U-Match Series DC Inverter Service Manual
50
7.2.7 Reserved fresh air valve interface for duct type unit
For the reserved connection way of air valve performer, connect it to F, C, O of wiring board according
to the wiring diagram. Connect the public port of air valve to F, connect CLOSE to C and connect OPEN to
O.
Figure 2-7-17
7.2.8 Interface of anion generator
For the cold plasma anion generator, connect the red line to HEALTH
(
X4
)
and the blue line to N2(X6)
according to the principle circuit. The detector of cold plasma anion generator should be places at the air
return. The distance between two detectors should be 10mm (3/8inch)
≤ L ≤ 25mm (1inch).
MOTOR
WIRING
DIAGRAM
EARTH
WIRING
DIAGRAM
M
G
G
G
POWER
L1
L2
L1
L2
F
C
O
2BU
1RD
5WH
8BN
COOL PLASMA
GENERATOR
9RD
L1
L1
RD
BU
AP1
15WH
XT1
OUTDOOR
UNIT
1
2
WIRE
CONTROL
XT2
AP2
X1
X2
CLOSE
Fresh Air Valve
Common
OPEN
1
2
H1
H2
L2
L4
11RD
12BK
13BN
14OG
COM6
COM7
T2
T3
PUMP-C PUMP
SA
15K
20K
LIQUID SWITCH
Environment
Temp. Sensor
Pipe
Temp. Sensor
Pump Motor
E500
N2(X6)
AC-L
(X501)
V-NEW-CLOSE(X2)
V-NEW-OPEN(X1)
AC-N
(X500)
HEALTH
(X4)
N2
(X6)
D
C
-MO
T
OR
1
Figure 2-7-18
Summary of Contents for GKH18D3FI
Page 1: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL T1 R410A 60Hz GC201410...
Page 4: ...U Match Series DC Inverter Service Manual 1 PRODUCT...
Page 16: ...U Match Series DC Inverter Service Manual 13 CONTROL...
Page 55: ...U Match Series DC Inverter Service Manual 52 INSTALLATION...
Page 96: ...U Match Series DC Inverter Service Manual 93 MAINTENANCE...
Page 112: ...U Match Series DC Inverter Service Manual 109 H6 DC fan error...
Page 121: ...U Match Series DC Inverter Service Manual 118 Model GUHD24ND3FO Model GUHD30ND3FO...
Page 122: ...U Match Series DC Inverter Service Manual 119 Model GUHD36ND3FO Model GUHD42ND3FO...
Page 126: ...U Match Series DC Inverter Service Manual 123 Model GKH48D3FI...
Page 191: ...U Match Series DC Inverter Service Manual 188 JF00302305...