AVFM 5.0 Area-Velocity Flow Meter
CALIBRATION
Non Contacting Level Sensor Configuration
Press
to
Calibration
and
to enter. Use
or
to position
before each
menu item and
to enter. When settings are completed press
to store and
return to the Calibration menu.
20mA Flo
[5V Flo]
Press
and enter the flow rate value for 20mA.
Note: Analogue output can be selected as 4-20mA or 0-5V in Special Functions.
4mA Flo
[0V Flo]
Press
and enter the flow rate value for 4mA.
20mA Vel
[5V Vel]
Press
and enter the velocity value for 20mA.
4mA Vel
[0V Vel]
Press
and enter the velocity value for 4mA.
20mA Level
[5V Level]
Optional for QZ02L-A type sensor. Press
and enter the level
value for 20mA.
4mA Level
[0V Level]
Optional for QZ02L-A type sensor. Press
and enter the level
value for 4mA.
MaxRg
Only for PZxx type sensor. Press
and enter the zero water
level (distance from the PZxx sensor to the zero water level).
Summary of Contents for AVFM 5.0
Page 2: ...Note This page has been left blank intentionally ...
Page 5: ...Page 5 AVFM 5 0 Area Velocity Flow Meter CONNECTIONS ...
Page 7: ...Page 7 AVFM 5 0 Area Velocity Flow Meter CALIBRATION MENU ...
Page 8: ...Page 8 AVFM 5 0 Area Velocity Flow Meter ICONS ...
Page 20: ...Page 20 AVFM 5 0 Area Velocity Flow Meter ...
Page 29: ...Page 29 AVFM 5 0 Area Velocity Flow Meter AREA VELOCITY FLOW DATA SHEET ...
Page 34: ...Page 34 AVFM 5 0 Area Velocity Flow Meter SS PIPE MOUNTING BAND OPTION VSJ ...
Page 36: ...Page 36 AVFM 5 0 Area Velocity Flow Meter ...
Page 44: ...Page 44 AVFM 5 0 Area Velocity Flow Meter Dual Non Contacting Sensor Configuration ...
Page 45: ...Page 45 AVFM 5 0 Area Velocity Flow Meter CONNECTIONS Dual Sensor Configuration ...
Page 51: ......