background image

section 3: installation

Page 8

OPERatiOn WitH RaDiatORs

Grant Solo fan convectors are ultra-low water content heat 

emitters and should ideally not share heating circuits with 

conventional radiators, as this may result in a reduced flow 

through the fan convectors.
If this cannot be avoided and the fan convectors must be added 

to an existing radiator circuit the following requirements must be 

met:
a) 

The flow and return pipework must be 22mm minimum. 

Smaller pipework will result in poor or no heat output from the 

fan convector(s).

b) 

When installed, first shut off the conventional radiator(s) to 

check that the fan convector(s) operate correctly.

Then, turn on the radiator(s) and adjust the lockshield valve 

on each radiator and reduce the flow until the fan convector(s) 

operate.

3.5  PiPEWORK matERiaLs

The Grant Solo fan convectors can be used with both copper 

and plastic pipe. Where plastic pipe is used it must be of the 

oxygen barrier type and be the correct class (to BS7291-1) for the 

application concerned.
On sealed systems, if plastic pipe is to be used, the installer must 

check with the plastic pipe manufacturer that the pipe to be used 

is suitable for the temperatures and pressures concerned. Plastic 

pipe must be Class S to BS7291-1.

Two flexible hose connections will be required for installation of 

the Grant Solo Hideaway fan convector. These are supplied with 

the unit.

3.6  PiPE COnnECtiOns

sOLO COmPaCt anD COmPaCtmax mODELs: 

Remove the front cover to access the flow and return pipe 

connections. Refer to Section 3.6 or 3.7, as required, for details 

on removal of the front cover.

The flow and return connections are located at the left-hand side 

of the unit.

The flow and return pipework can enter/exit the unit either

a)  To the rear of the unit through the wall, or
b)  To the bottom of the unit, through the opening in the lower 

casing.

It is recommended that 15mm isolation valves (not supplied) 

are fitted to the flow and return connections before connecting 

the flow and return pipework. These valves must be of the ‘full 

bore’ type to ensure no added restriction to the flow and return 

pipework. 

sOLO HiDEaWaY: 

The flow and return connections are located on the right-hand 

side of the unit.
To allow the unit to be fully withdrawn from the plinth or base 

board in which it is fitted, without having to disconnect it from the 

system, two flexible hose connections (supplied) will be required 

for installation of the Grant Solo Hideaway fan convector. These 

are long enough to allow the fan convector to be completely 

removed from the plinth/baseboard when they are connected. 

These will be connected between the system flow and return 

pipework, located at the rear of the fixed kitchen unit, and the 15 

mm full bore valves on the flow and return connections on the fan 

convector.

3.7  instaLLatiOn PROCEDURE:

 

sOLO COmPaCt anD sOLO  

 

COmPaCtmax mODELs

1.  Carefully remove the Solo fan convector unit from the 

packaging.

2. 

Lay the unit on a flat surface (floor, table, etc.) with the front 

cover facing upwards.

3. 

Unscrew and remove the three fixing screws from along the 

lower edge of the front cover.

4.  Lift the lower front edge of the front cover and then slide it 

forwards and off the unit.

5.  Safely store the front cover for now where it will not be 

damaged or scratched for re-fitting after the Solo Compact or 

CompactMAX fan convector has been installed.

6.  Position the unit against the wall so that the lower edge is 

approximately 75-100mm above the skirting level. 

7.  Use a spirit level on the top of the unit to ensure it is level 

and mark the position of the three fixing holes in the back 

plate onto the wall. Refer to Figure 2-5 0r 2-6 for the fixing 

hole positions.

8.  Remove the unit from the wall and drill the three holes to take 

a suitable wall fixings (not supplied).

9. 

Securely fix the unit to the wall using three screws (not 

supplied).

10. 

Remove the rubber bungs from the flow and return 

connections on the fan convector and check that the bleed 

screws on the flow connection are both closed.

It is recommended that 15mm isolation valves (not supplied) are 

fitted to the flow and return connections before connecting the 

flow and return pipework.

These valves must be of the ‘full bore’ type to ensure no added 

restriction to the flow and return pipework. 

 

 

 

Solo Compact 

410 

610 

Outline of front cover 

65 

90 

155 

Figure 3-3:

 Solo Compact fixing holes (viewed from the front)

Summary of Contents for Solo Compact

Page 1: ...UK DOC 0139 Rev 1 0 October 2018 Grant Solo Fan Convectors Installation and User Instructions ...

Page 2: ...tallation commissioning and servicing of the Grant Solo fan convectors After installion leave these instructions with the user User instructions to guide users in the operation of the fan convectors are given in Section X of these instructions Special Text Formats The following special text formats are used in these instructions for the purposes listed below WARNING Warning of possible human injur...

Page 3: ...edure 8 Solo Compact and Solo CompactMAX models 3 8 Installation procedure 9 Solo Hideaway model 4 Electrical 11 4 1 General 11 4 2 Electrical connections 11 Contents Page 3 5 COMMISSIONING 11 6 Fault finding 12 6 1 Initial checks 12 6 2 Fault diagnosis flow chart 13 7 Spares PARTS 14 7 1 Fan convector parts list 14 8 OPERATING INSTRUCTIONS 14 8 1 Mains ON OFF switch 14 8 2 Control panel 15 9 Clea...

Page 4: ...ase but is insulated from it providing a low casing surface temperature regardless of the water flow temperature The top grille prevents contact with the heat exchanger With the electrical supply to the Solo fan convector switched on when the water temperature sensor located in the heat exchanger detects that the water temperature entering the unit exceeds 29 C the unit will start The air temperat...

