Basic Installation/Operation
70421501 (EN)
16
General Information
This information is to be used when installing gas
tumble dryers in countries, and/or on gases, different
than the machine’s factory configuration. Tumble
dryers are supplied from the factory for operation on
Natural Gas 8914 kcal/m
3
(1000 Btu/cu ft.) or L.P. Gas
22,250 kcal/m
3
(2500 Btu/cu ft.) in the countries of
GB/IE/PT/ES/IT/GR/LU/CH. To install machines in
any other country or on any other gas requires some
level of modification.
Models are built in two different configurations:
•
Regulated Natural Gas
– Injector is sized for
Natural Gas, second family, group H (E) at
20 mbar inlet pressure. Regulator/governor is
operational. Gas valve CAN be field-converted
to a non-regulating type.
•
Unregulated Liquefied Petroleum (L.P.) Gas
–
Injector is sized for L.P. Gas, third family, group
3+ at 28.37 mbar inlet pressure. Regulator/
governor is blocked open. Gas valve CANNOT
be field-converted to a regulating type.
Serial plates supplied from the factory are configured
for the countries of GB/IE/PT/ES/IT/GR/LU/CH.
These instructions pertain to the situations when the
country of use or gas supply is different than that on
the serial plate.
NOTE: This manual is only a supplement. Refer to
installation/operation manual for full instructions.