E35.0.01.6C-03                     Manual for connection and operation of the EB 3000                        page 17 of 19

Here are 2 essential settings:

1) Allocation of the respective measurement channels

  - By 

measurement channel

 the 

EASY

BUS

-measurement channel with identification number is shown, which

is allocated to the respective channel. Until 20 channels can be listed. Measurement channels can also be
multiple listed and you can change the order of sequence as you like, so that by cyclic display (adjustable in
the control box on the top left-hand corner) any cyclic illustration flow is reachable.
Reselection resp. modification of the left shown attached 

EASY

BUS

-measurement channels results via „drag

and drop“ or by activation of the right mouse button.

Hint: „----„ means that no measurement channel is allocated and this channel will not be monitored.

  - By 

timeout

 the minimum updating-rate of the measurement channels in seconds will be specified (adjust-

able between 8,0 and 50,0 seconds). If a updating of the  measurement value of the respective measure-
ment channel within the specified time-interval will not be possible (resp. overload of bus capacity), an error
message will be displayed (timeout-error).

Hint: For fully occupied measurement system choose timeout duration not too low, to avoid error messages
of the measurement system.

2) Predetermination of the display of individual channels

  -

auxiliary display

„channel description“ for the respective channel shown in the auxiliary display. The
input of the „channel description“ can be 2-digit, both letters and numbers are accepted.
Hand-over of the channel description causes via click outside of the input folder resp.
by pushing the enter-key. If the decimal point next to the channel description of the
auxiliary display illuminates, cyclic operation is adjusted.

Hint: please note, because of the restricted possibility of the 7-segment-display not all
letters can be indicated.

  -

main display

measurement value of the respective channel.
For actualisation push button „refresh“ beyond this column.

  -

LED‘s

you can allocate one or more „unit-LED’s“ to each measurement channel. The 
4 „unit-LED’s“ are on the front side of the EB3000 on the right side next to the main
display. This settings are binary coded (for example by setting value 3 illuminates
LED 1+ LED 2). A click with the right mouse button on the respective value opens
dialogue window „edit unit-LED‘s“.

  -

display endurance

duration time in seconds, how long this channel will be indicated by cyclic display

(max.25,5s).

Hint: there is no relationship between display endurance and channel monitoring. For
example by setting display endurance = 0 the respective channel will not be displayed
but he will be monitored.

Summary of Contents for EB 3000

Page 1: ...B 3000 page 1 of 19 Manual for connection and operation of EASYBus control display and supervisory device EB 3000 as of Version 1 7 GREISINGER electronic GmbH D 93128 Regenstauf Hans Sachs Stra e 26 T...

Page 2: ...sioning of the EB3000 8 6 OPERATION OF THE EB3000 8 6 1 How to display the current measurement values 8 6 2 How to display or reset the min max values 9 6 3 Setting of switching points 9 6 4 Setting o...

Page 3: ...evice must be switched off and must be marked against using again in case of obvious malfunc tions of the device which are e g visible damage no prescripted working of the device storing the device un...

Page 4: ...terfaces EASYBUS output connection for the EASYBUS sensor modules EASYBUS input permits via level converter e g EBW1 EBW64 communication with a superior computer master The EB3000 cyclically enquires...

Page 5: ...setting setting mode selection 3 Key 4 interruption recognition of the last setting acknowledgement of an error message 4 Main display indication of current measurement value resp min max value 5 Aux...

Page 6: ...1 Switching output 3 normally open 10 Switching output 4 normally open 9 Alarm output normally closed 8 Alarm output normally open 7 Alarm output common connector 6 Supply voltage 230VAC 5 Supply volt...

Page 7: ...y 2 EASYBUS standard loads EBN 2 EASYBUS standard loads EBHT EBT EBH 1 5 EASYBUS standard loads GIA20EB GIR2002 1 EASYBUS standard load W hen connecting the modules keep in mind that the sum of all bu...

Page 8: ...calculation functions choose register tab virtual channels for programming the desired func tion for virtual channel 1 or 2 For details see chapter 9 EB3000 Configuration 6 Operation of the EB3000 Hin...

Page 9: ...off point In the auxiliary display the text of the allocated channel appears Use key 1 to select the adjustable switching parameter Push key 2 or 3 In the main display the currently adjusted switching...

Page 10: ...the main display AL Lo appears again With key 4 you can cancel the setting at any time the made modification is resetted and in the main display AL Lo appears again Press key 1 again and the adjusted...

Page 11: ...ossible causes Incorrect scale Counter overflow Remedies The error message will be reset if the display value is below 9999 Reset the counter When happening frequently check the scale setting maybe it...

Page 12: ...ion error CRC Code wrong Indicates that the enquiry of an attached EASYBUS measurement channel has generated an CRC error Possible causes multiple attached EASYBUS measurement channels have the same a...

Page 13: ...rformed incorrect configuration bus is blocked in fact of a master requiry Remedies remove alarm by pushing key 4 or by using EASYBUS Configurator software perform new configuration of the EB3000 The...

Page 14: ...lly adjustable Alarm output 1 relay output changeover Switching capacity 230VAC 5A ohmic load Alarm functions Collective alarm for all sensors alarm settings for all sensors changeable Displays Main d...

Page 15: ...d system configuration In this case the following described EB3000 configuration must be performed again Afterwards you reached the EB3000 configuration window displayed on next page with all availabl...

Page 16: ...19 10 2 EB3000 Configuration By double click on the EB3000 symbol on the device overview a configuration window for the EB3000 opens Now 5 register tabs are available monitoring display control outpu...

Page 17: ...not too low to avoid error messages of the measurement system 2 Predetermination of the display of individual channels auxiliary display channel description for the respective channel shown in the aux...

Page 18: ...e modified via EB3000 device keys switch off point delay minimum switching delay in seconds after a turn off until output turns on again function switching function of the outputs in case of error see...

Page 19: ...l functions for download are available After download copy transferred datafiles easily into directory EB3CV inside of the configurator installation directory By the next start of register tab virtual...

Reviews: