background image

section 4: Electrical and section 5: Commissioning

Page 11

4.1  GEnERaL  

Grant Solo fan convectors require a ~230V 1ph 50Hz electrical 

supply protected by a 3 Amp fuse.
A fused double pole switch, with contact separation of at least 

3mm in both poles, should be used for connection to the mains 

electrical supply, serving the boiler and heating system controls 

only.
For the Solo Compact and Solo CompactMAX this switch can be 

located on the wall next to the fan convector.
For the Solo Hideaway, this switch can be located in a convenient 

position for the user to access when necessary, e.g. on the wall 

above kitchen unit/worktop level or inside the kitchen unit.
For the UK, the electrical installation must be carried out by a 

competent installer in accordance with the requirements of the 

Electricity at work Regulations 1989 and BS7671:2018 – IET 

Wiring Regulations 18th Edition. 
If installed in the Republic of Ireland, the wiring installation must 

comply with all ETCI rules. All the wiring and supplementary earth 

bonding external to the boiler must be in accordance with the 

above-mentioned wiring regulations. 
Do NOT interrupt the electrical supply to the Grant Solo with any 

external controls. 

4.2  ELECtRiCaL COnnECtiOns 

Connect the electrical supply to the fan convector as follows:

sOLO COmPaCt anD sOLO COmPaCtmax 

Remove the front cover from the fan convector (if not already 

removed).

To do this, unscrew and remove the three fixing screws from 

along the lower edge of the front cover.

Pull outwards the lower front edge of the front cover and then lift it 

off the unit.
The electrical supply terminal block is located at the lower right-

hand side of the fan convector. Refer to Figure 4-1.
Pass the cable through the hole with grommet and the cable 

restraint – both located at the right-hand end of the fan convector. 

See Figure 4-1.
Connect the mains supply cable (from the fused double pole 

switch) to the terminal block as follows:

• 

Terminal L: Live – Brown wire

• 

Terminal N: Neutral – Blue wire

• 

Terminal P

E

: Earth – Green/yellow wire

Secure the cable in the cable restraint to prevent it being pulled 

out of the terminal block.
Replace the front cover on the fan convector and secure with the 

three screws along the lower edge.
Switch on the electrical supply to the fan convector at the fused 

double pole switch.

sOLO HiDEaWaY

The Solo Hideaway is supplied with a pre-wired 1mm

2

 3-core 

cable 1,300mm long for connection to the electrical supply.
This can be connected directly to a fused double pole switch 

located under the kitchen unit.

Alternatively, a 3-pin 13A plug (fitted with a 3A fuse) can be fitted 

to the cable for connection to a 3-pin socket under the kitchen 

unit and this socket is fed from a fused double pole switch located 

either within a kitchen unit or above the worktop level, as required.
Switch on the electrical supply to the fan convector at the fused 

double pole switch.

4 ELECtRiCaL

Ensure that the system is filled and vented and that each Solo fan 

convector has also been vented. Refer to either Section 3.6 or 3.7 

as required.
Switch on the mains electrical supply to the fan convector at the 

fused isolator.
Switch the mains ON/OFF switch to ON.
On the Solo Compact and CompactMAX models, the mains 

switch is located under the right-hand end of the front casing. 

Refer to Figure 8-1.
On the Solo Hideaway model, the mains switch is located on the 

right-hand side of the unit and should have been set to the ON 

position before being finally fitted in to the plinth/baseboard. Refer 

to Figure 8-2.
Switch the boiler or heat pump on and set the heating system 

controls to call for heat.

Operate the heating system to raise the flow temperature 

REFERRinG tO sECtiOn 8 – OPERatinG 

instRUCtiOns

Check the operation of the Solo fan convector(s) as follows:
Press and hold the ON/OFF button on the Solo fan convector 

control panel to switch the unit on.

The Alarm/Boost light will flash until the water flow temperature 

reaches 29°C. 

When the flow temperature reaches at 29°C the Alarm/Boost light 

will stop flashing and one of the temperature Indicator lights will 

be lit – either flashing or constant. 

Using the ON/OFF button, set the air temperature to each one of 

the four settings in turn to check their operation and then finally 

set the air temperature to the required setting.

! nOtE !

it is nOt possible to adjust the temperature setting if the 

water flow temperature is at less than 29°C.

Press the Boost/Cool button to check the boost function operation.
Press the Boost/Cool button again to switch the boost function off.
Set the heating system controls to the user’s requirements.

5 COmmissiOninG

Summary of Contents for Solo Compact

Page 1: ...UK DOC 0139 Rev 1 0 October 2018 Grant Solo Fan Convectors Installation and User Instructions ...

Page 2: ...tallation commissioning and servicing of the Grant Solo fan convectors After installion leave these instructions with the user User instructions to guide users in the operation of the fan convectors are given in Section X of these instructions Special Text Formats The following special text formats are used in these instructions for the purposes listed below WARNING Warning of possible human injur...

Page 3: ...edure 8 Solo Compact and Solo CompactMAX models 3 8 Installation procedure 9 Solo Hideaway model 4 Electrical 11 4 1 General 11 4 2 Electrical connections 11 Contents Page 3 5 COMMISSIONING 11 6 Fault finding 12 6 1 Initial checks 12 6 2 Fault diagnosis flow chart 13 7 Spares PARTS 14 7 1 Fan convector parts list 14 8 OPERATING INSTRUCTIONS 14 8 1 Mains ON OFF switch 14 8 2 Control panel 15 9 Clea...

Page 4: ...ase but is insulated from it providing a low casing surface temperature regardless of the water flow temperature The top grille prevents contact with the heat exchanger With the electrical supply to the Solo fan convector switched on when the water temperature sensor located in the heat exchanger detects that the water temperature entering the unit exceeds 29 C the unit will start The air temperat...

Page 5: ...eration After this period has elapsed the Solo unit automatically returns to the normal temperature control with the fan operating at either Low or High setting as dictated by the difference between the air temperature and the air temperature setting on the unit 1 3 CONTROL PANEL OVERVIEW Grant Solo fan convectors are supplied with a simple control panel Refer to Figure 1 3 and Section 8 2 control...

Page 6: ... power W 4 4 4 Sound pressure level at 1 metre ISO 3744 Low speed dB A 18 18 18 High speed dB A 22 23 22 Boost dB A 38 39 38 2 2 PERFORMANCE DATA Table 2 2 Heating capacity BS EN ISO 16430 on high low fan speed Mean water temperature Units Solo Compact Solo CompactMAX Solo Hideaway High Low High Low High Low 35 C W 314 247 604 470 314 247 40 C W 426 335 831 646 426 335 45 C W 542 426 1 071 832 542...

Page 7: ...t for sealed water systems Code of practice for domestic heating and hot water supply 3 3 Location Solo Compact and CompactMAX fan convectors should be positioned with the lower edge approximately 75 100mm above the skirting level The Solo Hideaway fan convectors are fitted into the plinth or baseboard of fixed units e g kitchen units Refer to Section 3 7 for dimension of the opening required The ...

Page 8: ... and return pipework Solo Hideaway The flow and return connections are located on the right hand side of the unit To allow the unit to be fully withdrawn from the plinth or base board in which it is fitted without having to disconnect it from the system two flexible hose connections supplied will be required for installation of the Grant Solo Hideaway fan convector These are long enough to allow t...

Page 9: ...Refer to Section 5 Commissioning 3 8 Installation procedure Solo Hideaway model Accurately mark and cut the opening required in the plinth or panel into which the Grant Solo Hideaway unit is to be fitted The bottom edge of the opening MUST be at least 12mm above the finished floor level Refer to Figure 2 7 for the dimensions of the opening Figure 3 5 Solo Hideaway cut out and fixings holes NOTE If...

