GREISINGER GIA1000 FR Connecting And Operating Manual Download Page 3

GIR1002 FR / GIA1000 FR       Connecting and Operating Manual         Version: 4.03-3       page: 3

Introduction

The following manual gives a description for the connection and operation of the
devices GIA1000 FR and GIR1002 FR. Please note that in this manual the GIR1002 FR
control device only will be mentioned from now on to facilitate matters. The GIA 1000
FR is to be connected and operated in the same way with functions relating to relay
outputs not being valid.

The GIR1002 FR is a micro-processor controlled signal controller for frequency signals. It can be used for
4 different input levels (30mVss, 300mVss, 2Vss and TTL).
The large 4-digit numeric LED as well as seven additional LEDs ensure a clear and well legible display of
all measuring values and operating parameters.
The GIR1002 FR is designed for direct connection of a frequency source. The controller range is adapted
to the source by directly entering the output range for 0Hz and 3000Hz, i. e. no external devices being
necessary.
All parameters and limit values can be entered via four buttons located at the front side of the device.
The front side of the controller is splash water proof and wipe resistant fulfilling all requirements of the IP65
rating.
All programmable parameters of the GIR1002 FR are stored in an EEPROM and in case of a current
failure they will be safe for at least ten years.
The GIR1002 FR is equipped with a self-diagnosis function constantly monitoring the essential parts of the
controller for their trouble-free operation. Together with the self-diagnosis function the monitoring functions
for 

breaking of the measuring sensor

 and 

sensor short-circuit

 as well as values falling below or

exceeding the limited range ensure optimum operational reliability.
We will supply the GIR1002 FR factory tested and completely calibrated.

Before you can actually use it, make sure to configurate your GIR1002 FR for your special
application. Please also refer to the chapter 

Configuration

.

Skilled personnel

are persons familiar with installation, connection, commissioning and operation of the product and have a
professional qualification relating to their job.
For example:

Training or instruction and qualification to switch on/off, isolate, ground and mark electric circuits and
devices/systems.

Training or instruction according to the state of the art of safety technology to maintain and operate
adequate safety equipment.

First-aid training.

Attention:

When running electric devices parts of these devices will always be highly energised.
Unless the warnings are observed serious personal injuries or damage to property
may result. Skilled personnel only should be allowed to work with this device. For
trouble-free and safe operation of the device, please ensure professional transport,
storage, installation and connection as well as proper operation and maintenance.

Safety Regulations

In order to exclude any risk whatever for the operator the following points have to be
observed:

a) Immediately switch off the device in case of visible damage or obvious malfunctions.
b) Make it a rule to always disconnect voltage source and device before opening it up. The entire device

and its connection have to protected against touching electrical contacts after installation.

c) Standard regulations for operation and sefety for electrical. light and heavy current equipment have to

be observed, with particular attention having to be paid to national safety regulations ( e.g. VDE 0100).

d) When connecting the GIR 1002 FR to other devices (e.g. PC), the interconnection has to be designed

most thoroughly as internal. Connections in third-party devices (e.g. connection GND with protective
earth ) may lead to undesired voltage potentials.

Summary of Contents for GIA1000 FR

Page 1: ...rating Manual GIR1002 FR GIA1000 FR Version 4 03 This connecting and operating manual may be subject to technical alternations ON SP SET min OFF Hy 1 2 max GIR GIA ALARM Scale Analog CAL SET 1 2 3 4 I...

Page 2: ...ge 7 Max value reset page 7 Display of min value page 7 Min value reset page 7 Display setting of making point switching point for switching output 1 or 2 page 7 Display setting of breaking point hyst...

Page 3: ...l supply the GIR1002 FR factory tested and completely calibrated Before you can actually use it make sure to configurate your GIR1002 FR for your special application Please also refer to the chapter C...

Page 4: ...connected to a suitable RC element for example RC220 Electric connection and commissioning of the device must be carried out by trained and skilled personnel Wrong connection may lead to the destructi...

Page 5: ...min selectable Interface RS485 Power supply 230VAC or as specified on device housing Power consumption 5W 230VAC 3W 24VDC 1 5W 12VDC Relay switching power 10A 250V AC ohmic load use RC element when sw...

Page 6: ...setting of making point button 1 4 1 2 3 7 display setting of switching point button 1 4 4 5 6 8 display setting of breaking point button 1 4 1 2 3 7 display setting of hysteresis button 1 4 4 5 6 8 S...

Page 7: ...in case of alarm LED min LEDflashing Min value reset To be called up by pressing button 3 for approx 4s Display please refer to display of min value Display setting of makingpoint switching point for...

Page 8: ...briefly no more than 1 s When pressing these buttons for a longer time over 1 s the values will start scrolling upwards respectively downwards After scrolling of approx 150 digits the scrolling speed...

Page 9: ...int to the left or button 3 shift decimal point to the right to set desired decimal point position acknowledge position by pressing button 4 If decimal point is positioned to the right of the lowest d...

Page 10: ...urrent of 20mA LED max will start flashing acknowledge by pressing button 4 8 LEDs Analog min and LED CAL are illuminated The display will show the measuring value stored in the GIR1002 FR for which a...

Page 11: ...rmissibe range This fault code indicates that the min display value of 1999 digits has fallen below Remedies FE 4 will be reset as soon as the values on the display are back within their permissible r...

Page 12: ...This method as well as the fact that the interface operates in the half duplex mode ensure that up to 16 devices can be called via only one 2 wire line Interface configuration Type RS485 Transfer mode...

Page 13: ...s specifying the parameter and or value to be processed For assignments please refer to table 1 of chapter functional code ASCII Code 2FH Indicates the end of a data transfer process Each data transfe...

Page 14: ...g point Switching point 0 9 30H 39H 1 Switching output 2 Breaking point Hysteresis 0 A 30H 41H 1 Max alarm limit 0 B 30H 42H 1 Min alarm limit 0 C 30H 43H 1 Input signal 1 5 31H 35H 3 Position of deci...

Page 15: ...l The assignment is as follows 0 2Vss 1 300mVss 2 30mVss 3 TTL Data format 4 This format is used to call up and or program the position of the decimal point The assignment is as follows 0 no decimal p...

Reviews: