Dry Contact & 24 Volt Adaptor
16
Parameter
code
Parameter
name
Parameter range
Default
value
Remark
P05
Indoor unit’s
operation
status when
the fire alarm
signal is
disappeared
00: resume to the
previous status
01: keep OFF
status
00
When set to “00”, resume to status
before the fire alarm signal (when the
previous signal is ON, resume ON status
when the fire alarm is disappeared);
When set to “01”, keep OFF status when
the fire alarm signal is disappeared.
P06
Device
address
setting
01: master device
02: slave device
01
This device is only used as a dry contact
detection board (when P01 is set at
“02”); when it’s used with the wired
controller, it needs to set the wired
controller and this device: one is set as
master device and the other one is set as
slave device.
P07
Static
pressure
setting for
indoor fan
01, 02, 03, 04, 05,
06, 07, 08, 09
05
There are two kinds of static pressure
level:
Low static pressure: 03, 04, 05, 06, 07
High static pressure: 01, 02, 03, 04, 05,
06, 07, 08, 09