Troubleshooting
332590A
11
Temperature data not displayed on
website.
4-pin connector is not plugged into
the correct terminal on the tempera-
ture control board or module.
Ensure unit is properly installed.
See Installation on page 3.
Reactor temperature measurement
is not working.
See Reactor repair manual.
Hose zone temperature data not
displayed on website.
The RTD or thermocouple is not
correctly installed on the hose or is
broken.
See Reactor repair manual.
Pressure data not displayed on
website.
4-pin connector is not plugged into
the correct terminal on the tempera-
ture control board or module.
Ensure unit is properly installed.
See Installation on page 3.
Reactor pressure measurement is
not working.
See Reactor repair manual.
Pressure setpoints not displayed on
website.
Unit installed on a hydraulic Reac-
tor.
Hydraulic Reactor pressure is set
manually. InSite will not report a
pressure setpoint on hydraulic
Reactors.
Problem
Cause
Solution