Page 10: ...om the plinth baseboard when they are connected Connect the electrical supply to the Solo fan convector unit Refer to Section 4 Electrical NOTE Do NOT fit the Solo Hideaway unit into the opening until the system has been filled and the fan convector s vented When all the Solo fan convectors have been connected to the system pipework the system can be filled Once the system is filled open the HIGHE...

Page 11: ... the lower edge Switch on the electrical supply to the fan convector at the fused double pole switch Solo Hideaway The Solo Hideaway is supplied with a pre wired 1mm2 3 core cable 1 300mm long for connection to the electrical supply This can be connected directly to a fused double pole switch located under the kitchen unit Alternatively a 3 pin 13A plug fitted with a 3A fuse can be fitted to the c...

Page 12: ...erature correctly set on the control panel refer to Section 8 2 Set required air temperature using the ON OFF button on the control panel Is the required temperature setting indicator light flashing refer to Section 8 2 Set point temperature has not yet been reached Wait until indicator light stops flashing Low heat output from fan convector Is the water flow through the fan convector too low Chec...

Page 13: ... SP0012 Any lights illuminated on the control panel Replace power and control PCB SP0129 and user interface PCB SP0128 Boost light flashing 20 C indicator light 2 bars flashing Check fans are running heat is being emitted Check power on fan output blue wire on PCB 50V AC Replace transformer SP0012 Check hot water supply to Solo is above 29 C Is the heat source functioning correctly Fix issue with ...

Page 14: ...nits have a factory fitted double pole mains ON OFF switch Solo Compact and CompactMAX models This switch is located under the right hand end of the front casing Refer to Figure 10 1 Figure 8 1 Solo Compact and CompactMAX mains ON OFF switch underside of unit Solo Hideaway model This switch is located on the right hand side of the unit It should have been set to the ON position before being finall...

Page 15: ...will then stop heating until needed again NOTE It is NOT possible to adjust the temperature setting if the water flow temperature is at less than 29 C Alarm Light The Alarm light will flash if the water flow temperature is less than 29 C Boost Cool button Press this button momentarily whilst the Solo unit is operating and the normal Solo temperature control will be overridden for a period of 20 mi...

Page 16: ...00 4 5 2006 EN 61000 4 6 2009 EN 61000 4 11 2004 EN 62233 2008 I hereby declare that the equipment named above has been tested and found to comply with the relevant sections of the above referenced specifications The unit complies with all essential requirements of the Directives Responsible Person Neil Sawers Position Technical Manager Signature Date 5th October 2018 10 DECLARATION OF CONFORMITY ...

Page 17: ...ns For guidance on the disassembly of the fan convector refer to the information given in the Servicing section of these instructions Recycling Many of the materials used in Grant fan convectors can be recycled these are listed in the table below Component Material Chassis and casing Mild steel galvanised Heat exchanger Copper tubes Aluminium fins Front casing panel wall hung units Polycarbonate C...

Page 18: ...r to contact Grant Engineering UK Limited Service Department on 44 0 1380 736920 who will arrange for a competent service engineer to rectify the fault Remember before you contact Grant Engineering UK Limited Ensure the fan convector has been installed and commissioned by a competent person in accordance with the installation and user instructions Ensure there is an electrical supply the fan conve...

Page 19: ...r s details The Company will endeavour to provide prompt service in the unlikely event of a problem occurring but cannot be held responsible for any consequential losses This guarantee applies to Grant Engineering UK Limited fan convectors purchased and installed on the UK mainland Isle of Wight Channel Islands and Scottish Isles only2 Provision of in guarantee cover elsewhere in the UK is subject...

Page 20: ...Grant Engineering UK Limited Hopton House Hopton Industrial Estate Devizes Wiltshire SN10 2EU Tel 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com www grantuk com ...

Reviews: