D.C. Inverter Multi-variable Modular
27
NOTE:“224+280”: indicates the combination of GMV-224WM/B-X and GMV-280WM/B-X unit.
Please refer to the following table for circuit breaker and air switch for indoor units. Breaker listed
in the table represents total capacity of breaker in one system.
Total capacity of indoor
units
Capacity of circuit
breaker (A)
Min. sectional area of
power cord (mm
2
)
Min. sectional area of
grounding wire (mm
2
)
Below10A
10
1.0
1.0
16~10A
16
1.5
1.5
20~16A
20
2.5
2.5
32~20A
32
4.0
4.0
Total capacity of indoor
units
Capacity of circuit
breaker (A)
Min. sectional area of
power cord (mm
2
)
Min. sectional area of
grounding wire (mm
2
)
40~32A
40
6.0
6.0
50~40A
50
10.0
10.0
63~50A
63
16.0
16.0
80~63A
80
25.0
16.0
100~80A
100
35.0
16.0
125~100A
125
50.0
25.0
Breaker capacity and power cord specification for every indoor unit
Indoor unit
Capacity of circuit
breaker (A)
Min. sectional area of
grounding wire (mm
2
)
Min. sectional area of
power cord (mm
2
)
Wall-mounted type
6
1.0
1.0
Duct type unit (heat
pump)
6
1.0
1.0
Cassette type unit (heat
pump)
6
1.0
1.0
One-way cassette type
unit
6
1.0
1.0
If indoor unit is equipped with auxiliary electric heater, select capacity of circuit breaker as per
auxiliary electric heater, which requires special setting.
Indoor unit models (with auxiliary
electric heater)
Capacity of
circuit breaker
(A)
Min. sectional area of
grounding wire (mm
2
)
Min. sectional area of
power cord (mm
2
)
22,25,28,32,36 duct type unit
6
1.0
1.0
40,45,50 duct type unit
10
1.0
1.0
56,63,71,80 duct type unit
16
1.5
1.5
90,100,112,25,140 duct type unit
10
1.0
1.0
28,36,45,50 cassette type unit
6
1.0
1.0
56,63,71,80 cassette type unit
10
1.0
1.0
90,112,125,140 cassette type unit
6
1.0
1.0
Note:
①
Specification of circuit breaker and power cord is selected on the basis of unit’s maximum
power (max. current).
②
Specification of power cord is based on the working condition where ambient temperature is
40 and multi-core cable with copper conductor(working temperature is 90 , e.g. power cable with
YJV cross-linked copper, insulated PE and PVC sheath) is lying on the surface of slot. If working