6

Operation on 208 Volt Supply

The unit transformer is factory connected for 230 V operation.  If 

unit is to operate on 208 V, disconnect the red wire from terminal 

3 of the unit transformer and connect them to terminal 2 of the 

unit transformer.

24 Volt Thermostat Wiring

NOTE:

  Removable connectors are provided with the control 

to make thermostat wire connections. The connectors may be 

removed, wire connections made and the connector replaced. It is 

STRONGLY

 recommended that you do not connect multiple wires 

into a single terminal. Wire nuts are recommended to ensure one 

wire is used for each terminal. Typical 18 AWG thermostat wire may 

be used to wire the system components. 150 feet is the maximum 

recommended length of wire recommended between indoor and 

outdoor unit, or between indoor unit and thermostat.

NOTE: 

Wire routing must not interfere with the circulator blower 

operation or routine maintenance.

CoolCloud™ HVAC Phone Application

NOTE

: This equipment has been tested and found to comply with 

the limits for a Class B digital device, pursuant to part 15 of the FCC 

Rules. These limits are designed to provide reasonable protection 

against harmful interference in a residential installation. This equip

-

ment generates, uses and can radiate radio frequency energy and, 

if not installed and used in accordance with the instructions, may 

cause harmful interference to radio communications. However, 

there is no guarantee that interference will not occur in a particular 

installation. If this equipment does cause harmful interference to 

radio or television reception, which can be determined by turning 

the equipment off and on, the user is encouraged to try to correct 

the interference by one or more of the following measures:

—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit different 

from that to which the receiver is connected.

—Consult the dealer or an experienced radio/ TV technician 

for help.

Actual screens may look different based on the mobile device 

being used.

   

Figure 7

This air handler is Bluetooth ready and functions with the Cool

Cloud HVAC phone application designed to improve the

contractor’s setup / diagnostic experience. Users can see specific

model information, review active diagnostic error codes, observe

system menu testing of all operational modes (heat / cool / fan)

directly from the phone. The phone application is also capable of

directly updating the air handler software anytime updates are

available. The application will automatically notify the user.

NOTE: 

The software update may take up to 20 minutes to

complete.

Quick Start Guide for Communicating Outdoor Units

EXTREMELY IMPORTANT: For all cooling calls the system only

requires a single Y input from the thermostat. For all heating

calls (including applications with backup electric heater kits) the

system only requires a single W input from the thermostat.

Internal algorithms will control all available cooling and heating

stages based on these inputs. Any single-stage 24VAC thermostat

can be used. For proper operation, the thermostat must be setup

to control a single stage AC outdoor unit and to control single

stage electric heat operation. The control board does not

accommodate an O wire thermostat input (reversing valve signal).

If a heat pump is installed, the thermostat should be setup as

stated above. Setting the thermostat for the heat pump control

or multistage control may result in incorrect performance.

1.   Connect all necessary thermostat wires to the thermostat 

connector on the air handler control as instructed by the 

applicable wiring diagrams shown in this section.

2.   Connect the 1 & 2 wires between the indoor and outdoor 

unit for communicating operation.

 Note:

  Verify  two  stage  outdoor  units  include  a  24VAC 

transformer (for outdoor control board power). Two stage 

outdoor units may not behave properly without this 24 VAC 

transformer.

Summary of Contents for MBVC 1 Series

Page 1: ...MENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR...

Page 2: ...edobjects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discharge your body to ground before removing a new control from its container Follow st...

Page 3: ...ons Internal algorithms will provide 2 stage or inverter Air Conditioner or Heat Pump functionality based on these simple inputs With built in Bluetooth operation the CoolCloud HVAC phone appli cation...

Page 4: ...f the blower cabinet Figure 3 NOTE All panels should be in place when installing the unit NOTE Supply ductwork for counterflow applications must be Class I However if combustible ductwork is used shee...

Page 5: ...disconnected during shipping and handling 208 230 Volt Line Connections If heater kits will not be installed remove the proper size knockout for the electrical conduit connection Connect electrical c...

Page 6: ...et on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Actual screens may look different based on the mobile device be...

Page 7: ...show Release the RECAL button 7 Press and hold the RECALL button again for another 5 seconds the 7 Segment display should show Release the RECALL button 8 Press and hold BOTH the RECALL AND TEST butt...

Page 8: ...he system has already terminated charge mode Pressing the LEARN button will exit the menus If after pressing the RECALL button at step 8 the 7 Segment displays still show press RECALL to change the di...

Page 9: ...e stage Heat Pumps for two stage Air Conditioners and for 2 stage Heat Pumps 4 Go to the Tonnage Units Menu and select the tonnage valuethatcorrespondstothedesiredairflowfortheoutdoor unit See the fol...

Page 10: ...or the thermostat energizes this terminal when dehumidifcation is required set the control board Dehum Logic Menu to using the push buttons or CoolCloud HVAC phone application If the humidistat opens...

Page 11: ...ermostatto ensureGsignal isenergized during accessory operation Figure 15 4 Select the appropriate fan only airflow for the accessory using the indoor unit push button menus or the CoolCloud HVAC phon...

Page 12: ...in a person s hand during grounding will be discharged 3 Service integrated control module or connecting wiring following the discharge process in step 2 Use caution not to recharge your body with sta...

Page 13: ...disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten or co...

Page 14: ...necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module High or...

Page 15: ...Airflow Trim default 0 Cooling Airflow Profile setting default profile D shown as 4 Cooling Airflow On Delay Time default 5 seconds Cooling Airflow Off Delay Time default 60 seconds Percentage of hig...

Page 16: ...the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low stag...

Page 17: ...nits Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non comm...

Page 18: ...r kit size See Menu Navigation and Selection Instructions above Default selection is 0 No Heat Kit Select installed heater kit for heater kit operation NR Not Rated Electric Heat Airflow Table Menu Na...

Page 19: ...ACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C USE COPPER CONDUCTORS ONLY 4 UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N E C AND LOCAL CODES 5 TO REC...

Page 20: ...and drain pan tab lets contain corrosive chemicals that can be harmful to aluminum tube and fin evaporator coils Even a one time application of these corrosive chemicals can cause premature aluminum...

Page 21: ...21 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 22: ...22 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 23: ...23 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 24: ...p www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA...

Reviews: