background image

D.C. Inverter Multi-variable Modular

46

06_Detect outdoor 

components

db

Light

06

Light

OC

Light

No error is detected in outdoor components. 

Start next progress.

If error is detected, system will stay at current progress. Error has to be solved manually. Below is 

relevant error:

——

Debugging code

Progress code

Status code

Meaning

progress

LED1

LED2

LED3

Code

Display 

status

code

Display 

status

Code

Display 

status

06_Detect outdoor 

components

db

Light

06

Light

Error 

code

Light

System detects error in outdoor components.

Elimination methods of above error can be found in Troubleshooting.

Step11: 

progress 07 is “Detect indoor components”

If no error is detected, system will display as below and then start next progress.

——

Debugging code

Progress code

Status code

Meaning

progress

LED1

LED2

LED3

Code

Display 

status

code

Display 

status

Code

Display 

status

07_Detect indoor 

components

db

Light

07

Light

OC

Light

No error is detected in indoor components. 

Start next progress.

If error is detected, system will stay at current progress. Error has to be solved manually. Below is 

relevant error:

——

Debugging code

Progress code

Status code

Meaning

progress

LED1

LED2

LED3

Code

Display 

status

code

Display 

status

Code

Display 

status

07_Detect indoor 

components

db

Light

07

Light

XXXXor

Error 

code

Light

System detects error in indoor 

components.

XXXX is the project no. of the faulted IDU. 3s later, relevant error code is displayed. For example, 

IDU no. 100 has d5 error, then LED3 displays like this: 01 (2s later) 00 (2s later) d5, and repeat again.

Elimination methods of above error can be found in Troubleshooting.

Step 12:

 progress 08 is “Confirm preheated compressor”

If more than 8h of preheat time is detected, system will display as below and start next progress.

——

Debugging code

Progress code

Status code

Meaning

progress

LED1

LED2

LED3

Code

Display 

status

code

Display 

status

Code

Display 

status

08_Confirm 

preheated 

compressor

db

Light

08

Light

OC

Light

Preheat time for compressor is 8h. Start next 

progress.

If less than 8h of preheat time is detected, system will give error alarm and display as below. 

Then press SW7 confirmation button to skip the wait time and start next progress. But this will cause 

force start of the compressor, which may damage the compressor.

——

Debugging code

Progress code

Status code

Meaning

progress

LED1

LED2

LED3

Code

Display 

status

code

Display 

status

Code

Display 

status

08_Confirm 

preheated 

compressor

db

Light

08

Light

UO

Light

Preheat time for compressor is less than 8h.

Summary of Contents for GMV-1010WM/B-X

Page 1: ...s manual carefully before operation and retain it for future reference If you have lost the Owner s Manual please contact the local agent or visit www gree com or sent email to global gree com cn or e...

Page 2: ...fter malfunction occurs 6 All units have been strictly tested and proved to be qualified before ex factory To avoid unit damage or even operation failure which may be caused by improper disassembly pl...

Page 3: ...2 Connection Pipe 12 4 3 Installation of the Connection Pipe 22 4 4 Air Purging and Refrigerant Charge 24 4 5 Electric Wiring 25 4 6 System Communication 29 4 7 Connection Method and Steps for System...

Page 4: ...the nameplate And also take care of the power safety Installation should be conducted by dealer or qualified personnel Please do not attempt to install the unit by yourself Improper handling may resul...

Page 5: ...or gas will damage the unit appearance Only use soft cloth with a little neutral detergent to clean the outer casing of unit Open the door and window and keep good ventilation in the room to avoid oxy...

Page 6: ...let Fig 1 NO Name Fan Motor Electric Box Assembly Valve interface Power cord through hole Communication code through hole 2 2 Combinations of Outdoor Units Model Single GMV 504WM B X GMV 560WM B X GMV...

Page 7: ...mbined GMV 280WM B X GMV 450WM B X GMV 450WM B X GMV 450WM B X GMV 335WM B X GMV 450WM B X GMV 450WM B X GMV 450WM B X GMV 400WM B X GMV 450WM B X GMV 450WM B X GMV 450WM B X GMV 450WM B X GMV 450WM B...

Page 8: ...e wall mounted type duct type etc When any one IDU receives operation signal ODU will start to work according to the capacity when all IDUs stop ODU will also stop 2 4 The Range of Production Working...

Page 9: ...ch with resistance 1 Must be connected to the last IDU of communication connection 3 Mark Master 2 Attach on the wired controller of master IDU or on the front panel 3 2 Installation Site Forbidden It...

Page 10: ...on for single module unit Electrical Box Outlet on this side Air Outlet 1000 3000 1000 1000 1200 Fig 3 3 2 1 2 Space dimension for dual module unit Electrical Box Outlet on this side Air Outlet 1000 2...

Page 11: ...at least 300mm or above When the unit is located in a totally open space with no obstructions in four directions keep the distance between the unit top and wall at least 1500mm or above See Fig 7 Whe...

Page 12: ...limit on the height of wall Front side Front side Back side Back side Max 4 sets side by side Fig 9 200 200 200 1000 1200 1200 200 1000 1200 1200 No limit on the height of wall Front side Front side...

Page 13: ...ld supplied The height of the base should higher than that of the snowfall Fig 12 3 3 Piping Work Requirements There should be no fall among outdoor modules Refer to the table below for piping work re...

Page 14: ...tdoor Unit and Mounting Hole Outline and Physical Dimention of GMV 224WM B X and GMV 280WM B X unit 792 930 765 729 1605 1 22 15 1 Installation hole Fig 13 Outline and Physical Dimention of GMV 335WM...

Page 15: ...een outdoor manifolds Connection pipe between outdoor manifold and the first indoor manifold Connection pipe between indoor manifold and indoor units Connection pipe between indoor manifold and indoor...

Page 16: ...ing Sequence GMV 224WM B X and GMV 280WM B X Liquid pipe Gas pipe Oil checking valve Low pressure check valve Oil balance pipe Fig 16 GMV 335WM B X GMV 400WM B X and GMV 450WM B X Liquid pipe Gas pipe...

Page 17: ...utdoor unit and the farthest indoor unit Fig 18 L10 Length from the first branch to the farthest IDU L11 Length from the first branch to the nearest IDU Equivalent length of branch of IDU is 0 5m R410...

Page 18: ...m ODU to the first branch of IDU is 90m then adjust the pipe size of the gas pipe and liquid pipe of main pipe according to the following table Outdoor Model Gas pipe size mm Liquid pipe size mm GMV 2...

Page 19: ...should be no height drop among outdoor units Fig 19 0 2m 0 25m H 0m 2m B A Outdoor unit Outdoor unit Outdoor unit Fig 20 Note When the distance between outdoor units exceeds 2m U type oil trap should...

Page 20: ...nifold connected to oudoor module as per the pipe size of basic module Pipe size of basic outdoor module is shown as follows Outdoor unit1 Outdoor unit2 Outdoor unit3 Fitting pipe between module and o...

Page 21: ...28 0 Q 22 4 22 2 9 52 40 0 Q 28 0 25 4 12 7 45 0 Q 40 0 28 6 12 7 68 0 Q 45 0 28 6 15 9 96 0 Q 68 0 31 8 19 05 135 0 Q 96 0 38 1 19 05 Q 135 0 44 5 22 2 4 2 5 4 Fitting pipe between the first manifol...

Page 22: ...Liquid Pipe mm GMV 504WM B X 28 6 15 9 GMV 560WM B X 28 6 15 9 GMV 615WM B X 28 6 15 9 GMV 680WM B X 28 6 15 9 GMV 730WM B X 31 8 19 05 GMV 785WM B X 31 8 19 05 GMV 850WM B X 31 8 19 05 GMV 900WM B X...

Page 23: ...Indoor manifold Fig 26 R410A Refrigerant System Total capacity of downstream indoor unit s C kW Model Y type Manifold C 20 0 FQ01A A 20 0 C 30 0 FQ01B A 30 0 C 70 0 FQ02 A 70 0 C 135 0 FQ03 A 135 0 C...

Page 24: ...9 68 0 C 96 0 31 8 19 05 96 0 C 135 0 38 1 19 05 135 0 C 44 5 22 2 4 2 5 7 Fitting pipe between indoor unit and manifold Manifold should be matched with fitting pipe of indoor unit Outdoor unit1 Outdo...

Page 25: ...Spanner Torque Spanner 90 o Fig 29 1 Align the expansion end of copper pipe with the center of threaded joint Tighten the flare nuts with your hands 2 Tighten the flare nuts with torque wrench until y...

Page 26: ...line 1 To avoid condensate or water leakage on connecting pipe the gas pipe and liquid pipe must be wrapped with thermal insulating material and adhesive pipe for insulation from the air 2 For heat pu...

Page 27: ...d on the oil balance valve Confirm outdoor oil balance valves are closed See Fig 34 Liquid pipe Gas pipe Oil checking valve Oil balance pipe Low pressure check valve LO Knob HI Knob Vacuuming pump Man...

Page 28: ...nt to the unit through the filling opening of the liquid pipe valve of the outdoor unit If required additional refrigerant can not be quickly filled for increase of pressure in the pipe set the unit a...

Page 29: ...X 280 280 400 80 25 25 40 2 5 2 5 6 0 2 5 5 2 5 5 6 0 5 GMV 1010WM B X 280 280 450 80 25 25 40 2 5 2 5 6 0 2 5 5 2 5 5 6 0 5 GMV 1065WM B X 280 400 400 100 25 40 40 2 5 6 0 6 0 2 5 5 6 0 5 6 0 5 GMV 1...

Page 30: ...cord mm2 Wall mounted type 6 1 0 1 0 Duct type unit heat pump 6 1 0 1 0 Cassette type unit heat pump 6 1 0 1 0 One way cassette type unit 6 1 0 1 0 If indoor unit is equipped with auxiliary electric h...

Page 31: ...are type I electrical appliances they must be reliably grounded 2 Ground resistance must be in accord with requirements of local standard 3 The green yellow wire within units are ground wire Do not us...

Page 32: ...Communication among outdoor basic modules 2 Communication between ODU and IDU 3 Communication among IDUs 4 Communication between IDU and wired controller 5 Connection between IDU and light board rece...

Page 33: ...ive board Communication between ODU and IDU Communication among basic modules Communication among basic modules Communication among IDUs IDU IDU IDU IDU IDU IDU Wired controller Wired controller IDU m...

Page 34: ...ride sheathed cord 60227 IEC 52 60227 IEC 53 L 1000 2 0 75 IEC 60227 5 2007 1 If the wire diameter is enlarged to 2 1 mm2 the total communication length can reach 1500m 2 The cord shall be Circular co...

Page 35: ...or pressure welded Do not simply twist the wires together 4 6 4 Communication address Auto addressing technology is adopted for GMV5 IDU and ODU No need to set address codes manually Only the addresse...

Page 36: ...Us MODBUS or BACnet gateway Prev IDU Next IDU Communication matched resistance Wired controller Connect with the outdoor module The gateway is available when central controlling is required Fig 44 Con...

Page 37: ...munication wire and power cord must be separated Communication wire must be of proper length Extension is not allowed IDUs must be connected in series The last IDU must be connected with the communica...

Page 38: ...elect parameter code P13 Press mode button to switch to setup of parameter values Then the parameter value will blink Press button or button to select code 02 And then press confirm cancel to finish s...

Page 39: ...remote receiver can be used at the same time When light board remote receiver is used please use remote controller at the same time 4 7 4 Communication connection of central controlling units NOTE Th...

Page 40: ...2 D1 D2 G1 G2 D1 D2 G1 G2 D1 D2 G1G2 D1 D2 G1G2 D1 D2 G1G2 D1 D2 G1G2 D1 D2 G1G2 D1 D2 G1G2 D1 D2 G1G2 D1 D2 G1G2 ODU 2 slave unit ODU 3 slave unit ODU 4 slave unit ODU 1 master unit ODU 2 slave unit...

Page 41: ...E PE L1 L2 L3 N G1 G2 D1 D2 PE PE PE PE PE PE L1 L2 L3 N L1 L2 L3 N L N D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 Power Power Terminal Board XT1 Power Terminal Board XT2 Communication Terminal Board XT1 Pow...

Page 42: ...XT1 Power Terminal Board XT2 Communication Terminal Board XT1 Power Terminal Board XT2 Communication ODU 1 master module ODU 2 ODU 3 Remote monitor Wire resistance matching Terminal Board XT1 Power Te...

Page 43: ...unit can not run normally Communication malfunction might happen Has the communication line been connected correct The unit can not run normally Communication malfunction might happen Is the piping co...

Page 44: ...ugging confirm again whether the cut off valve of each basic module is fully turned on 4 During debugging front panel of the outdoor unit must be fully closed otherwise debugging accuracy will be affe...

Page 45: ...ortion of rated capacity db light 05 light CL light IDU ODU low proportion of rated capacity db light 05 light OC light Detection is finished Start next progress 06_Detect outdoor components db light...

Page 46: ...light 15 light U9 light Outdoor pipeline and valves are not normal db light 15 light XXXX U8 light System detects error in indoor pipeline XXXX is the project no of the faulted IDU 3s later error cod...

Page 47: ...in progress 01 if master unit is not correctly set progress 01 will show the following errors Debugging Code Progress Code Status Code Meaning Progress LED1 LED2 LED3 Code Display status Code Display...

Page 48: ...tion If no error is detected system will display as below and then start next progress Debugging code Progress code Status code Meaning progress LED1 LED2 LED3 Code Display status code Display status...

Page 49: ...D1 LED2 LED3 Code Display status code Display status Code Display status 07_Detect indoor components db Light 07 Light XXXXor Error code Light System detects error in indoor components XXXX is the pro...

Page 50: ...ium pressure is lower than 0 3MPa Step 14 progress 10 is Status judgments of outdoor valves before startup If master unit displays below status judgments are enabled Debugging code Progress code Statu...

Page 51: ...Display status 12_Status judgments of outdoor valves before startup db Light 12 Light AE Light Manual calculation of refrigerant quantity is set up Step 17 after unit is confirmed to start debugging...

Page 52: ...U 3s later error code U8 is displayed For example IDU no 100 has U8 error then LED3 displays like this 01 2s later 00 2s later U8 and repeat again Step 18 if there s no error during operation for abou...

Page 53: ...em s high pressure value in heating mode is 40 52 8 System low pressure When ambient temp is 25 35 system s low pressure value in cooling mode is 0 8 When ambient temp is 5 10 system s low pressure va...

Page 54: ...mode inlet tube temp will be 1 7 lower than outlet tube temp For a same IDU under heating mode inlet tube temp will be 10 20 lower than outlet tube temp 24 Outlet tube temp of indoor heat exchanger 25...

Page 55: ...ter is blocked for dirt Clean the filter Note When installing remote monitor or central controller displacement on indoor units project codes must be made Otherwise there will be collision malfunction...

Page 56: ...will keep running 20 70s so as to take good use of excess cooling and heating and prepare for next operation Mode conflict COOL or HEAT mode can not be operated When the indoor operating mode conflic...

Page 57: ...of indoor coil inlet temperature sensor Malfunction of indoor mid coil temperature sensor Malfunction of ODU unified Low discharge temperature protection Alarm because the air quality is bad PCB of w...

Page 58: ...unction of fan Low voltage protection of compressor s drive DC bus bar Low voltage protection of fan s drive DC bus bar Phase lacking of inverter compressor Phase lacking of inverter fan Drive chargin...

Page 59: ...nkcase 6 Check if the outdoor unit is installed firmly If there is something abnormal please contact the GREE appointed service center 8 4 Maintenance after Seasonal Use 1 Cut off main power supply of...

Page 60: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com...

Reviews: