Exiting the Line Fault Recording Mode
➭
The line fault recording mode is exited by pressing and
holding the
ESC|FUNC
key.
Note!
☞
Automatic shut-off is disabled in the line fault
recording mode.
21.2
Trigger Parameters for Line Fault Recording
An overview (flow chart) of the complete trigger menu can
be found on page 54.
Mains Failure Measuring Range:
MAinS rAnGE
A measuring range of either 300 V or 600 V can be entered
here for line fault recording.
SEt
↵
V
triG
↵
V
MAinS
↵
rAnGE: 300/600 V
VU
↵
Trigger Thresholds
H-triG
and
L-triG
Measuring function V for line fault recording requires its
own upper and lower thresholds for triggering purposes.
The upper limit should always be greater than the respec-
tive lower limit.
Entering upper and lower thresholds in digits:
SEt
↵
V
triG
↵
V
MAinS
↵
rAnGE: XXXX V
↵
e.g.
600 V
H-triG: XXXXXX
VU
↵
e.g. 250000 = 250.00 V
L-triG: XXXXXX
VU
↵
e.g. 190000 = 190.00 V
Examples for the entry of trigger thresholds in digits can be
found in the table in Chapter 17.1, page 32.
Drop Out Trigger Level:
triG drPout
A level with a value ranging from 0 V and 600 V can be
selected here in 10 V steps for the mean value of the volt-
age measurement for the respective time period.
SEt
↵
V
triG
↵
V
MAinS
↵
rAnGE: XXXX V
↵
H-triG: XXXXXX
↵
L-triG: XXXXXX
↵
triG drPout: 0 ... 600 V
VU
↵
Pulse Trigger:
triG PULSE
A trigger level can be selected here as an absolute value
for transient voltages which are superimposed upon the
line voltage.
SEt
↵
V
triG
↵
V
MAinS
↵
rAnGE: XXXX V
↵
H-triG: XXXXXX
↵
L-triG: XXXXXX
↵
triG drPout: XXXX V
↵
triG PULSE: amplitudes from 200 to 600 V
VU
↵