U-Match Series DC Inverter Service Manual
77
1~1.5m(3-2/7~5feet)
× (wrong)
√ (Correct) 1/100 or more gradient
Figure 3-1-59
(5) The incline of attached drain hose should be 75mm (3inch) or less so that the drain outlet does
not have to withstand additional force.
≤7
5m
m
(3
in
ch
)
≤1
00
0m
m
(3
9-
3/
8in
ch
)
Drain hose(attachment)
Figure 3-1-60
1.3.11 Testing of Drain Piping
After piping work is finished, check if drainage flows smoothly. Shown in the Figure 3-1-61, Add
approximately 1liter of water slowly into the drain pan and check drainage flow during COOL running.
Drain hose
Test hole cover
Test hole
<Immiting water from the rest hole>
Plastic water pot [The length of
the pipe should be about
100mm(3-7/8inch)].
<Immiting water from the outlet vent terminal>
Above 100mm(3-7/8inch)
Drain vent for repair use (plastic stopper
is included) (drain the water in waterspoit
by this outlet vent)
Figure 3-1-61
Summary of Contents for GKH18D3FI
Page 1: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL T1 R410A 60Hz GC201410...
Page 4: ...U Match Series DC Inverter Service Manual 1 PRODUCT...
Page 16: ...U Match Series DC Inverter Service Manual 13 CONTROL...
Page 55: ...U Match Series DC Inverter Service Manual 52 INSTALLATION...
Page 96: ...U Match Series DC Inverter Service Manual 93 MAINTENANCE...
Page 112: ...U Match Series DC Inverter Service Manual 109 H6 DC fan error...
Page 121: ...U Match Series DC Inverter Service Manual 118 Model GUHD24ND3FO Model GUHD30ND3FO...
Page 122: ...U Match Series DC Inverter Service Manual 119 Model GUHD36ND3FO Model GUHD42ND3FO...
Page 126: ...U Match Series DC Inverter Service Manual 123 Model GKH48D3FI...
Page 191: ...U Match Series DC Inverter Service Manual 188 JF00302305...