Available Internal Data
3A6338B
9
Automation Inputs (signals from EFR system to PLC)
Instance ID
Description
Data Type
BIT
Input Byte
Index’s
1
Heartbeat To PLC
Boolean
0
0
2
System On
Boolean
1
3
System Ready
Boolean
2
4
Active Alarms
Boolean
3
5
Active Deviations
Boolean
4
6
Active Advisories
Boolean
5
7
Current Sequence is Playing
Boolean
6
8
Current Sequence is Paused
Boolean
7
9
Current Sequence is Stopped
Boolean
8
1
10
Dispense Valve Open
Boolean
9
11
System is Priming
Boolean
10
12
System is Purging
Boolean
11
13
System is Parking
Boolean
12
14
System is Depressurizing
Boolean
13
15
Gel Shot is Running
Boolean
14
16
EFR is Dispensing
Boolean
15
17
{Reserved Bits}
Boolean
16-23
2
18
{Reserved Bits}
Boolean
24-31
3
19
Current Active Sequence
uint8
0-7
4
20
Current Step of the Active Sequence
uint8
0-7
5
21
Time Remaining to Complete Step (XX.X s)
uint16
0-7
6
8-15
7
22
Red Pump Outlet Pressure (XXXX.X bar)
uint16
0-7
8
8-15
9
23
Blue Pump Outlet Pressure (XXXX.X bar)
uint16
0-7
10
8-15
11
24
Red Pump Inlet Pressure (XXXX.X bar)
uint16
0-7
12
8-15
13
25
Blue Pump Inlet Pressure (XXXX.X bar)
uint16
0-7
14
8-15
15
26
Pump Flow Rate (XXXX cc/min)
uint16
0-7
16
8-15
17
27
Active Error Number Requiring Acknowledgment
uint8
0-7
18
28
Active Operator Mode Dispense Flow Rate
(XXXX cc/min)
uint16
0-7
19
8-15
20
29
Data Exchanged Element Selected
uint8
0-7
21
30
Data Exchanged Element Value
uint16
0-7
22
8-15
23
31
Selected Step of the Active Sequence
uint8
0-7
24
32
Selected Step Amount (XXXX.XX)
uint32
0-7
25
8-15
26
16-23
27
24-31
28