EN / 15
N° Working status
Indication
WARNING
Remarks
Nor Bat Bps Fau
1
Line mode
Normal voltage
None
High/low voltage protec-
tion, turn to battery mode
Once every four
seconds
2
Battery mode
Normal voltage
Once every four
seconds
Battery Voltage abnormal
WARNING
Once per second
3
Bypass mode
Main AC Normal voltage
in bypass mode
Once every two
minutes
Eliminate after starting the UPS
Main AC high voltage
WARNING
in bypass
mode
Once every four
seconds
Main AC low voltage
WARNING
in bypass
mode
Once every four
seconds
4
Battery disconnect
WARNING
Bypass mode
Once every four
seconds
Affi rm if the battery switch is
closed
Inverting mode inverting
mode
Once every four
seconds
Affi rm if the battery switch is
closed
Power up or start
Six times
Affi rm if the battery is connected
well
5
Output overload protection
Overload
WARNING
in
line mode,
Twice per second
Remove the uncritical loads
Overload in line mode,
protection
Long beeps
Remove the uncritical loads
Overload
WARNING
in
battery mode
Twice per second
Remove the uncritical loads
Overload in battery mode,
protection
Long beeps
Remove the uncritical loads
6
Overload
WARNING
in
bypass mode
Once every 2 seconds
Remove the uncritical loads
7
Fan fault (fan icon
fl ashing)
Once every 2 seconds
Check if the fan is blocked by
object.
8
Fault mode
Long beeps
If display fault code and iconli-
ghts, contact for maintenance
when you can’t deal with it by
yourself.
Table 3: The corresponding working status of indications
- indicator lights for a long time
- indicator fl ashes
- the status of indicator depends on other conditions