Gossen MetraWatt PROFITEST PRCD Operating Instructions Manual Download Page 6

6

GMC-I Messtechnik GmbH

Simulation of “Interference Voltage in the Protec-
tive Conductor” with Probe

In the case of type S PRCDs (PRCD-S), the 
on/off key is made of a conductive material 
or coated with conductive plastic so that the 
sensor inside the device is capable of 
detecting dangerous contact voltage at the 
protective conductor terminal of the electri-
cal power connection in the form of a differ-
ence in potential relative to the user’s con-
tacting finger.
During simulation of the “interference voltage 
in the protective conductor” fault (tripping 
test / potential fault as extended function 
test for PRCD-S) by touching the on/off key 
of the single-phase PRCD (PRCD-S) with 
the probe, a difference in potential between 
the contactable sensor surface and the pro-
tective conductor terminal is generated 
which causes tripping of the PRCD-S.
The probe socket on the PRCD adapter is 
connected to the phase conductor (L) of the 
power supply network via a series resistor 
(safety impedance) with a value of 1 M

Ω

 

using the test adapter’s earthing contact 
plug to this end.
Touch current at the probe socket is limited 
by the internal protective circuit to less than 
the maximum permissible value of 0.5 mA in 
accordance with DIN EN 61010-1.
Execution of this test results in maximum 
touch current of: 

Measuring Protective Conductor Current

Protective conductor current or bias current 
may result in premature tripping of PRCDs. 
For this reason, the protective conductor is 
led out of the housing as a loop between 
surface mount sockets 4 and 6. This makes 
it possible to measure any protective con-
ductor current with the help of a current 
clamp transformer. 

3

Initial Start-Up

See the connections overview on page 2 for 
all connection variants.

3.1

Testing the LEDs

Before performing any measurements, the 
LEDs should be tested for correct function-
ing.

Single-Phase Mains Connection

Insert the earthing contact plug into the 
earthing contact mains outlet, remove it, 
rotate it 180° and insert it again.

When connected with correct polarity, the 

PRCD IN L1

 LED must light up, and when 

rotated 180° the 

PRCD IN

 

L1

 and 

PRCD IN PE

 

LEDs must light up simultaneously.

3-Phase Mains Connection

Insert the CEE plug into the CEE outlet.

The 

PRCD IN L1

L2

 and 

L3

 LEDs must light 

up. If any of the phase conductors are con-
nected to the neutral conductor, i.e. L1-N, 
L2-N or L3-N, N lights up instead Lx. If any 
of the phase conductors are connected to 
protective earth, i.e. L1-PE, L2-PE or L3-PE, 
PE lights up instead of Lx.

3.2

Mains Connection

The test adapter must be connected to the 
mains for fault simulation, as well as for indi-
cation by means of the phase LEDs.

Connect the test adapter to the mains 
via the single or 3-phase mains power 
cable. Refer to the characteristic values 
on page 14 for nominal mains values.

Attention!

!

Single-Phase Mains Connection

 

For correct phase connection, the 
earthing contact plug must inserted 
into the mains outlet such that only 
the 

PRCD IN L1

 LED lights up. 

The 

PRCD IN

 PE LED lights up as well 

in the case of polarity reversal.

I

T

 [A] = 

U

Mains (L–PE)

 [V]

1 M

Ω

PROFI

TEST

P

RCD

Initial Start-Up 

Summary of Contents for PROFITEST PRCD

Page 1: ... PRCD Adapter for Standards Compliant Testing of PRCDs by Simulating Faults 3 349 797 15 7 4 19 Important Read carefully before use Keep on file for future reference Please observe the manufacturer s details on the devices under test ...

Page 2: ...6 for connecting the PROFITEST MXTRA during protective con ductor and insulation measurements 10 PRCD outlet sockets connected in paral lel to plugs 1 and 2 for connecting the PROFITEST MXTRA during protective con ductor and insulation measurements 11 Five replaceable fuses Instrument Overview 8 7 6 4 1 2 10 3 9 Mains Connection To PRCD Outlet To PRCD Inlet PRCD IN 5 11 PRCD OUT Fault Selection Ma...

Page 3: ...tor Resistance Rlo 7 4 2 Measuring Insulation Resistance Riso 8 4 3 Tripping Test with Nominal Residual Current and Measurement of Time to Trip 8 4 4 Varistor Test PRCD K 9 5 Protective Conductor Current Measurement 9 6 Fault Simulation 10 6 1 PRCD S single phase 10 6 1 1 Simulated Interruption 10 6 1 2 Simulated Wire Reversal 10 6 1 3 Simulation of PE to Phase PE UEXT 10 6 1 4 Contacting the ON K...

Page 4: ...ment cables are in flawless condition e g no damage to insulation no cracks in cables or plugs etc When using a test probe with coil cord PROFITEST MXTRA Grip the tip of the test probe firmly for example during insertion into a jack socket Tensioning at the coil cord may otherwise cause the test probe to snap back resulting in possible injury Touch current at the probe socket is limited by the int...

Page 5: ...Fault indication by means of LEDs on the test adapter Attention In any case comply with the manu facturer s recommendations con cerning tests to be conducted in accordance with DGUV Provision 3 Testing of PRCDs with the Test Adapter by Simu lating Faults and Measuring Protective Conductor and Insulation Resistance as well as Tripping Current and Time to Trip using the PROFITEST MXTRA Test Instrume...

Page 6: ...ctive conductor is led out of the housing as a loop between surface mount sockets 4 and 6 This makes it possible to measure any protective con ductor current with the help of a current clamp transformer 3 Initial Start Up See the connections overview on page 2 for all connection variants 3 1 Testing the LEDs Before performing any measurements the LEDs should be tested for correct function ing Sing...

Page 7: ... whose protective conduc tor is not switched as well as for insulation mea surements Rins with the PROFITEST MXTRA 4 1 Measuring Protective Conductor Resistance Rlo As opposed to the usual default setting for low resistance measurements the device under test does not have to be discon nected from all sources of voltage in this case Depending on the PRCD the rotary selector switches have to be set ...

Page 8: ...sidual Cur rent and Measurement of Time to Trip Note If you operate your test adapter at an electrical system with a 30 mA breaker the mains RCCB may be tripped during the tripping test tripping current and time to trip instead of the PRCD In this case the MAINS L1 LED goes out In order to prevent an upstream RCD also non selevtive RCD from being tripped and to ensure that the actual tripping curr...

Page 9: ...n 30 mA R 220 Ω 1 W For PRCD K with In 10 mA R 620 Ω 0 5 W 3 Switch on PRCD K by pressing the ON button 4 Press key T device must trip PE circuit is functioning properly The shutdown test of the PRCD K stipulated by KOPP at this point is performed in con nection with the testing of the RCD protec tion device with a continuously rising resid ual current until the device is tripped 5 Protective Cond...

Page 10: ...the orange area for single phase wire reversal Instead of the L1 LED the PE LED must light up It must not be possible to activate the PRCD when this fault is simulated 6 1 3 Simulation of PE to Phase PE UEXT Set the left hand rotary selector switch to the PE UEXT position The L1 LED and the PE LED PE light up It must not be possible to activate the PRCD when this fault is simulated Step Rotary Swi...

Page 11: ...turning the right hand rotary selector switch to the 1 ON position 6 2 1 Simulated Interruption Start with the left hand rotary se lector switch in the first ON position in the orange area for single phase interrup tion Switch through the positions one after the other in the clockwise direction ta ble from top to bottom Due to its design the following tests are omitted for the PRCD K PE interrupti...

Page 12: ...onnection although N is interrupted Note Tripping performance may deviate from this example in the case of PRCDs from other manufacturers adhere to the manufacturer s test instructions Step Rotary Switch Test Adapter PRCD Action L1 LED L2 LED L3 LED N LED PE LED LED 1 Activate the PRCD 2 The PRCD is tripped It must not be possible to reactivate it 3 Activate the PRCD 4 The PRCD is tripped It must ...

Page 13: ...ible to activate the PRCD when this fault is simulated Step 18 see section entitled Protective Conductor Current Measurement on page 9 Step Rotary Switch Test Adapter PRCD Action L1 LED L2 LED L3 LED N LED PE LED LED 11 It must not be possible to activate the PRCD 12 It must not be possible to activate the PRCD 13 It must not be possible to activate the PRCD 14 It must not be possible to activate ...

Page 14: ... 230 400 V 3P N PE 16 A Throughput rating Earth contact 10 VA CEE 30 VA Power consumption Earth contact 2 VA CEE 4 VA Electrical Safety Measurement category 300 V CAT II Pollution degree 2 Fuse links 5 ea FF315mA 500V Ambient Conditions Operating temperature 5 50 C Storage temperature 20 60 C Relative humidity Max 75 no condensation allowed Mechanical Design Test adapter protection IP 40 per DIN V...

Page 15: ...g positions in which errors are simulated for measuring purposes must be exempt from this test Conductor interruption PE orange PE green 3P 30 MΩ Reversed conductors L1 PE orange L1 PE green L2 PE green L3 PE green 30 MΩ Voltage on protective conductor PE Uext green orange approx 1 5 MΩ Connection and or Contacting of PRCD Adapter 3 phase 400 V The protective conductor resistance test is performed...

Page 16: ...w This device is subject to the RoHS directive Furthermore we make reference to the fact that the current status in this regard can be accessed on the Internet at www gossenmetrawatt com by entering the search term WEEE In accordance with WEEE 2012 19 EU and ElektroG we identify our electrical and electronic devices with the symbol in accor dance with DIN EN 50419 which is shown at the right Devic...

Reviews: