22 / EN
CONFIGURING BATTERY SETTINGS
Set the UPS for the number of EBPs installed.
To ensure maximum battery runtime, confi gure the UPS for the correct number of EBPs, refer to Table 8 for the
appropriate setting of battery numbers and type. Use the up and down scroll keys to select the number of battery
strings according to your UPS confi guration:
All UPS and EBP Cabinets
Number of Battery Strings
UPS only (internal batteries)
1 (default)
UPS+1EBP
3
UPS+2EBP
5
UPS+3EBP
7
UPS+4EBP
9
NOTE
: The UPS contains one battery string; each EBP contains two battery strings.
Table 8: Battery number Confi guration
CAUTION
• The following process must be performed if the UPS is connected with generator.
• First, turn on the generator, after it runs stably connect output power of the generator to UPS input
terminal, then turn on the UPS. After the UPS is turned on, please connect load one by one.
• It is recommended that the generator capacity is as twice as the UPS rated capacity.
• You had better not use the ECO mode when the quality of the input AC mains is not good.
5 Communication
This section describes the:
• Communication ports (RS-232 and USB)
• Connectivity cards
• Emergency Power-off (EPO)
• Load Segments
• UPSilon2000 Power Management Software
1.
Output Socket
2.
Battery Socket
3.
Internal SNMP Slot
4.
Net Surge Protect
(optional)
5. Fan
6. RS232, USB
7.
AC Input
8. Input Breaker
9.
EPO
FIG 20