Gordon RC4000 Series Owner'S Manual Download Page 17

Power Input Wiring

All power wires must be brought into the box through the .860"
(21.8mm) hole on the left side, using a suitable ½" (13mm)
electrical fitting.  Wire size must conform to local electrical
code requirements for 8 amperes (normally #14 AWG will
meet these requirements).

Set the 115/230 volt selector switch to the proper position.
Connect three-wire 115 or 230 VAC, single phase power to
terminals 1, 2 and 3.  Terminal 1 must be well grounded to a
common electrical ground.  The AC line power must be sup-
plied from a disconnect box that is either fused or equipped
with circuit breakers.

Output Wiring

If you use a permanent magnet motor in your application,
connect the motor armature wires to terminals 4 and 5 - please
note the polarity of the terminals and your armature wires - if
you reverse the polarity, your motor will run in the opposite
direction.  Terminals 6 and 7 are not used with permanent
magnet motors.

If you use a shunt wound motor for your application, connect
the motor armature wires to terminals 4 and 5 - please note the
polarity of the terminals and your armature wires - if you
reverse the polarity, your motor will run in the opposite direc-
tion.  Then, connect the motor field wires to terminals 6 and 7

- once again, be sure to observe the polarity of the terminals
and your field wires.

Modification 04A060 must be installed on any RC4000M Reel
Control that is intended for use with Form Factor 1.0 motors
(Bodine Electric has a line of these), as follows:

04A060-1

for1/50, 1/20 & 1/12 HP

04A060-2

for 1/8 HP 

04A060-3

for 1/4 HP

In general, all wire should be heavy enough to accept crimped,
push-on style terminals and to withstand the rigors of your
production environment.

Auto Interlock

This feature allows external on-off control of the reel motor in
AUTO mode only.  See page 9 for details.

Shut-off Interlock

This feature allows external shut-off control of the reel motor
in both Auto and Manual modes.   See page 9 for details.

Relay Outputs

The  Operation section describes the procedure for enabling
the High and Low Limit Relays.  See page 9 for details.

RC4000M Installation

www.gordoneng.com

1.800.315.9233

13

Mounting Flange

Press

Mounting Bracket

Box

Lockwasher

Nut

3/4" Washer

Nut

Shock Mount

Lockwasher

CAUTION! DO NOT

OVERTIGHTEN!

03A155 SHOCK MOUNT KIT

03A155 - Shock Mount Kit

Our 03A155 shock mount kits 

contain Lord Corporation’s

# SMB006-0100-7 shock mounts.

We recommend that you use these

or their equivalents, whenever the

control unit is mounted in a high

vibration environment.

Wiring Terminals

for RC4000

and RC4000M

Summary of Contents for RC4000 Series

Page 1: ...Series Reel Control Systems http www gordoneng com revision date 05 17 01 Owner s Manual Installation Operation and Applications R e e l o r T ake Up Dereel or Payoff 1 800 315 9233 call toll free in...

Page 2: ...This product will be repaired or replaced for five years from the date of purchase if it fails to perform to published specifications The product must be used in accordance with the specified manufac...

Page 3: ...ions RC4000 Reel Control page 2 RC4000M Reel Control page 3 ii Contents 8 9 RC4000 Installation Input Output Wiring page 9 Interlocks page 9 Shock Mounts page 9 4 6 Antenna Selection 7 Speed Reduction...

Page 4: ......

Page 5: ...ty motor controllers while the RC4000M has a self contained motor controller The control unit determines the load and status of the antenna assembly and establishes a tuned RF sensing field around the...

Page 6: ...ted by dirt grease vibration etc temperature 0 F 130 F humidity 0 95 R H RC4000 Specifications 2 www gordoneng com 1 800 315 9233 Keypad Controls SELECT in setup mode push to select reel or dereel mod...

Page 7: ...dia 21 84mm B Hole C Coupler 50 dia 12 7mm B C Top View Front View base only Side View 4 Mounting Holes clearance holes for 250 6mm bolt 7 30 185 42mm Fuse Holder RC4000M Specifications www gordoneng...

Page 8: ...f material sizes are processed by the same equipment Process down time is kept to a minimum allowing you to maximize productivity Once you ve determined the size of the material you wish to control ju...

Page 9: ...ip 1 3 strip 3 5 strip 3 5 strip 4 7 strip 4 7 strip 6 or wider strip Part Number 04A073 04A074 04A091 04A092 04A067 04A068 04A069 04A071 04A070 04A072 04A088 Flat L e n g t h o f V Antenna idth W Cab...

Page 10: ...r 2 4 meters and optional lengths of fifteen feet 15 or 4 6 meters and twenty five feet 25 or 7 62 meters are readily available Mount your antenna so the material runs through the middle of the V and...

Page 11: ...sed for example for a motor rated at 1725 RPM calculate the ratio for 1500 RPM Sample Calculation 1500 3 14 6 1000 Where S 1500 RPM F 1000 units of measure min d 6 units of measure Note the Speed S at...

Page 12: ...uration with the Reel mode selected For specifics on mounting the antenna coupler assembly refer to page 6 In dereel applications if the material breaks it may be pulled from the sensing field by the...

Page 13: ...o a relay contact that closes when reel motor stop is required The Auto LED blinks to indicate the interlock is asserted and since the unit is temporarily in SETUP mode the JOG feature can be used Whe...

Page 14: ...antenna Limit lights lit when loop height exceeds control range Run light on when motor function is active AUTO or JOG Auto light on when unit is in the Auto mode reel motor is controlled by antenna i...

Page 15: ...is reached then press ENTER The ADJUST Up and Down keys allow the speed to be fine tuned Pressing any other key than ADJUST Up or Down disables this function AUTO Ensure that your line is operational...

Page 16: ...specifics on mounting the antenna coupler assembly refer to page 6 In dereel applications if the material breaks it may be pulled from the sensing field by the machine processing the material This wi...

Page 17: ...nnect the motor field wires to terminals 6 and 7 once again be sure to observe the polarity of the terminals and your field wires Modification 04A060 must be installed on any RC4000M Reel Control that...

Page 18: ...antenna Limit lights lit when loop height exceeds control range Run light on when motor function is active AUTO or JOG Auto light on when unit is in the Auto mode reel motor is controlled by antenna...

Page 19: ...is reached then press ENTER The ADJUST Up and Down keys allow the speed to be fine tuned Pressing any other key than ADJUST Up or Down disables this function AUTO Ensure that your line is operational...

Page 20: ...n problem We also make a full range of inductive ring sensors For price and delivery call our sales department or the regional distributor listed below Don t forget our Five Year Guarantee it comes wi...

Reviews: