Dry Contact & 24 Volt Adaptor
14
Table 4.4.7 Unit parameters setting list
Parameter
code
Parameter
name
Parameter range
Default
value
Remark
P00
Error code
check
The last 5 error
codes occurred
- -
Check historic error. When nixie tube
displays “P00”, press “ENTER
(
SW4
)
”button to enter historic error
check; press “UP
(
SW3
)
”or“DOWN
(
SW2
)
”to switch to display 5 historic
errors.
P01
Device type
setting
00: 24 Volt
Adaptor(load
control)
01: 24 Volt
Adaptor(mode
control)
02: Dry Contact
Adaptor
00
When set to “00”, “01”, as an adapter for
the 24V thermostat, it needs to be
connected to a third-party thermostat. It
also has the function of fire alarm and dry
contact signal detection, while it can’t be
matched with the wired controller for
operation and it is not recommended to
use with remote monitoring and
centralized controller.
When set to “02”, this device is only used
as a dry contact detection board. It is
only used to detect fire alarm and dry
contact signals, while it can’t be
connected to a third-party thermostat. In
this case, the device can be matched
with the wired controller, while this device
should be set as slave device. Refer to
the setting on P06.