D.C. Inverter Multi-variable Modular
28
condition is different, please adjust the specification according to national standard.
③
Copper-core cable must be used.
④
The above sectional area is suitable for a maximum distance of 15m. If it’s over 15m, sectional
area must be expanded to prevent overload current from burning the wire or causing fire hazard.
⑤
Specification of circuit breaker is based on the working condition where the ambient
temperature of circuit breaker is 40
. If working condition is different, please adjust the specification
according to national standard.
⑥
The air switch should include magnetic trip function and thermal trip function so that system
can be protected from short circuit and overload.
⑦
An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring
4.5.3 Connection of power cord
Warning: before obtaining access to terminals, all supply circuits must be
disconnected.
Note:
(1) If units are type I electrical appliances, they must be reliably grounded.
(2) Ground resistance must be in accord with requirements of local standard.
(3) The green-yellow wire within units are ground wire. Do not use it for other purposes. Nor
should it be cut off or secured by tapping screws. Otherwise, it may cause electric shock.
(4) Power supply at user side must have reliable ground terminal. Do not connect ground wire to
the following places:
1) water pipe, 2) gas pipe, 3) drainage pipe, 4)other places that are considered by professionals
as unreliable.
(5) Power cord and communication wire should be separated, with a distance of more than 20cm.
Otherwise, system’s communication may not work well.
Steps and graphic of power cord connection:
(1) Knock off the cross-through opening that’s used for leading the external power cord, with the
cross-through rubber ring on the opening. Then lead the cable through the opening. Connect
L1, L2, L3, N of power cord and ground wire separately to the positions on wiring board (for
power supply) that are marked with L1, L2, L3, N and the ground screw nearby.
(2) Use cable ties to tie the cable securely,
(3) Lead the power cord as instructed in the graphic below: