TROUBLESHOOTING MATRIX

Symptoms of Abnormal 

Operation 

Diagnostic 

/ Status 

LED Codes

Fault Description

Possible Causes

Corrective Actions

No outdoor unit operations



Communication error 
with outdoor unit

Improper low voltage wiring 
between the indoor and 
outdoor unit

Outdoor control board lost 
power duirng operation

Locate and correct improper low 
voltage wiring issue

Identify reason outdoor control 
board lost power during operation

No Air Handler operation



Open fuse

Short in low voltage wiring

Locate and correct short in low 
voltage wiring

Replace fuse with 3-amp automotive 
type

No Air Handler operation



Auxiliary switch 
(condensate switch) 
open or open fuse

High water level in the 
evaporation coil or short in 
low voltage wiring

Check evaporator drain pan, trap, 
piping

Replace fuse with 3-amp automotive 
type

No Air Handler operation



Data not yet on network

No network data

Populate shared data set using 
memory card

No Air Handler operation



Invalid memory card data

Air Handler blower does not 
contain an appropriate shared 
data set

Populate correct shared data using 
memory card

Operation different than expected 
or no operation



Invalid memory card data

Shared data set on memory 
card has been rejected by 
integrated control module

Verify shared data set is correct for 
the specifc model. Re-populate data 
using correct memory card if required

No Air Handler operation



Circulator blower motor 
not running with demand 
present

Loose or disconnected wiring 
connection at circulator 
motor power leads

 Open circuit in inductor or 
loose wiring connection at 
inductor (3/4 Hp and 1 Hp 
models only)

Failed circulator blower motor

Tighten or correct wiring connection

Verify continuous circuit through 
inductor.

Replace if open or short circuit

Check circulator blower motor

No Air Handler operation



Integrated control 
module has lost 
communications with 
circulator blower motor

Loose wiring connection at 
circulator motor control leads

Failed circulator blower motor

Failed integrated control 
module

Tighten or correct wiring connection

Check circulator blower motor, 
replace if necessary

Check integrated control module, 
replace if necessary

No Air Handler operation



Circulator blower motor 
horse power in shared 
data set does not match 
circulator blower motor 
horse power

Incorrect circulator blower 
motor in Air Handler

Incorrect shared data set in 
integrated control module

Verify circulator blower if motor 
horse power is the same specifed for 
the specifc Air Handler model, 
replace if necessary

Verify shared data set is correct for 
the specifc model, re-populate data 
using correct memory card if required

Air Handler operates at reduced 
performance

Airfow delivered is less than 
expected



Circulator blower motor 
is operating in a power, 
temperature, or speed 
limiting condition

Blocked flters

Restrictive or undersized 
ductwork

High ambient temperatures

Check filters for blockage, clean 
flters or remove obstruction

Check ductwork for blockage, 
remove obstruction and verify all 
registers are fully open

Verify ductwork is appropriately sized 
for system and resize/replace ass 
needed

Summary of Contents for MBVC 1 Series

Page 1: ...MENT THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR...

Page 2: ...edobjects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discharge your body to ground before removing a new control from its container Follow st...

Page 3: ...ons Internal algorithms will provide 2 stage or inverter Air Conditioner or Heat Pump functionality based on these simple inputs With built in Bluetooth operation the CoolCloud HVAC phone appli cation...

Page 4: ...f the blower cabinet Figure 3 NOTE All panels should be in place when installing the unit NOTE Supply ductwork for counterflow applications must be Class I However if combustible ductwork is used shee...

Page 5: ...disconnected during shipping and handling 208 230 Volt Line Connections If heater kits will not be installed remove the proper size knockout for the electrical conduit connection Connect electrical c...

Page 6: ...et on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Actual screens may look different based on the mobile device be...

Page 7: ...show Release the RECAL button 7 Press and hold the RECALL button again for another 5 seconds the 7 Segment display should show Release the RECALL button 8 Press and hold BOTH the RECALL AND TEST butt...

Page 8: ...he system has already terminated charge mode Pressing the LEARN button will exit the menus If after pressing the RECALL button at step 8 the 7 Segment displays still show press RECALL to change the di...

Page 9: ...e stage Heat Pumps for two stage Air Conditioners and for 2 stage Heat Pumps 4 Go to the Tonnage Units Menu and select the tonnage valuethatcorrespondstothedesiredairflowfortheoutdoor unit See the fol...

Page 10: ...or the thermostat energizes this terminal when dehumidifcation is required set the control board Dehum Logic Menu to using the push buttons or CoolCloud HVAC phone application If the humidistat opens...

Page 11: ...ermostatto ensureGsignal isenergized during accessory operation Figure 15 4 Select the appropriate fan only airflow for the accessory using the indoor unit push button menus or the CoolCloud HVAC phon...

Page 12: ...in a person s hand during grounding will be discharged 3 Service integrated control module or connecting wiring following the discharge process in step 2 Use caution not to recharge your body with sta...

Page 13: ...disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten or co...

Page 14: ...necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module High or...

Page 15: ...Airflow Trim default 0 Cooling Airflow Profile setting default profile D shown as 4 Cooling Airflow On Delay Time default 5 seconds Cooling Airflow Off Delay Time default 60 seconds Percentage of hig...

Page 16: ...the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low stag...

Page 17: ...nits Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non comm...

Page 18: ...r kit size See Menu Navigation and Selection Instructions above Default selection is 0 No Heat Kit Select installed heater kit for heater kit operation NR Not Rated Electric Heat Airflow Table Menu Na...

Page 19: ...ACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C USE COPPER CONDUCTORS ONLY 4 UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N E C AND LOCAL CODES 5 TO REC...

Page 20: ...and drain pan tab lets contain corrosive chemicals that can be harmful to aluminum tube and fin evaporator coils Even a one time application of these corrosive chemicals can cause premature aluminum...

Page 21: ...21 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 22: ...22 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 23: ...23 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 24: ...p www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA...

Reviews: