AHU-KIT
17
When several AHU-KITs are connected to one AHU, the piping diagram is as follows:
Fig.3.5.2 Several AHU-KITs to one AHU
3.5.2.1Selection of Branch Pipe
(1) Branch pipes (a, b) between outdoor units shall be selected according to the total
capacity of outdoor unit ,as follows:
Model
Selection of branch pipe between ODU modules
ML01/A
(2) Branch pipe (c, d) between indoor units shall be selected according to the total capacity
of downstream IDUs, as follows:
Selection of branch pipe
between indoor units
Total rated capacity of
downstream IDUs C(kBtu/h)
Model
Y-type Manifold
C
<
68
FQ01A/A
68
≤C≤102
FQ01B/A
102
<
C
≤239
FQ02/A
239
<
C
FQ03/A
T- type Manifold
C≤136
FQ014/H1
136
<
C≤232
FQ018/H1
232
<
C
FQ018/H2
(3) When several AHU-KITs are connected to one AHU, branch pipe (e) shall be selected
according to the following table:
Model(Combined)
Branch pipe
Quantity
GMV-N48U/A-T(U)+GMV-N192U/A-T(U)
FQ01U/A
1