U-MATCH Air
Conditioners
Service Manual
Tighten the valve caps and use soapy water or a leak detector to check any leakage on indoor unit,
outdoor unit and connection parts of pipes.
Caution:
If conditions are allowed, a vacuum pump shall be used for drawing off air inside the system at a valve. Method
for creation of vacuum by using a vacuum pump is as follows:
Take out the nut cover of the inlet for refrigerant.
Connect the tube of the vacuum watch with the vacuum pump, having the low-pressure end linking to the
inlet for refrigerant. (As shown in Figure 3-1-5)
Pressure Gage
Pressure Gage
³/2´.QRE
³+,´.QRE
/LTXLG9DOYH
Vacuum Pump
Connecting Hose
Gas Valve
Figure 3-1-5
Starting the vacuum pump, when the indicator turns to-1 bar, closing the low pressure handle and stopping
YDFXXPL]H.HHSIRUPLQXWHVHQVXULQJWKHSUHVVXUHRIWKHYDFXXPZDWFKUHPDLQV
7DNHRXWWKHYDOYHFRYHURIWKHJDVYDOYHWRJHWKHUZLWKWKHOLTXLGYDOYH
/RRVLQJWKHFRUGRIOLTXLGYDOYHXQWLOWKHSUHVVXUHULVHWREDU
Dismantle the tube from the cover of the inlet for refrigerant then, tighten the cover.
/RRVHWKHYDOYHFRUGRIWKHJDVYDOYHDVZHOODVWKHOLTXLGYDOYHHQWLUHO\
7LJKWHQWKHYDOYHFRYHURIWKHJDVYDOYHDQGOLTXLGYDOYHVRDVWRFKHFNZKHWKHUOHDNDJHRFFXUUHG
3. Installation of Protective Layer of Connecting Pipe
To avoid generation of condensate on the connecting pipe and avoid leakage, the big pipe and the small
pipe of the connecting pipe must be covered by thermal insulation materials, be bundled by adhesive tape,
and be isolated from air.
The joint connecting to the indoor unit must be wrapped by thermal insulation material. There shall be no
gap between the connecting pipe joint and the wall of the indoor unit. Refer to Figure 3-1-6.
Figure 3-1-6 Figure 3-1-7
Use adhesive tape to bundle the connecting pipe and the cables together. To prevent condensate from
overflowing out from the drainage pipe, separate the drainage pipe firm the connecting pipe and the
cables.
Use thermal insulation tape to wrap the pipes from the bottom of the outdoor unit until the upper end of the
pipe where the pipe enters the wall. When wrapping thermal insulation tape, the later circle of tape must
Summary of Contents for GKH12K3BI
Page 1: ...U MATCH AIR CONDITIONERS SERVICE MANUAL T1 R410A 50Hz...
Page 4: ...1 U MATCH Air Conditioners Service Manual PRODUCT QSPEVDU...
Page 31: ...28 U MATCH Air Conditioners Service Manual CONTROL DPOUSPM...
Page 33: ...30 U MATCH Air Conditioners Service Manual DPOUSPM 1 2 Heating Operation...
Page 50: ...47 U MATCH Air Conditioners Service Manual INSTALLATION...
Page 86: ...83 U MATCH Air Conditioners Service Manual MAINTENANCE...
Page 93: ...90 U MATCH Air Conditioners Service Manual Malfunction display E6 Communications Failure...
Page 111: ...108 U MATCH Air Conditioners Service Manual Model GTH30K3B1I Model GTH60K3B2I...
Page 151: ...148 U MATCH Air Conditioners Service Manual 2 Model GUHN24NK3AO Exploded Views...
Page 156: ...153 U MATCH Air Conditioners Service Manual 5 Model GUHN42NM3AO GUHN48NM3A1O Exploded Views...
Page 158: ...155 U MATCH Air Conditioners Service Manual 6 Model GUHN60NM3AO Exploded Views...
Page 160: ...157 U MATCH Air Conditioners Service Manual 7 Model GUHN60NM3A2O Exploded Views...
Page 165: ...162 U MATCH Air Conditioners Service Manual 2 Model GUHN24NK3AO Exploded Views...
Page 168: ...165 U MATCH Air Conditioners Service Manual 4 Model GUHN36NK3AO GUHN36NM3AO Exploded Views...
Page 173: ...170 U MATCH Air Conditioners Service Manual 6 Model GUHN60NM3A2O Exploded Views...
Page 175: ...172 U MATCH Air Conditioners Service Manual 7 Model GUCN42NM3AO Exploded Views...
Page 177: ...174 U MATCH Air Conditioners Service Manual 8 Model GUCN48NM3AO Exploded Views...
Page 189: ...186 U MATCH Air Conditioners Service Manual 3 Model GKH30K3B1I Exploded Views...
Page 191: ...188 U MATCH Air Conditioners Service Manual 4 Model GKH42K3B1I GKH48K3B3I Exploded Views...
Page 193: ...190 U MATCH Air Conditioners Service Manual 5 Model GKH60K3B2I Exploded Views...
Page 209: ...JF00300193...