GREE Duct type split Air conditioner Inverter Series
68
pipes whose gauge is suitable for the operating capacity of the unit.(take the cassette type unit
for example).
6.3 Testing of Drain Piping
(1) After piping work is finished, check if drainage flows smoothly.
(2) Shown in the figure, Add approximately 1liter of water slowly into the drain pan and check
drainage flow during COOL running.
7 Electrical Installation
(1) The wiring must be in accordance with the local rules.
(2) Rated supply voltage and special circuit for air conditioner must be used.
(3) Do not pull the power cord forcefully.
(4) All the electric installations must be carried out by specialist technicians in accordance with the
local laws, rules and these instructions.
(5) The diameter of flexible wire should be wide enough. Replace the damaged power cord and
connecting wire with special flexible wire.
(6) The earthing shall be reliable and connected to the special earthing device on the construction.
The installation must be done by specialist technicians. The leak protection switch and air switch
with enough capacity must be installed. The air switch shall have both the magnetic tripping and
thermal tripping functions to ensure protection against the short circuit and overload.
(7) The air conditioner belongs to I type electric appliances. The reliable earthed action is a must.
(8) The yellow and green wire inside the air conditioner is the earthed wire. Do not use it for other
purpose or even cut off it. Do not fix it with tapping screw,. Otherwise, it may cause electric
shock.
(9) The earthed resistance must meet the requirements of local national standard.
(10) There should be reliable earthed terminal for the power supply. Never connect the earth lead to
the following articles:
①
water pipe;
②
gas pipe;
③
drain pipe;
④
unreliable place considered by professionals.
Summary of Contents for CF01000730
Page 56: ...GREE Duct type split Air conditioner Inverter Series 54 7 Switchover of Software Languages...
Page 118: ...GREE Duct type split Air conditioner Inverter Series 116 FGR40Pd D 2 Na X I FGR20Pd DNa X O...
Page 119: ...GREE Duct type split Air conditioner Inverter Series 117 FGR25Pd DNa X O FGR30Pd DNa X O...
Page 129: ...JF00303352 JF00304016...