Table 14: Electrical Input (All Models)
Nominal Frequency
50/60 Hz auto-sensing
Frequency Range
45–55 Hz (50Hz)/55-65Hz (60Hz) before transfer to battery
Bypass Voltage Range
+5%,+10%,+15%,+25% (+25% by default),-20%,-30%,-45% (-45% by default)
Table 15: Electrical Input (All Models)
Table 16: Electrical Input Connections (All Models)
Model Default Input
Voltage/Current
Selectable Input Voltages
Voltage Range at 100%
Load
1KVAS/1KVAH
230V / 4.4A
200, 208, 220, 230, 240
160 - 290Vac
1.5KVAS/1.5KVAH
230V / 6,5A
200, 208, 220, 230, 240
160 - 290Vac
2KVAS/2KVAH
230V / 8,7A
200, 208, 220, 230, 240
160 - 290Vac
3KVAS/3KVAH
230V / 13,0A
200, 208, 220, 230, 240
160 - 290Vac
Model
Input Connection
Input Cable
1KVAS/1KVAH
IEC320 C13-10A
IEC320 C14-10A
1.5KVAS/1.5KVAH
IEC320 C13-10A
IEC320 C14-10A
2KVAS/2KVAH
IEC320 C13-10A
IEC320 C19-16A
3KVAS/3KVAH
IEC320 C13-10A
IEC320 C19-16A
Table 17: Electrical Output (All Models)
High Voltage Models
Nominal Outputs
200/208/220/230/240V
(voltage confi gurable or
auto-sensing)
1000/1500/2000/3000 VA
0.9/1.35/1.8/2.7 kW
Frequency
50 or 60 Hz, autosensing
Output Overload
(Normal Mode)
108%±5%–150%±5%: Load transfers to Fault mode after 30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode after 300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Output Overload
(Bypass Mode)
100%±5%–130%±5%: Load transfers to Fault mode after 20 minutes.
130%±5%–150%±5%: Load transfers to Fault mode after 2 minutes.
150%±5%–200%±5%: Load transfers to Fault mode after 15 seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.