating systems water heaters commercial devices etc where it can lead to problems if it is hard Hard water is generated if water containing carbon dioxide flows through layers of calcium It dissolv...

Page 11: ...d and is again ready for softening Drinking water raw water As protection against corrosion we recommend a soft water hardness of at least 3 dH 5 3 f 0 53 mmol l According to the German Drinking Water...

Page 12: ...controlled The regeneration is released when the pre set water volume in an exchanger tank has been softened The system regenerates with soft water All system data is summarised in tables C 1 and C 2...

Page 13: ...0 700 780 900 Overall height of brine tank mm 810 880 870 1100 1250 Height of safety overflow on brine tank mm 700 780 770 980 1120 Connection height of control valve raw water mm 940 1160 1420 1710 1...

Page 14: ...1080 1300 1560 Exchanger tank mm 208 257 334 369 469 Distance between centre of bottles mm 400 700 Brine tank mm 410 500 570 700 700 Overall height of brine tank mm 670 810 880 870 870 Height of safet...

Page 15: ...man Drinking Water Ordinance are binding residual hardness of 3 dH 8 dH max sodium content of 200 mg l chapter E 2 1 A blending valve for mixing supply water is also needed The system is adjusted to t...

Page 16: ...mat duo WE OSMO X without LCD display The operation is carried out via the control electronics of the reverse osmosis system GENO OSMO X Turbine water meter TWZ can be replaced by water meter with cou...

Page 17: ...soft water non return valve overflow valve 2 flexible stainless steel woven hoses connection R 1 female length 600 mm 125 850 Overflow valve connection R 1 male opening pressure 0 8 bar to cover peak...

Page 18: ...ns are subject to a certain wear and tear in the event of heavy duty Wearing parts are listed below Note Although these are wearing parts we grant a limited warranty period of 6 months a Seals control...

Page 19: ...s1 Total height mm 1310 1530 1790 1840 1970 1310 1530 1790 1840 1970 Overall height without control unit mm 1080 1300 1560 1840 1970 1080 1300 1560 1840 1970 Exchanger tank mm 208 257 334 369 469 208...

Page 20: ...tions Install a drinking water filter upstream e g BOXER Use corrosion resistant material for soft water lines OR Meter corrosion inhibitor downstream of the water softener Provide a drain connection...

Page 21: ...46 inter_074_GENO mat duo_WE X docx 21 1 2 Electrical installation A shock proof plug is adequate for the electrical connection However it must comply with the specifications given in table D 1 may no...

Page 22: ...PE 11 Microswitch control valve 3 terminals on the right on the terminal strip at the control valve LiYY 3x0 5 mm 24 V Litz wire 1 BK 12 S1 Litz wire 2 YE 13 24 V 14 S2 Litz wire 3 OG Colour of litz w...

Page 23: ...94 RS485 B GND2 95 RS485 GND With cable length 20 m Use LiYcY 3x0 25 mm and connect the shielding at one end either in the OSMO X control unit or IONO matic WE control unit DEA at a free PE terminal 2...

Page 24: ...ser pipes in the exchanger containers 3 Pour ion exchange resin into the tanks Use the funnel provided Remove the protective cap fix the control valve in place 4 Centre the riser pipes precisely 5 On...

Page 25: ...ne hose onto the brine valve 6 Only if removed Insert the brine valve and replace the yellow cover 3 How to connect the system 3 1 Water connection 1 Make the water connection as indicated in the inst...

Page 26: ...ne tank mm 500 570 700 780 900 410 500 570 700 700 D Total height of brine tank mm 810 880 870 1100 1250 670 810 880 870 870 E Height of safety overflow of brine mm 700 780 770 980 1120 570 700 780 77...

Page 27: ...rear view Fig D 3 Exploded view of brine line connection Fig D 2 Pressure loss curve Druckverlust GENO mat duo WE 0 00 0 50 1 00 1 50 2 00 2 50 3 00 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 11 0...

Page 28: ...for the automatic salt reduction system compact air washer Note Small systems nominal connection diameter 1 are supplied pre assembled This means steps 1 and 2 can be skipped 1 Attach the control unit...

Page 29: ...valve and at the injector of the control valve A defined salt quality is required for the reliable function of the water softener Only use salt tablets that conform to DIN EN 973 A 3 Insert salt table...

Page 30: ...gard to the blending hardness Example Softening of drinking water Supply water 22 dH contains sodium 51 6 mg l Possible addition of sodium during softening 200 mg l 51 6 mg l 148 4 mg l Sodium content...

Page 31: ...Total hardness water inspection device 6 Set the blending hardness as required In order to do so Turn the adjusting cap to the left close so as to reduce the blending hardness Turn the adjusting cap...