Page 5: ...eration After this period has elapsed the Solo unit automatically returns to the normal temperature control with the fan operating at either Low or High setting as dictated by the difference between the air temperature and the air temperature setting on the unit 1 3 CONTROL PANEL OVERVIEW Grant Solo fan convectors are supplied with a simple control panel Refer to Figure 1 3 and Section 8 2 control...

Page 6: ... power W 4 4 4 Sound pressure level at 1 metre ISO 3744 Low speed dB A 18 18 18 High speed dB A 22 23 22 Boost dB A 38 39 38 2 2 PERFORMANCE DATA Table 2 2 Heating capacity BS EN ISO 16430 on high low fan speed Mean water temperature Units Solo Compact Solo CompactMAX Solo Hideaway High Low High Low High Low 35 C W 314 247 604 470 314 247 40 C W 426 335 831 646 426 335 45 C W 542 426 1 071 832 542...

Page 7: ...t for sealed water systems Code of practice for domestic heating and hot water supply 3 3 Location Solo Compact and CompactMAX fan convectors should be positioned with the lower edge approximately 75 100mm above the skirting level The Solo Hideaway fan convectors are fitted into the plinth or baseboard of fixed units e g kitchen units Refer to Section 3 7 for dimension of the opening required The ...

Page 8: ... and return pipework Solo Hideaway The flow and return connections are located on the right hand side of the unit To allow the unit to be fully withdrawn from the plinth or base board in which it is fitted without having to disconnect it from the system two flexible hose connections supplied will be required for installation of the Grant Solo Hideaway fan convector These are long enough to allow t...

Page 9: ...Refer to Section 5 Commissioning 3 8 Installation procedure Solo Hideaway model Accurately mark and cut the opening required in the plinth or panel into which the Grant Solo Hideaway unit is to be fitted The bottom edge of the opening MUST be at least 12mm above the finished floor level Refer to Figure 2 7 for the dimensions of the opening Figure 3 5 Solo Hideaway cut out and fixings holes NOTE If...

Page 10: ...om the plinth baseboard when they are connected Connect the electrical supply to the Solo fan convector unit Refer to Section 4 Electrical NOTE Do NOT fit the Solo Hideaway unit into the opening until the system has been filled and the fan convector s vented When all the Solo fan convectors have been connected to the system pipework the system can be filled Once the system is filled open the HIGHE...

Page 11: ... the lower edge Switch on the electrical supply to the fan convector at the fused double pole switch Solo Hideaway The Solo Hideaway is supplied with a pre wired 1mm2 3 core cable 1 300mm long for connection to the electrical supply This can be connected directly to a fused double pole switch located under the kitchen unit Alternatively a 3 pin 13A plug fitted with a 3A fuse can be fitted to the c...

Page 12: ...erature correctly set on the control panel refer to Section 8 2 Set required air temperature using the ON OFF button on the control panel Is the required temperature setting indicator light flashing refer to Section 8 2 Set point temperature has not yet been reached Wait until indicator light stops flashing Low heat output from fan convector Is the water flow through the fan convector too low Chec...

Page 13: ... SP0012 Any lights illuminated on the control panel Replace power and control PCB SP0129 and user interface PCB SP0128 Boost light flashing 20 C indicator light 2 bars flashing Check fans are running heat is being emitted Check power on fan output blue wire on PCB 50V AC Replace transformer SP0012 Check hot water supply to Solo is above 29 C Is the heat source functioning correctly Fix issue with ...

Page 14: ...nits have a factory fitted double pole mains ON OFF switch Solo Compact and CompactMAX models This switch is located under the right hand end of the front casing Refer to Figure 10 1 Figure 8 1 Solo Compact and CompactMAX mains ON OFF switch underside of unit Solo Hideaway model This switch is located on the right hand side of the unit It should have been set to the ON position before being finall...

Page 15: ...will then stop heating until needed again NOTE It is NOT possible to adjust the temperature setting if the water flow temperature is at less than 29 C Alarm Light The Alarm light will flash if the water flow temperature is less than 29 C Boost Cool button Press this button momentarily whilst the Solo unit is operating and the normal Solo temperature control will be overridden for a period of 20 mi...

Page 16: ...00 4 5 2006 EN 61000 4 6 2009 EN 61000 4 11 2004 EN 62233 2008 I hereby declare that the equipment named above has been tested and found to comply with the relevant sections of the above referenced specifications The unit complies with all essential requirements of the Directives Responsible Person Neil Sawers Position Technical Manager Signature Date 5th October 2018 10 DECLARATION OF CONFORMITY ...

Page 17: ...ns For guidance on the disassembly of the fan convector refer to the information given in the Servicing section of these instructions Recycling Many of the materials used in Grant fan convectors can be recycled these are listed in the table below Component Material Chassis and casing Mild steel galvanised Heat exchanger Copper tubes Aluminium fins Front casing panel wall hung units Polycarbonate C...

Page 18: ...r to contact Grant Engineering UK Limited Service Department on 44 0 1380 736920 who will arrange for a competent service engineer to rectify the fault Remember before you contact Grant Engineering UK Limited Ensure the fan convector has been installed and commissioned by a competent person in accordance with the installation and user instructions Ensure there is an electrical supply the fan conve...

Page 19: ...r s details The Company will endeavour to provide prompt service in the unlikely event of a problem occurring but cannot be held responsible for any consequential losses This guarantee applies to Grant Engineering UK Limited fan convectors purchased and installed on the UK mainland Isle of Wight Channel Islands and Scottish Isles only2 Provision of in guarantee cover elsewhere in the UK is subject...

Page 20: ...Grant Engineering UK Limited Hopton House Hopton Industrial Estate Devizes Wiltshire SN10 2EU Tel 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com www grantuk com ...

Reviews: