4.3. Connection example

Hint:

In order to avoid undefined input states and unwanted or wrong switching processes, we
suggest to connect the device’s switching outputs after You have configured the device
properly.

4.3.1. Connection information:

The interface-converter can supply the specifieded numbers of 

EASY

BUS

 standard loads (max. 30 pieces).

The module management is limited to max. 20 

EASY

BUS

-measuring channels.

Please note that some 

EASY

BUS

 -modules have a higher bus load as the standard load!

Please notice the corresponding specification in the module manual.

Bus loads of some 

EASY

BUS 

modules:

EASY

LOG

-family:

EASY

BUS

 standard loads

EBN:

EASY

BUS

 standard loads

EBHT, EBT, EBH:

1.5 

EASY

BUS

 standard loads

GIA20EB, GIR2002: 1 

EASY

BUS

 standard load

W hen connecting the modules keep in mind that the sum of all bus loads of the modules must not exceed
the maximal allowed number.

Worked sample:
1) Connection of 5 

EASY

LOG

, 8 EBHT and 7 GIA20EB:

5 * 2 + 8 * 1.5 + 7 * 1 = 10 + 12 + 7  =  29 standard loads (20 devices)  => connection is possible

2) Connection of 15 

EASY

LOG

 and 2 EBN:

15 * 2 + 2 * 2 = 30 + 4  =  34 standard loads (17 devices)  => EB3000 are overloaded!

3) Connection of 4 EBHT and 20 GIA20EB:

4 * 1.5 + 20 * 1 = 6 + 20  =  26 standard loads (24 devices / 28 meas. channels)  => max. number of meas. channels transcended!

Please note: The 

EASY

BUS

-modules can feature more as one measurement channels (e.g: EBHT, ...)

EB 3000
Top side

switching outputs

alarm output

mains: 230V

level converter
EBW1,EBW 64..

sensor module

sensor module

Example for connection

2 wire cable

PC

Summary of Contents for EB 3000

Page 1: ...B 3000 page 1 of 19 Manual for connection and operation of EASYBus control display and supervisory device EB 3000 as of Version 1 7 GREISINGER electronic GmbH D 93128 Regenstauf Hans Sachs Stra e 26 T...

Page 2: ...sioning of the EB3000 8 6 OPERATION OF THE EB3000 8 6 1 How to display the current measurement values 8 6 2 How to display or reset the min max values 9 6 3 Setting of switching points 9 6 4 Setting o...

Page 3: ...evice must be switched off and must be marked against using again in case of obvious malfunc tions of the device which are e g visible damage no prescripted working of the device storing the device un...

Page 4: ...terfaces EASYBUS output connection for the EASYBUS sensor modules EASYBUS input permits via level converter e g EBW1 EBW64 communication with a superior computer master The EB3000 cyclically enquires...

Page 5: ...setting setting mode selection 3 Key 4 interruption recognition of the last setting acknowledgement of an error message 4 Main display indication of current measurement value resp min max value 5 Aux...

Page 6: ...1 Switching output 3 normally open 10 Switching output 4 normally open 9 Alarm output normally closed 8 Alarm output normally open 7 Alarm output common connector 6 Supply voltage 230VAC 5 Supply volt...

Page 7: ...y 2 EASYBUS standard loads EBN 2 EASYBUS standard loads EBHT EBT EBH 1 5 EASYBUS standard loads GIA20EB GIR2002 1 EASYBUS standard load W hen connecting the modules keep in mind that the sum of all bu...

Page 8: ...calculation functions choose register tab virtual channels for programming the desired func tion for virtual channel 1 or 2 For details see chapter 9 EB3000 Configuration 6 Operation of the EB3000 Hin...

Page 9: ...off point In the auxiliary display the text of the allocated channel appears Use key 1 to select the adjustable switching parameter Push key 2 or 3 In the main display the currently adjusted switching...

Page 10: ...the main display AL Lo appears again With key 4 you can cancel the setting at any time the made modification is resetted and in the main display AL Lo appears again Press key 1 again and the adjusted...

Page 11: ...ossible causes Incorrect scale Counter overflow Remedies The error message will be reset if the display value is below 9999 Reset the counter When happening frequently check the scale setting maybe it...

Page 12: ...ion error CRC Code wrong Indicates that the enquiry of an attached EASYBUS measurement channel has generated an CRC error Possible causes multiple attached EASYBUS measurement channels have the same a...

Page 13: ...rformed incorrect configuration bus is blocked in fact of a master requiry Remedies remove alarm by pushing key 4 or by using EASYBUS Configurator software perform new configuration of the EB3000 The...

Page 14: ...lly adjustable Alarm output 1 relay output changeover Switching capacity 230VAC 5A ohmic load Alarm functions Collective alarm for all sensors alarm settings for all sensors changeable Displays Main d...

Page 15: ...d system configuration In this case the following described EB3000 configuration must be performed again Afterwards you reached the EB3000 configuration window displayed on next page with all availabl...

Page 16: ...19 10 2 EB3000 Configuration By double click on the EB3000 symbol on the device overview a configuration window for the EB3000 opens Now 5 register tabs are available monitoring display control outpu...

Page 17: ...not too low to avoid error messages of the measurement system 2 Predetermination of the display of individual channels auxiliary display channel description for the respective channel shown in the aux...

Page 18: ...e modified via EB3000 device keys switch off point delay minimum switching delay in seconds after a turn off until output turns on again function switching function of the outputs in case of error see...

Page 19: ...l functions for download are available After download copy transferred datafiles easily into directory EB3CV inside of the configurator installation directory By the next start of register tab virtual...

Reviews: