Goodman GCV9 Series Installation Instructions Manual Download Page 33

33

Outdoor fan and compressor are energized to their
appropriate speed.

Circulator blower is energized on the appropriate cool speed
at the level and time determined by the selected ramping
profile.  Electronic air cleaner terminals are energized with
circulator blower.

Furnace circulator blower and outdoor cooling unit run their
appropriate speed, integrated control module monitors safety
circuits continuously.

R and YLO/G or Y/G thermostat contacts open, completing
the call for cool.

Outdoor fan and compressor are de-energized.

Circulator blower continues running during a cool off delay
period.  The OFF delay time and airflow level are determined
by the selected ramping profile.

Electronic air cleaner terminals and circulator blower are de-
energized.

Furnace awaits next call from thermostat.

F

AN

 O

NLY

 M

ODE

The normal operational sequence in fan only mode is as follows:

R and G thermostat contacts close, initiating a call for fan.

Integrated control module performs safety circuit checks.

Circulator blower is energized on continuous fan speed (56%
of high stage cooling) following a five (5) second delay.
Electronic air cleaner terminals are energized.

Circulator blower runs, integrated control module monitors
safety circuits continuously.

R and G thermostat contacts open, completing the call for
fan.

Circulator blower is de-energized.  Electronic air cleaner
terminals are de-energized.

Furnace awaits next call from thermostat.

XVI. OPERATIONAL CHECKS

B

URNER

 F

LAME

The burner flames should be inspected with the burner compart-
ment door installed.  A sight glass is provided for inspection pur-
poses.  Flames should stable, quiet, soft, and blue (dust may cause
orange tips but they must not be yellow).  Flames should extend
directly outward from the burners without curling, floating, or lifting
off.  Flames must not impinge on the sides of the heat exchanger
firing tubes.

Check the burner flames for: 
1. Good adjustment
2. Stable, soft and blue 
3. Not curling, floating, or lifting off. 

Burner Flame

XVII. SAFETY CIRCUIT DESCRIPTION

G

ENERAL

A number of safety circuits are employed to ensure safe and proper
furnace operation.  These circuits serve to control any potential safety
hazards and serve as inputs in the monitoring and diagnosis of ab-
normal function.  These circuits are continuously monitored during
furnace operation by the integrated control module.

I

NTEGRATED

 C

ONTROL

 M

ODULE

The integrated control module is an electronic device which, if a
potential safety concern is detected, will take the necessary precau-
tions and provide diagnostic information through an LED.

P

RIMARY

 L

IMIT

The primary limit control is located on the partition panel and moni-
tors heat exchanger compartment temperatures.  It is a normally-
closed (electrically), automatic reset, temperature-activated sensor.
The limit guards against the overheating as a result of insufficient
conditioned air passing over the heat exchanger.

A

UXILIARY

 L

IMIT

The auxiliary limit controls  are located on or near the circulator
blower and monitors blower compartment temperatures.  They are
a normally-closed (electrically), manual-reset sensors.  These limits
guard against overheating as a result of insufficient conditioned air
passing over the heat exchanger.

R

OLLOUT

 L

IMIT

The rollout limit controls are mounted on the burner/manifold as-
sembly and monitor the burner flame.  They are normally-closed
(electrically), manual-reset sensors.  These limits guard against
burner flames not being properly drawn into the heat exchanger.

P

RESSURE

 S

WITCHES

The pressure switches are normally-open (closed during operation)
negative air pressure-activated switches.  They monitor the airflow
(combustion air and flue products) through the heat exchanger via
pressure taps located on the induced draft blower and the coil front
cover.  These switches guard against insufficient airflow (combus-
tion air and flue products) through the heat exchanger and/or blocked
condensate drain conditions.

F

LAME

 S

ENSOR

The flame sensor is a probe mounted to the burner/manifold as-
sembly which uses the principle of flame rectification to determine
the presence or absence of flame.

XVIII. TROUBLESHOOTING

E

LECTROSTATIC

 D

ISCHARGE

 (ESD) P

RECAUTIONS

NOTE:

  Discharge body’s static electricity before touching unit.  An

electrostatic discharge can adversely affect electrical components.

Use the following precautions during furnace installation and ser-
vicing to protect the integrated control module from damage.  By
putting the furnace, the control, and the person at the same electro-
static potential, these steps will help avoid exposing the integrated
control module to electrostatic discharge.  This procedure is appli-
cable to both installed and uninstalled (ungrounded) furnaces.

1. Disconnect all power to the furnace.  Do not touch the

integrated control module or any wire connected to the control
prior  to discharging your body’s electrostatic  charge to
ground.

2. Firmly touch a clean, unpainted, metal surface of the furnaces

near the control.  Any tools held in a  person’s hand during
grounding will be discharged.

3. Service integrated control module or connecting wiring

following the discharge process in step 2.  Use caution not to

Summary of Contents for GCV9 Series

Page 1: ...han when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of co...

Page 2: ...ES 12 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 13 STANDARD FURNACE CONNECTIONS 13 ALTERNATE FURNACE CONNECTIONS 14 NON DIRECT VENT SINGLE PIPE PIPING 16 DIRECT VENT DUAL PIPE PIPING 17 V...

Page 3: ...cuit Description 33 GENERAL 33 INTEGRATED CONTROL MODULE 33 PRIMARY LIMIT 33 AUXILIARY LIMIT 33 ROLLOUT LIMIT 33 PRESSURE SWITCHES 33 FLAME SENSOR 33 XVIII Troubleshooting 33 ELECTROSTATIC DISCHARGE E...

Page 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty certificate in a safe location for future reference If additional informatio...

Page 5: ...itch 24 Inductor Not All Models 25 Two Stage Integrated Control Module with fuse and diagnostic LED 26 24 Volt Thermostat Connections 27 Transformer 40 VA 28 ECM Variable Speed Circulator Blower 29 Au...

Page 6: ...ion are replaced The input rate and temperature rise are set per the furnace rating plate The input rate and temperature rise are set per the furnace rating plate 100 outside air is provided for combu...

Page 7: ...ems Do not install the furnace where the combustion air is exposed to the following substances chlorinated waxes or cleaners chlorine based swimming pool chemicals water softening chemicals deicing sa...

Page 8: ...rrected Corrections must be in accordance with the latest edition of the Na tional Fuel Gas Code NFPA 54 ANSI Z223 1 and or CSA B149 In stallation Codes printing inks paint removers varnishes hydrochl...

Page 9: ...red a part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be pro vided with two permanent openings communicating directl...

Page 10: ...ree area in 5 3 3 consideration shall be given to the block ing effect of louvers grilles or screens protecting openings Screens used shall not be smaller than 1 4 inch mesh If the area through a desi...

Page 11: ...ed for the drain trap Additionally the appropriate downward piping slope must be maintained from the drain trap to the drain location Refer to Section X Condensate Drain Trap and Lines for further det...

Page 12: ...is the responsibility of the installer to follow the manufacturers recommendations and to verify that all vent flue piping and connec tors are compatible with furnace flue products Additionally it is...

Page 13: ...es should be made for minor expansion and contraction due to temperature variations For this reason particular care must be taken to secure piping when a long run is followed by a short offset of less...

Page 14: ...t flue and combustion air intake piping run vertically from the side of the cabinet NOTE Standard and alternate locations can be combined i e an installation may use the standard combustion air intake...

Page 15: ...tion refer to the following steps and the Alternate Combus tion Air Intake Location figure NOTE Counterflow unit instructions follow the upflow instructions 1 Remove and save the four screws securing...

Page 16: ...be in stalled on the inside and outside of the wall The wall penetration should be sealed with silicone caulking material In a basement installation the vent flue pipe can be run between joist spaces...

Page 17: ...er for construction of the vent flue and combustion air intake pipe systems of a direct vent dual pipe installation The number of elbows tabulated represents the number of elbows and or tees in each V...

Page 18: ...LEVEL Standard Horizontal Terminations Dual Pipe 24 MAX 3 MIN 24 MAX AIR INTAKE 90 MEDIUM RADIUS ELBOW 12 MIN ABOVE HIGHEST ANTICIPATED SNOW LEVEL Alternate Horizontal Vent Termination Dual Pipe SUPPO...

Page 19: ...d through the right or left side panel and into the drain trap secured to the outside of the cabinet NOTE Refer to Section X Condensate Drain Lines and Drain Trap Alternate Vent Flue Hose Connections...

Page 20: ...p 2 Secure drain trap to side panel at the mounting holes dimples or crosshairs on counterflow models located below the grommet drain holes 3 Attach PVC drain line to drain trap outlet with either a 9...

Page 21: ...NG ANY ELECTRICAL WIRING CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING WIRING...

Page 22: ...e Condensing Unit Single Stage Cooling Dehumidistat Optional NOTE To apply a single stage heating thermostat the thermostat selector jumper on the integrated Control module must be set on single stage...

Page 23: ...eaner 1 0 Amp maximum at 120 VAC Turn OFF power to the furnace before installing any accessories Follow the humidifier or air cleaner manufacturers instructions for locating mounting grounding and con...

Page 24: ...ring the gas supply pressure and manifold pressure are provided on the valve The gas valve has a manual ON OFF control located on the valve itself This control may be set only to the ON or OFF positio...

Page 25: ...opane gas leak Rust can reduce the level of odorant in propane gas Do not rely on your sense of smell Contact a local propane connection is 375 in lbs excessive over tightening may damage the gas valv...

Page 26: ...ng a pair of seamer pliers or seamer tongs NOTE Airflow area will be reduced by ap proximately 18 if duct flanges are not unfolded This could cause performance issues and noise issues WARNING EDGES OF...

Page 27: ...ds If the furnace is installed without filters the warranty will be voided On upflow units guide dimples locate the side return cutout locations Use a straight edge to scribe lines connecting the dimp...

Page 28: ...h an ignition device which automatically lights the burner Do not try to light the burner by hand 5 Move the furnace gas valve manual control to the OFF position 6 Wait five minutes then smell for gas...

Page 29: ...w 8 Remove regulator cover screw from the low LO outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure 9 Energize main M solenoi...

Page 30: ...t High Stage Heat Tap Model 390 520 715 930 600 800 1100 1430 840 920 1000 1080 1210 1325 1440 1555 A B C D 520 715 910 1170 800 1100 1400 1800 1125 1195 1265 1335 1620 1720 1820 1920 A B C D 520 715...

Page 31: ...to enhance cooling performance and increase comfort level The ramping profiles are selected using DIP switches 5 and 6 Refer to the following figure for switch positions and their corresponding taps...

Page 32: ...e monitors flame presence Gas valve will remain open only if flame is detected If the thermostat call is for low heat gas valve and induced draft blower will continue on low stage If the call is for h...

Page 33: ...etected will take the necessary precau tions and provide diagnostic information through an LED PRIMARY LIMIT The primary limit control is located on the partition panel and moni tors heat exchanger co...

Page 34: ...r leakage Check the outside termination and the connections at and internal to the furnace Heat exchanger Check for corrosion and or buildup within the heat exchanger passageways Burners Check for pro...

Page 35: ...9 Clean residue from furnace using a vacuum cleaner 10 Replace the parts removed in the previous steps in reverse order 11 Turn on electrical power and gas to furnace Check for leaks and proper unit...

Page 36: ...36...

Page 37: ...Inspect pressure switch hose Repair if necessary Inspect flue and or inlet air piping for blockage proper length elbows and termination Check drain system Correct as necessary Correct pressure switch...

Page 38: ...emove obstruction Check circulator blower speed and performance Correct speed or replace blower if necessary Check burners for proper alignment Check flue and air inlet piping for blockage proper leng...

Page 39: ...OLS SINGLE CONTROL ON 45 kBTU PK PINK PLUG CONNECTION BURNER COMPARTMENT BLOWER COMPARTMENT VT IGNITER 2 MANUFACTURER S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING PK YL 5 FLASHES FLAME SE...

Page 40: ...40 2004 2006 Goodman Manufacturing Company L P 2550 North Loop West Suite 400 Houston TX 77092 www goodmanmfg com...

Reviews: