GENO
®
-flushing compressor 1988 K
Order no. 015 151 963-inter Created: KONS-gmei-mrie G:\BA-151963-INTER_GENO-SPUELKOMP-1988_K.DOC
47
3 | Performing system installation as per DIN EN 806-4 and
DVGW work sheet W 557
Danger!
Dosing of the disinfectant may only be performed in cold
water, for this reason the warm water heater must be switched off and
prevented from being accidentally turned on again.
Danger!
The water does not comply with the German drinking water
ordinance during the entire disinfection process. The authorised
withdrawal of water must be prevented by taking suitable measures.
Shut off/block the installation affected by disinfection from the other
parts of the installation.
Danger!
The safety data sheets, application instructions and
information on disposal of the disinfectant used are to be observed and
the designated personal protective equipment is to be worn.
Warning!
The dosing system DM-SK as well as the accessories used
must be in a hygienically perfect condition and, particularly when not
used for extended periods, must be disinfected beforehand.
Note:
The work sheet DVGW W 557 Cleaning and disinfection of
drinking water installations summarises the key requirements for
practical use.
Note:
Disinfection should be performed in stages in order to minimise
partial material corrosion.
A water/disinfectant mixture is used to disinfect pipelines.
The disinfectant GENO
®
-Chlor-A (chlorine) or
GENO
®
-perox (hydrogen peroxide) is added with the dosing system
GENODOS
®
DM-SK. The dosing pump is controlled by the flushing
compressor electronics.
Make the settings on the GENODOS
®
dosing pump according to the
designated disinfectant stipulated in Table 1.