Limitid indikator GWG - type GWD -issue 2
Part no. 15 382 57 b
11 / 12
WARRANTY
We guarantee that the product will function as intended and will not leak during
the legally specified period. The scope of our warranty is based on Section 8 of
our terms and conditions of delivery and payment.
TECHNICAL CHANGES
All the information contained in this assembly and operating manual is the result of product
testing and corresponds to the level of knowledge at the time of testing and the relevant
legislation and standards at the time of issue. We reserve the right to make technical changes
without prior notice. Errors and omissions excepted. All figures are for illustration purposes
only and may differ from actual designs.
FUNCTION CHECK
Upon electrical installation and within the
framework of the repetitive inspections, the
function of the GWG must be checked and
documented using a precision instrument. An
annual function check is recommended; this
check can be performed while filling the
tank/battery tank in combination with GWG and
the overfill prevention mechanism on the road
tanker. See OPERATION.
Limit indicators are safety devices, so they have to be tested at least every 10 years for their
correct functioning. This function check also includes a test of the deactivation and the
response time (≤ 1.5s) through immersion in liquid. The check is to be carried out using the
suitable test equipment. The check is to be documented.
If the determined response time is
> 1.5s, the GWG shall be replaced immediately.
Recurring FUNCTION CHECK
The safety equipment was subjected to a recurring FUNCTION CHECK and worked
correctly at that time.
Place, date
Specialised company (stamp, signature)