GREE Duct type split Air conditioner Inverter Series
60
External Static Pressure
Static pressure level of indoor fan motor
0 inWG(0 Pa)
01
0.12 inWG(30 Pa)
02
0.24 inWG(60 Pa)
03
0.36 inWG(90 Pa)
04
0.48 inWG(120 Pa)
05
0.60 inWG(150 Pa)
06
0.72 inWG(180 Pa)
07
0.84 inWG(210 Pa)
08
1.00 inWG(250 Pa)
09
Note:
Keep in mind that a shortage of airflow quantity or water leakage will result because the air
conditioner will be operated outside the rated range of airflow quantity if the external static pressure is
wrongly set.
(1) If you choose 01,the indoor motor will adjust static pressure of the blast pipe automatically when
start-up every time.Here is the way to enter P67.
(2) Long press FUNCTION button for 5s and the temperature zone displays “C00”; press MODE
button for three times in 3s;long press FUNCTION button for another 5s to enter the interface of
setting wired controller parameters. “P00” is displayed in temperature zone.
(3)
Press “▲” or “▼” button to select parameter code. Press MODE button to enter parameter
setting. At that
time, parameter value is blinking. Press “▲” or “▼” button to adjust the parameter
value and press ENTER/CANCEL button to finish setting.
(4) Press ENTER/CANCEL button to return to last step until exists setting parameters.
The parameter setting list is as following:
Parameter code
Parameter name
Parameter range
Default value
P67
Select the way of adjusting static pressure
00: manually
01:automatically
00
3.3.3 External static pressure reading
If you want to know the exact external static pressure,you can set P67 to 01,restart the machine,after
about 2 minutes,enter C24 to read the exact ESP.
(1) Long press FUNCTION button for 5s and the temperature zone displays “C00”; press MODE
button for three times in 3s.
(2)
Press “▲” or “▼” button to C24,there you can read t
he exact ESP.
3.4 Installation notice
(1) The unit shall be installed by the professional personnel according to this installation instruction
to ensure proper use.
(2) Please contact the local Gree appointed service center before installation. Any
malfunctioncaused by the unit that is not installed by the Gree appointed service center would
probably not be dealt with on time because of the inconvenience of the business contact.
Summary of Contents for CF01000730
Page 56: ...GREE Duct type split Air conditioner Inverter Series 54 7 Switchover of Software Languages...
Page 118: ...GREE Duct type split Air conditioner Inverter Series 116 FGR40Pd D 2 Na X I FGR20Pd DNa X O...
Page 119: ...GREE Duct type split Air conditioner Inverter Series 117 FGR25Pd DNa X O FGR30Pd DNa X O...
Page 129: ...JF00303352 JF00304016...