Page 32: ...t bet ween 2 regenerations factory setting 0 2 hours 12 minutes At the end of the regeneration it is necessary to wait for this time to elapse before a manual regeneration can be triggered again 4 Ope...

Page 33: ...e residual capacity time since last regeneration Press and hold for 1 sec access to the operator menu Acknowledge of errors warnings Within a menu Switch to the next parameter Opened parameters Reduce...

Page 34: ...ighting again 2 2 Meaning of the LEDs red yellow green Green LED is illuminated everything OK Yellow LED is illuminated message service due low salt time incorrect after power failure 24 hours Red LED...

Page 35: ...med see table below printed in bold The raw water hardness must be set to the highest hardness that is encountered if there are fluctuations in the water quality Starting point Basic display time resi...

Page 36: ...e that the data logging was terminated with No Note The SD card used must be formatted FAT32 We recommend proper formatting instead of quick formatting 2 6 How to release a manual regeneration Startin...

Page 37: ...splay time residual capacity time since last regeneration Press and hold P and keys simultaneously the code request appears Use the or keys to set code 290 and confirm with the P key Parameters Factor...

Page 38: ...ers are volume controlled The systems are operated and monitored by means of the control electronics of the GENO WE OSMO Xreverse osmosis system Drinking water filter BOXER K 1 Reverse osmosis system...

Page 39: ...the OSMO X control unit This can be found in the subsystem range of the INFO level can be called up using the or keys Residual capacity AT m Flow rate Q m h Time since last regeneration h Current reg...

Page 40: ...can be selected by tapping on it The middle line is in slightly larger print however Save your selection with this button Quit the menu with this button without changing the prior selection The numeri...

Page 41: ...h to error list The error list may show one or several entries Tap on the entry you are interested in switch to the acknowledgement window Button to return to the Home screen The acknowledgement windo...

Page 42: ...n adjustable period of time As soon as the touch screen is tapped on or a signal or an error occurs the display returns to the basic display 3 System range 3 1 System menu I System menu I can be acces...

Page 43: ...nual regeneration Off On 3 3 System setting Parameters Factory setting Setting range Comment Hardness unit dH dH f mol m Applies to raw water hardness and capacity rate Data record Depending on system...

Page 44: ...ellow LED is illuminated Fault fault signal contact of the control unit opens terminals 29 30 red LED is illuminated As long as the power supply is on and no warning fault is pending the signal contac...

Page 45: ...r in operation may have reached the limits of its capacity Valve motor fault The next step setting on the control valve was not reached within the required time If the fault reoccurs within 5 minutes...

Page 46: ...al service authorised service company or by an approved company An operating log must be kept in order to document the maintenance work performed Notes A maintenance contract ensures that any required...

Page 47: ...ical service authorised service company Check control valve to drain for tightness in operating mode 2 1 How to refill salt Warning Impurities in the brine tank may adversely affect the water quality...

Page 48: ...water hardness soft water hardness 0 dH f mmol l test Readjust the blending valve and check the blending hardness again if necessary With Delta p program the required soft water hardness in the contro...

Page 49: ...possible via serial port If necessary reset service interval Record all data and activities including repair work in the operating log Hand over the water softener and the filled out operating log to...

Page 50: ...Water softener GENO mat duo WE X GENO mat duo WE OSMO X Order no 074 184 046 inter Edited by phar mrie G BA 184046 inter_074_GENO mat duo_WE X docx 50...

Page 51: ...og Customer Name Address GENO mat duo water softener WE X WE OSMO X 50 65 65 130 150 150 230 300 300 330 450 450 530 750 750 please check appropriate box Serial number Installed by Filter Make type Co...

Page 52: ...ading m Supply hardness dH measured Dilution hardness dH measured 0 dH inspection Inspections and checks on controller and control valve Controller setting checked Regeneration activation checked Inje...

Page 53: ...g m Supply hardness dH measured Dilution hardness dH measured 0 dH inspection Inspections and checks on controller and control valve Controller setting checked Regeneration activation checked Injector...

Page 54: ...g m Supply hardness dH measured Dilution hardness dH measured 0 dH inspection Inspections and checks on controller and control valve Controller setting checked Regeneration activation checked Injector...

Page 55: ...g m Supply hardness dH measured Dilution hardness dH measured 0 dH inspection Inspections and checks on controller and control valve Controller setting checked Regeneration activation checked Injector...

Page 56: ...g m Supply hardness dH measured Dilution hardness dH measured 0 dH inspection Inspections and checks on controller and control valve Controller setting checked Regeneration activation checked Injector...

Page 57: ...g m Supply hardness dH measured Dilution hardness dH measured 0 dH inspection Inspections and checks on controller and control valve Controller setting checked Regeneration activation checked Injector...