Installation
12
313813A
F
IG
. 4: Intrinsically Safe Installation
CLASS I, DIV I, GROUP D
Main Control
Panel
Safety
Barrier
Machine
Frame
Panel
Intrinsically
Safe Wiring
through
Barriers
460 VAC Supply Voltage
Robot
Base
X-P
SO
X-P
SO
X-P
SO
ISO
Metering
Pump
Robot
Control
Cabinet
POLY
Tempered
Water
Unit
ISO
Tempered
Water
Unit
POLY
Metering
Pump
ISO
Heater
X-P
SO
X-P
SO
X-P
SO
ISO
Agitator
X-P
SO
X-P
SO
X-P
SO
ISO
Agitator
POLY
Heater
All conduits must be rigid metal conduit
X-P SO = Explosion Proof Seal-Off
HAZARDOUS (CLASSIFIED) LOCATION
NON-HAZARDOUS
LOCATION ONLY
NOTES:
1. All intrinsically safe conduits/wires/cables are to enter the main control panel on the safety barrier side of the main control panel. This wiring
must not come near or in contact with any non-intrinsically safe wiring.
2. Any replacement of intrinsically safe barriers must be an identical replacement to maintain intrinsically safe circuit rating.
3. The non-intrinsically safe terminals (power rail) must not be connected to any device which uses or generates more than 250 Vrms or d.c.
unless it has been determined that the voltage has been adequately isolated.
4. The installation must meet the requirements of the National Electric Code, NFPA 70, Article 504 Resp., Article 505 and ANSI/ISA 12.06.01
5. Multiple earthing of components is allowed only if high integrity equipotential system is realized between the points of bonding.
6. Do not operate system with safety barrier cover removed.
WARNING:
Substitution of components may impair intrinsic safety. For installation, maintenance or operation instructions, see instruction
manual.