U-Match Series DC Inverter Service Manual
30
Table 2-4-2 Combination relationship of P03, P04, P05, P06, P07
Static
pressure
selection
Super
high
speed
High
speed
Medium
high speed
Mediu
m
speed
Medium
low speed
Low
speed
Quiet
R1
speed
Quiet
R2
speed
Quiet
R3
speed
P03
S09
S08
S07
S06
S05
S04
S03
S02
S01
P04
S10
S09
S08
S07
S06
S05
S04
S03
S02
P05
S11
S10
S09
S08
S07
S06
S05
S04
S03
P06
S12
S11
S10
S09
S08
S07
S06
S05
S04
P07
S13
S12
S11
S10
S09
S08
S07
S06
S05
4.9.12 Selecting compensation of temperature sensor at air return
Under debugging state, press Mode button to adjust to “12” in temperature displaying zone. Timer
zone displays setting state and press ▲ or ▼ button to adjust. There are 16 selections:
(1) Compensate 0
℃
(32
℉
) (LCD displays 00)
(2) Compensate 1
℃
(34
℉
) (LCD displays 01)
(3) Compensate 2
℃
(36
℉
) (LCD displays 02)
(4) Compensate 3
℃
(37
℉
) (LCD displays 03)
(5) Compensate 4
℃
(39
℉
) (LCD displays 04)
(6) Compensate 5
℃
(41
℉
) (LCD displays 05)
(7) Compensate 6
℃
(43
℉
) (LCD displays 06)
(8) Compensate 7
℃
(45
℉
) (LCD displays 07)
(9) Compensate 8
℃
(46
℉
) (LCD displays 08)
(10) Compensate 9
℃
(48
℉
) (LCD displays 09)
(11) Compensate 10
℃
(50
℉
) (LCD displays 10)
(12) Compensate 11
℃
(52
℉
) (LCD displays 11)
(13) Compensate 12
℃
(54
℉
) (LCD displays 12)
(14) Compensate 13
℃
(55
℉
) (LCD displays 13)
(15) Compensate 14
℃
(57
℉
) (LCD displays 14)
(16) Compensate 15
℃
(59
℉
) (LCD displays 15)
Note:
Indoor ambient temperature compensation can be set through wired controller (E.g. If 02 is
selected, it indicates the compensation temperature is 2
℃
(36
℉
). If the indoor ambient temperature
detected by the temperature sensor at air return is 29
℃
(84
℉
), the ambient temperature after
compensation is 29
℃
(84
℉
)-2
℃
(36
℉
)=27
℃
(81
℉
)).
After finishing setting, press Enter/Cancel button to save and exit setting. After entering this interface,
the system will exit this menu if there is no operation on the button within 20s. Normal off state interface will
be displayed and present setting will not be saved.
Summary of Contents for GKH18D3FI
Page 1: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL T1 R410A 60Hz GC201410...
Page 4: ...U Match Series DC Inverter Service Manual 1 PRODUCT...
Page 16: ...U Match Series DC Inverter Service Manual 13 CONTROL...
Page 55: ...U Match Series DC Inverter Service Manual 52 INSTALLATION...
Page 96: ...U Match Series DC Inverter Service Manual 93 MAINTENANCE...
Page 112: ...U Match Series DC Inverter Service Manual 109 H6 DC fan error...
Page 121: ...U Match Series DC Inverter Service Manual 118 Model GUHD24ND3FO Model GUHD30ND3FO...
Page 122: ...U Match Series DC Inverter Service Manual 119 Model GUHD36ND3FO Model GUHD42ND3FO...
Page 126: ...U Match Series DC Inverter Service Manual 123 Model GKH48D3FI...
Page 191: ...U Match Series DC Inverter Service Manual 188 JF00302305...