AHU-KIT
9
Model(Combined)
Capacity in application (kBtu/h)
Capacity DIP
GMV-N24U/A-T(U)
24
24
GMV-N48U/A-T(U)
30
30
36
36
48
48
GMV-N96U/A-T(U)
72
72
96
96
120
120
144
144
GMV-N192U/A-T(U)
168
168
192
192
288
288
GMV-N48U/A-T(U)+GMV-N192U/A-T(U)
336
48+288
(2) Connection method 2: one-to-more
The AHU-KIT as below can adopt one-to-more connection method with VRF outdoor unit.
Total capacity of AHU-KIT should be 50%~110% of that of outdoor unit.
Model
Capacity in application (kBtu/h)
Capacity DIP
GMV-N12U/A-T(U)
9
28
12
36
GMV-N24U/A-T(U)
15
45
18
56
24
71
GMV-N48U/A-T(U)
30
90
36
112
48
140
GMV-N96U/A-T(U)
72
224
96
280
(3) Connection method 3: one-to-more (mixed connection)
The AHU-KIT as below can adopt one-to-more connection method with general VRF indoor
unit. Total capacity of AHU-KIT and VRF indoor unit should be 50%~110% of that of outdoor unit.
Total capacity of AHU-KIT cannot exceed 30% of that of outdoor unit.