GREE U-Match 5 SERIES UNIT SERVICE MANUAL
144
4.5.2.2 Duct Type Unit
Removal of fan and motor
Note: Before removing the motor, make sure power is cut off.
Step
Picture
Work instruction
1. Remove the cover of
electric box.
Turn off the power supply of indoor
unit. Use a screwdriver to remove
the cover of electric box.
Disconnect the motor wire inside
the electric box.
2. Remove air return
plate, the longitudinal
component and air
return frame.
Use a hex wrench to loosen the
screws of fan.
Order of removal: air return plate,
air return frame, longitudinal
component, cross beam
3. Remove the upper
volute.
Loosen the screws of upper volute
and then pull out the upper volute.
4. Remove the lower
volute.
Loosen the screws of lower volute
and then rotate in the direction
shown by the arrow.
5. Remove the motor and
fan.
Use a screwdriver to remove the
clamping band of motor. Then
remove the motor and fan as a
whole.
6. Replace the motor.
Remove the motor from the motor
support.
Use a hex wrench to loosen the
screws of fan.
Remove the fan from the motor.
Replace with a new motor.
Summary of Contents for U-Match 5 Series
Page 31: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 28 Model GUD100W NhA T...
Page 32: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 29 Model GUD125W NhA T GUD140W NhA T...
Page 33: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 30 Model GUD100W NhA X...
Page 34: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 31 Model GUD125W NhA X GUD140W NhA X...
Page 35: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 32 Model GUD160W NhA X...
Page 59: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 56 Troubleshooting...
Page 78: ...GREE U Match 5 SERIES UNIT SERVICE MANUAL 75 Troubleshooting...
Page 224: ...JF00303775...