Gossen MetraWatt PROFITEST PRCD Operating Instructions Manual Download Page 4

4

GMC-I Messtechnik GmbH

1

Safety Precautions

The test adapter has been manufactured 
and tested in accordance with the following 
safety regulations:
IEC/EN 61010-1 / VDE 0411-1, DIN VDE 
0404, IEC/EN 61577 / VDE 0413-2,-4 / 
DIN EN 61557-16 / VDE 0413-16 (draft)
Safety of the operator, as well as that of the 
test adapter and the PRCD, is only assured 
when it is used for its intended purpose.

Read the operating instructions carefully and 
completely before placing your test instrument 
into service. Follow all instructions contained 
therein. Make sure that the operating instructions 
are available to all users of the instrument. 
Read the operating instructions for the PROFITEST 
MXTRA as well, in particular the sections con-
cerning the R

LO

, R

ISO

 and time-to-trip measure-

ments, as well as the tripping test.

Tests may only be performed by a qualified 
electrician, or under the supervision and 
direction of a qualified electrician. The user 
must be instructed by a qualified electrician 
concerning performance and evaluation of 
the test.

Observe the following safety precautions:

The instrument may only be connected 
to electrical systems with a maximum of 
230/400 V which comply with applicable 
safety regulations (e.g. IEC 60346, VDE 
0100) and are protected with a fuse or 
circuit breaker with a maximum rating of 
16 A.

The test adapter may only be used for 
testing PRCDs.

No power consuming devices may be 
connected to the earthing contact and 
CEE sockets.

The test adapter may not be used as an 
extension cord.

Measurements within electrical systems 
are prohibited.

Make certain that the measurement 
cables are in flawless condition, e.g. no 
damage to insulation, no cracks in 
cables or plugs etc.

When using a test probe with coil cord 
(

PROFITEST MXTRA)

Grip the tip of the test probe firmly, for 
example during insertion into a jack 
socket. Tensioning at the coil cord may 
otherwise cause the test probe to snap 
back resulting in possible injury.

Touch current at the probe socket is 
limited by the internal protective circuit to 
less than the maximum permissible value 
of 0.5 mA in accordance with 
DIN EN 61010-1.

Insulation resistance can only be mea-
sured at voltage-free objects.

Do not touch the insulation measuring 
instrument’s test probes (

PROFITEST 

MXTRA)

 during insulation resistance mea-

surements!

Please observe the manufacturer‘s 
details on the devices under test!

Fuse Replacement

All fuses for neutral and phase conductors 
are accessible from the outside (see section 
8.3). The fuses m
ay only be replaced when 
the instrument is voltage-free, i.e. the instru-
ment must be disconnected from mains 
supply power and may not be connected to 
a measuring circuit. The fuse type must 
comply with the specifications in the techni-
cal data or the labeling on the instrument 
(see section 7).

Opening the Instrument / Repairs

The test adapter may only be opened by 
authorized, trained personnel in order to 
ensure flawless operation and to assure that 
the guarantee is not rendered null and void.
Even original replacement parts may only be 
installed by authorized, trained personnel.
If it can be ascertained that the test adapter 
has been opened by unauthorized person-
nel, no guarantee claims can be honored by 
the manufacturer with regard to personal 
safety, measuring accuracy, compliance 
with applicable safety measures or any con-
sequential damages.

PROFI

TEST

P

RCD

Safety Precautions

Summary of Contents for PROFITEST PRCD

Page 1: ... PRCD Adapter for Standards Compliant Testing of PRCDs by Simulating Faults 3 349 797 15 7 4 19 Important Read carefully before use Keep on file for future reference Please observe the manufacturer s details on the devices under test ...

Page 2: ...6 for connecting the PROFITEST MXTRA during protective con ductor and insulation measurements 10 PRCD outlet sockets connected in paral lel to plugs 1 and 2 for connecting the PROFITEST MXTRA during protective con ductor and insulation measurements 11 Five replaceable fuses Instrument Overview 8 7 6 4 1 2 10 3 9 Mains Connection To PRCD Outlet To PRCD Inlet PRCD IN 5 11 PRCD OUT Fault Selection Ma...

Page 3: ...tor Resistance Rlo 7 4 2 Measuring Insulation Resistance Riso 8 4 3 Tripping Test with Nominal Residual Current and Measurement of Time to Trip 8 4 4 Varistor Test PRCD K 9 5 Protective Conductor Current Measurement 9 6 Fault Simulation 10 6 1 PRCD S single phase 10 6 1 1 Simulated Interruption 10 6 1 2 Simulated Wire Reversal 10 6 1 3 Simulation of PE to Phase PE UEXT 10 6 1 4 Contacting the ON K...

Page 4: ...ment cables are in flawless condition e g no damage to insulation no cracks in cables or plugs etc When using a test probe with coil cord PROFITEST MXTRA Grip the tip of the test probe firmly for example during insertion into a jack socket Tensioning at the coil cord may otherwise cause the test probe to snap back resulting in possible injury Touch current at the probe socket is limited by the int...

Page 5: ...Fault indication by means of LEDs on the test adapter Attention In any case comply with the manu facturer s recommendations con cerning tests to be conducted in accordance with DGUV Provision 3 Testing of PRCDs with the Test Adapter by Simu lating Faults and Measuring Protective Conductor and Insulation Resistance as well as Tripping Current and Time to Trip using the PROFITEST MXTRA Test Instrume...

Page 6: ...ctive conductor is led out of the housing as a loop between surface mount sockets 4 and 6 This makes it possible to measure any protective con ductor current with the help of a current clamp transformer 3 Initial Start Up See the connections overview on page 2 for all connection variants 3 1 Testing the LEDs Before performing any measurements the LEDs should be tested for correct function ing Sing...

Page 7: ... whose protective conduc tor is not switched as well as for insulation mea surements Rins with the PROFITEST MXTRA 4 1 Measuring Protective Conductor Resistance Rlo As opposed to the usual default setting for low resistance measurements the device under test does not have to be discon nected from all sources of voltage in this case Depending on the PRCD the rotary selector switches have to be set ...

Page 8: ...sidual Cur rent and Measurement of Time to Trip Note If you operate your test adapter at an electrical system with a 30 mA breaker the mains RCCB may be tripped during the tripping test tripping current and time to trip instead of the PRCD In this case the MAINS L1 LED goes out In order to prevent an upstream RCD also non selevtive RCD from being tripped and to ensure that the actual tripping curr...

Page 9: ...n 30 mA R 220 Ω 1 W For PRCD K with In 10 mA R 620 Ω 0 5 W 3 Switch on PRCD K by pressing the ON button 4 Press key T device must trip PE circuit is functioning properly The shutdown test of the PRCD K stipulated by KOPP at this point is performed in con nection with the testing of the RCD protec tion device with a continuously rising resid ual current until the device is tripped 5 Protective Cond...

Page 10: ...the orange area for single phase wire reversal Instead of the L1 LED the PE LED must light up It must not be possible to activate the PRCD when this fault is simulated 6 1 3 Simulation of PE to Phase PE UEXT Set the left hand rotary selector switch to the PE UEXT position The L1 LED and the PE LED PE light up It must not be possible to activate the PRCD when this fault is simulated Step Rotary Swi...

Page 11: ...turning the right hand rotary selector switch to the 1 ON position 6 2 1 Simulated Interruption Start with the left hand rotary se lector switch in the first ON position in the orange area for single phase interrup tion Switch through the positions one after the other in the clockwise direction ta ble from top to bottom Due to its design the following tests are omitted for the PRCD K PE interrupti...

Page 12: ...onnection although N is interrupted Note Tripping performance may deviate from this example in the case of PRCDs from other manufacturers adhere to the manufacturer s test instructions Step Rotary Switch Test Adapter PRCD Action L1 LED L2 LED L3 LED N LED PE LED LED 1 Activate the PRCD 2 The PRCD is tripped It must not be possible to reactivate it 3 Activate the PRCD 4 The PRCD is tripped It must ...

Page 13: ...ible to activate the PRCD when this fault is simulated Step 18 see section entitled Protective Conductor Current Measurement on page 9 Step Rotary Switch Test Adapter PRCD Action L1 LED L2 LED L3 LED N LED PE LED LED 11 It must not be possible to activate the PRCD 12 It must not be possible to activate the PRCD 13 It must not be possible to activate the PRCD 14 It must not be possible to activate ...

Page 14: ... 230 400 V 3P N PE 16 A Throughput rating Earth contact 10 VA CEE 30 VA Power consumption Earth contact 2 VA CEE 4 VA Electrical Safety Measurement category 300 V CAT II Pollution degree 2 Fuse links 5 ea FF315mA 500V Ambient Conditions Operating temperature 5 50 C Storage temperature 20 60 C Relative humidity Max 75 no condensation allowed Mechanical Design Test adapter protection IP 40 per DIN V...

Page 15: ...g positions in which errors are simulated for measuring purposes must be exempt from this test Conductor interruption PE orange PE green 3P 30 MΩ Reversed conductors L1 PE orange L1 PE green L2 PE green L3 PE green 30 MΩ Voltage on protective conductor PE Uext green orange approx 1 5 MΩ Connection and or Contacting of PRCD Adapter 3 phase 400 V The protective conductor resistance test is performed...

Page 16: ...w This device is subject to the RoHS directive Furthermore we make reference to the fact that the current status in this regard can be accessed on the Internet at www gossenmetrawatt com by entering the search term WEEE In accordance with WEEE 2012 19 EU and ElektroG we identify our electrical and electronic devices with the symbol in accor dance with DIN EN 50419 which is shown at the right Devic...

Reviews: